Daikin DP5HM Installation Instructions Manual Download Page 4

4

Specification sheets can be found at

www.daikincomfort.com for Daikin brand products. Within 

the website, please select the residential or commercial 

products menu and then select the submenu for the type 

of product to be installed, such as air conditioners or heat 

pumps, to access a list of product pages that each contain 

links to that model’s specification sheet. The units are ETL 

listed and AHRI certified.

The information on the rating plate is in compliance with 

the FTC & DOE rating for single phase units. 

EPA Regulations

Important: The United States Environmental 

Protection Agency (EPA) has issued various 

regulations regarding the introduction and 

disposal of refrigerants in this unit. Failure 

to follow these regulations may harm the 

environment and can lead to the imposition of 

substantial fines. Because regulations may vary 

due to passage of new laws, we suggest a certified 

technician perform any work done on this unit. 

Should you have any questions please contact the 

local office of the EPA.

National Codes

This product is designed and manufactured to permit  

installation in accordance with National Codes. It is the 

installer’s responsibility to install the product in accordance 

with National Codes and/or prevailing local codes and 

regulations.

MAJOR COMPONENTS

The unit includes a hermetically sealed refrigerating system 

(consisting of a compressor, condenser coil, evaporator 

coil with flowrator), an indoor blower, a condenser fan and 

all necessary internal electrical wiring. The heat pump also 

includes a reversing valve, solenoid, defrost thermostat 

and control and loss of charge protection. The system 

is factory-evacuated, charged and performance tested. 

Refrigerant amount and type are indicated on rating plate.

INSTALLATION

Pre-Installation Checks

Before attempting any installation, the following points 

should be considered: 

• 

  Structural strength of supporting members

• 

  Clearances and provision for servicing

• 

  Power supply and wiring

•   Air duct connections

• 

  Drain facilities and connections

• 

  Location may be on any four sides of a home, 

manufactured or modular, to minimize noise 

Clearances and Accessibility

The unit is designed to be located outside the building with 

unobstructed condenser air inlet and discharge. Additionally, 

the unit must be situated to permit access for service and 

installation. Condenser air enters from three sides. Air 

discharges upward from the top of the unit. Refrigerant 

gauge connections are made on the right side of the 

unit as you face the compressor compartment. Electrical 

connections can be made either on the right, bottom or 

duct panel side of the unit. The best and most common 

application is for the unit to be located 12” from wall (4” 

minimum) with the connection side facing the wall.  This 

“close to the wall” application minimizes exposed wiring.

Close to the wall application assures free, unobstructed 

air to the other two sides. In more confined application 

spaces, such as corners provide a minimum 12” clearance 

on all air inlet sides. Allow 36” minimum for service access 

to the compressor compartment and controls. The top of 

the unit should be completely unobstructed. If units are to 

be located under an overhang, there should be a minimum 

of 48” clearance and provisions made to deflect the warm 

discharge air out from the overhang. See Figure 1 - Ground 

Level Installation below.

4”

MIN

12” MIN

36” MIN

(FOR SERVICE)

.

48” MIN

12” MIN

 

36” MIN

(FOR

SERVICE)

 

NOTE:  Roof overhang should be no more than 36”

Ground Level Installation

Figure 1

Unit location

Consider the effect of outdoor fan noise on conditioned 

space and any adjacent occupied space. It is 

recommended that the unit be placed so that condenser air 

discharge does not blow toward windows less than 25 feet 

away. 

The unit should be set on a solid, level foundation – 

preferably a concrete slab at least 4 inches thick. The 

slab should be above ground level and surrounded by 

a graveled area for good drainage. Any slab used as a 

unit’s foundation should not adjoin the building as it is 

possible that sound and vibration may be transmitted to 

the structure. For rooftop installation, steel or treated wood 

beams should be used as unit support for load distribution.

Summary of Contents for DP5HM

Page 1: ...contact your distributor or our website for the applicable Specification Sheets referred to in this manual WARNING Do not bypass safety devices Affix this manual and Users Information Manual adjacent to the unit ONLY PERSONNEL THAT HAVE BEEN TRAINED TO INSTALL ADJUST SERVICE MAINTENANCE OR REPAIR HEREINAFTER SERVICE THE EQUIPMENT SPECIFIED IN THIS MANUAL SHOULD SERVICE THE EQUIPMENT THE MANUFACTUR...

