W1W2 G Y1 Y2
R
Y2
C
Y1
W1
G
W2
Furnace Integrated
Control Module
Thermostat
Two-Stage Heating
with
Two-Stage Cooling
(
(
Two-Stage Heating with Two-Stage Cooling
Thermostat Diagram
Single Stage Thermostat - Two-Stage Models
To use a single stage thermostat, move jumper located
to the left of the terminal strip labeled “Stage Delay” from
NONE to “5” or “10” minutes. This selection will cause
the control to run on low stage for the selected time (5
or 10 minutes) then shift to HIGH STAGE. This option
controls both cooling and heating modes. If the jumper
is not moved, only low-stage cool and low-stage heat
will operate.
5 MINUTE DELAY
PERIOD WITH
JUMPER IN THIS
POSITION
10 MINUTE DELAY
PERIOD WITH
JUMPER IN THIS
POSITION
Two-Stage Heating (timed) and Two-Stage Cooling
(timed)
with Single Stage Thermostat Diagram
Refer to the unit wiring diagram for electrical connections.
When installed, the unit must be electrically grounded in
accordance with local codes or in the absence of local
codes, with the National Electrical Code, ANSI/NFPA No.
70, and/or the CSA C22.1 Electrical Code. Ensure low
voltage connections are waterproof.
WARNING
T
O PREVENT PROPERTY D AMAGE OR SERIOUS PERSONAL INJURY D UE T O
FIRE OR EXPLOSION CAUSED BY A PROPANE GAS LEAK, INSTALL A GAS
DETECTING WARNING DEVICE.
I
F THE PROPANE GAS UNIT IS INSTALLED IN A N EXCAVATED AREA OR A
CONFINED SPACE, A WARNING DEVICE IS REQUIRED DUE T O:
•
P
ROPANE GAS IS HEAVIER THAN A IR AND ANY LEAKING GAS CAN
SETTLE IN ANY LOW AREAS OR CONFINED SPACES.
•
P
ROPANE GAS ODORANT MAY FADE, MAKING THE GAS UNDETECTABLE
EXCEPT WITH A WARNING DEVICE.
ELECTRICAL WIRING
Thermostat Location
Mount the thermostat approximately five feet above the
floor, in an area that has an inside, vibration-free wall
and has good air circulation.
Movement of air must not be obstructed by furniture,
door, draperies, etc. The thermostat must not be mounted
where it will be affected by drafts, hot or cold water pipes
or air ducts in walls, radiant heat from fireplace, lamps,
the sun, television, etc. Consult the Instruction Sheet
packaged with thermostat for mounting instructions.
Five ton models have two stages of heating and
two stages of mechanical cooling. Units which have
economizers may use thermostats with two or three
stages of cooling.
All other units have one stage of heating and one stage
of mechanical cooling. Units which have economizers
may use thermostats with one or two stages of cooling.
The units are designed for operation on 60 hertz current
and at voltages as shown on the rating plate. All internal
wiring in the unit is complete. It is necessary to bring in
the power supply to the contactor as shown on the unit
wiring diagram which is supplied with each unit. 24 volt
wiring must be connected between the unit control panel
and the room thermostat.
Thermostat Wiring - Single Stage Models
From
Unit
Single Stage Heating & Cooling Thermostat Diagram
Thermostat Wiring - Two Stage Models