IM 1199

Installation

Front Panel

The display is standard for all sensors. The functional keys 

on the display include the setpoint adjustment buttons and the 

tenant override button, as well as a numerical display to view 

changes.

Setpoint Buttons 

:

When pressed, the setpoint will display for three to four 

seconds. When pressed again, the setpoint will change in one 

degree increments. It will only change within the setpoint 

range that was ordered.

Tenant Override Button 

:

When the override button is pressed for 3-5 seconds the 

tenant override function will be initiated per the MicroTech 

III controller. The amount of time that the unit will come out 

of the unoccupied mode and operate in the tenant override 

mode is adjustable at the unit controller. 

Numerical Display

The default display shows current temperature. When the 

up/down buttons are pushed, then the display will show and 

adjust the current setpoint and hold the display for 3 to 4 

seconds. The unit can also be set up to display setpoint only 

or for setpoint lockout. 

 

Figure 3: Front Panel Display  