Page 2: ...AT AND SUBCOOLING 13 Checking Subcooling 13 Checking Superheat 14 Refrigerant Charge Check 14 Units with TXV Devices 14 ELECTRICAL HEAT INSTALLATION AND ADJUSTMENT 14 Heater Kit 14 MAINTENANCE 15 SERVICE 15 Inadequate Air Volume Through Indoor Coil 15 Outside Air into Return Duct 15 Undercharge 15 Poor Terminating Sensor contact 15 Malfunctioning Reversing Valve 12 15 REVERSING VALVE TROUBLESHOOTI...

Page 3: ...manufacturer for use with this unit Serious property damage personal injury reduced unit performance and or hazardous conditions may result from the use of such non devices WARNING HIGH VOLTAGE Disconnect all power before servicing or installing this unit Multiple power sources may be present Failure to do so may cause property damage personal injury or death WARNING Connecting unit ductwork to un...

Page 4: ... facilities and connections Location may be on any four sides of a home manufactured or modular to minimize noise Clearances and Accessibility The unit is designed to be located outside the building with unobstructed condenser air inlet and discharge Additionally the unit must be situated to permit access for service and installation Condenser air enters from three sides Air discharges upward from...

Page 5: ...ufficient structural support must be determined prior to locating and mounting the curb and package unit Curb insulation cant strips flashing and general roofing material are furnished by the contractor Curbing must be installed in compliance with the National Roofing Contractors Association Manual Construct duct work using current industry guidelines The duct work must be placed into the roof cur...

Page 6: ...ual Rigging Figure 4 CIRCULATING AIR AND FILTERS Airflow Conversion Units can easily be converted from horizontal to down discharge air flow delivery In down discharge or high static installations the installer should measure the total external static and review the blower performance charts before performing the installation In some installations it will be necessary to change the blower speed to...

Page 7: ... encouraged to use appropriately sized ducts based upon the CFM for your application unit s CFM If duct sizing through industry manuals or air duct calculators requires larger ducts than converter openings run larger duct size up to unit converter openings and reduce with a reducer duct fitting or transition right at the unit Plenum Application A suitable plenum or square duct must be constructed ...

Page 8: ...he voltage frequency and phase as shown on the rating plate All internal wiring in the unit is complete It is necessary to bring in the power supply to the contactor as shown on the unit wiring diagram which is supplied with each unit The low voltage wiring must be connected between the unit control panel and the room thermostat All exterior wiring must be within approved weatherproof conduit The ...

Page 9: ...mping down after an approximate 60 second delay 6 Slowly lower the cooling temperature until the unit starts The compressor blower and fan should now be operating Allow the unit to run 10 minutes make sure cool air is being supplied by the unit 7 Turn the temperature setting to the highest position stopping the unit The indoor blower will continue to run for approximately 60 seconds 8 Turn the the...

Page 10: ...and opens at 85 It warms the compressor crankcase thereby preventing liquid migration and subsequent compressor damage The insert type heater is self regulating It is connected electrically to the contactor L1 and L2 terminals 3 Condenser Motor This item is activated by the contactor during heating and cooling except during defrost and emergency heat operation 4 Compressor This item is activated b...

Page 11: ... function on the heating cycle as on the cooling cycle The TXVs also act as check valves to allow for the reverse of refrigerant flow The expansion devices are flowrator distributors and perform the same function on the heating cycle as on the cooling cycle The flowrator distributors also act as check valves to allow for the reverse of refrigerant flow When the heat pump is on the heating cycle th...

Page 12: ...volts 6 Using VOM check for voltage across fan terminals DF1 and DF2 on the board Should read line voltage 208 230 VAC indicating the relay is open in the defrost mode 7 Using VOM check for voltage across W W2 C terminals on the board Should read 24 volts 8 If not as above replace control board 9 Set thermostat to off position and disconnect power Remove jumper from defrost thermostat and replace ...

Page 13: ...CM blower motor has been preprogrammed for operation at 4 distinct air flow levels when operating in Cooling Heat Pump mode or Electric Heat mode These 4 distinct levels may also be adjusted slightly lower or higher if desired The adjustment between levels and the trim adjustments are made by changing the dip switch s either to an OFF or ON position See Appendix for Blower Performance Data tables ...

Page 14: ...tem at least 10 minutes to allow pressure to stabilize 2 Temporarily install thermometer on liquid small line near liquid line access fitting with adequate contact and insulate for best possible reading 3 Check subcooling and superheat System should have a subcooling and superheat within the range listed on the Design Superheat and Subcooling table a If subcooling and superheat are low adjust TXV ...

Page 15: ...tion pressure and excessive defrost cycling resulting in low heating output It may also cause false defrosting Undercharge An undercharged heat pump on the heating cycle will cause low discharge pressure resulting in low suction pressure and frost accumulation on the outdoor coil Poor Terminating Sensor contact The unit s defrost terminating sensor must make good thermal contact with the outdoor c...

Page 16: ...lve contains refrigerant gases at certain temperatures 2 The discharge line should be the same temperature after the valves discharge line 3 The true suction should be the same as the suction line after the valve If there is a 4 degree difference valve is leaking When stuck in the mid position part of the discharge gas from the compressor is directed back to the suction side resulting in excessive...

Page 17: ...ace the compressor c Low voltage connection c At compressor terminals voltage must be within 10 of nameplate volts when unit is operating d Capacitor weak open or shorted d Check capacitor If defective replace Low suction cool compressor a In Cooling Low indoor airflow a Iced evaporator coil In Heating Dirty outdoor coil defective defrost thermostat defective defrost control board outdoor fan not ...

Page 18: ...225 Plus 880 Plus 880 Plus 1 348 Plus 1 348 Minus 900 Minus 900 Minus 1 260 Minus 1 260 Normal 1 000 Normal 1 000 Normal 1 400 Normal 1 400 Plus 1 100 Plus 1 100 Minus 1 540 Plus 1 540 Minus 990 Minus 990 Minus 1 530 Minus 1 530 Normal 1 100 Normal 1 100 Normal 1 700 Normal 1 700 Plus 1 210 Plus 1 210 Plus 1 870 Plus 1 870 Minus 1 125 Minus 1 125 Minus 1 620 Minus 1 620 Normal 1 250 Normal 1 250 N...

Page 19: ...ff Off 1250 B On Off 1100 C Off On 1000 D On On 800 A Off Off 1800 B On Off 1700 C Off On 1400 D On On 1225 A Off Off 1800 B On Off 1700 C Off On 1400 D On On 1225 DP5HM24 DP5HM30 DP5HM42 DP5HM48 DP5HM36 CFM Output for DIP Switch Combinations 5 6 Cooling Heating MODEL SPEED TAP SWITCH 5 SWITCH 6 COOLING HP CFM A Off Off 1050 B On Off 950 C Off On 825 D On On 700 A Off Off 1250 B On Off 1100 C Off On 1000 D On On 800 ...

Page 20: ...2 34 51 47 SUPPLY 1 3 8 A RETURN POWER WIRE ENTRANCE 4 1 8 2 1 8 6 16 16 5 B B CONTROL WIRE ENTRANCE CONDENSATE DRAIN CONNECTION 3 4 NPT FEMALE 18 7 8 3 8 2 34 51 47 SUPPLY A RETURN 16 5 B CONTROL WIRE ENTRANCE CONDENSATE DRAIN CONNECTION 3 4 NPT FEMALE 18 7 8 SUCTION LIQUID PRESSURE PORT BEHIND PANEL 1 3 8 POWER WIRE ENTRANCE 4 1 8 2 1 8 6 16 B 3 8 MEDIUM CHASSIS DP5HM2441 DP5HM3041 LARGE CHASSIS...

Page 21: ...minum Indoor Coil Cleaning Qualified Servicer Only This unit is equipped with an aluminum tube evaporator coil The safest way to clean the evaporator coil is to simply flush the coil with water This cleaning practice remains as the recommended cleaning method for both copper tube and aluminum tube residential cooling coils An alternate cleaning method is to use one of the products listed in the te...

Page 22: ... Type NG Natural Gas LP Liquid Propane Residential Package Outdoor Section ELECTRICAL Supply Voltage Measure L1 and L2 Voltage L1 L2 Compressor Amps Condenser Fan Amps PRESSURES TEMPERATURES Suction Circuit Pressure Suction Line Temperature PSIG TEMP F Liquid Circuit Pressure Liquid Temperature PSIG TEMP F Outdoor Air Temperature Dry bulb Wet bulb DB F WB F SUPERHEAT SUBCOOLING SH SC Additional Ch...

Page 23: ...23 THIS PAGE IS LEFT INTENTIONALLY BLANK ...

Page 24: ...ly short process and entitles you to additional warranty protection except that failure by California and Quebec residents to register their product does not diminish their warranty rights The duration of warranty coverages in Texas differs in some cases For Product Registration please register by following this link https daikincomfort com owner support product registration You can also scan the ...

Reviews: