background image

7

the furnace where the combustion air is exposed to the
following substances:

permanent wave solutions

cleaning solutions (such as perchloroethylene)

printing inks

chlorinated waxes or cleaners

paint removers

chlorine-based swimming pool chemicals

varnishes

water softening chemicals

hydrochloric acid

carbon tetrachloride

cements and glues

deicing salts or chemicals

halogen type refrigerants

antistatic fabric softeners for clothes dryers

 and masonry acid washing materials

Seal off a 

non-direct vent

 furnace if it is installed

near an area frequently contaminated by any of the
above substances.  This protects the 

non-direct vent

furnace from airborne contaminants. To ensure that
the enclosed 

non-direct vent

 furnace has an adequate

supply of combustion air, vent from a nearby
uncontaminated room or from outdoors.  Refer to
the 

Combustion and Ventilation Air Requirements

for details.

If the furnace is used in connection with a cooling coil
unit, install the furnace upstream or in parallel with the
cooling coil unit.  Premature heat exchanger failure will
result if the cooling unit is placed ahead of the furnace.
For vertical (upflow or downflow) applications, the
minimum cooling coil width shall not be less than
furnace width minus 1”.  Additionally, a coil installed
above an upflow furnace or under a counterflow
furnace may be the same width as the furnace or
may be one size larger than the furnace.  

Example:

a “C” width coil may be installed with a “B” width
furnace.

For upflow applications, the front of the coil and
furnace must face the same direction.

If the furnace is installed in a residential garage,
position the furnace so that the burners and ignition
source are located not less than 18 inches (457 mm)

a

bove the floor.  Protect the furnace from physical

damage by vehicles.

If the furnace is installed horizontally, ensure the access
doors are not on the “up/top” or “down/bottom” side
of the furnace.

Do not connect this furnace to a chimney flue that
serves a separate appliance designed to burn solid
fuel.

On Counterflow Installations, the air conditioning
coil must be downstream on the supply (positive)
side of the furnace heat exchanger.

Counterflow Installation over a noncombustible
floor. 

Before setting the furnace over the plenum

opening, ensure the surface around the opening is
smooth and level. A tight seal should be made
between the furnace base and floor by using a
silicone rubber caulking compound or cement grout.

Counterflow Installation over a combustible floor. 

If

installation over a combustible floor becomes necessary,
use an accessory subbase (see Specification Sheet
applicable for your model for details.)  A special accessory
subbase must be used for upright counterflow unit
installations over any combustible material including
wood. Refer to subbase instructions for installation
details. Follow the instructions with the subbase for
proper installation. Do not install the furnace directly
on carpeting, tile, or other combustible material other
than wood flooring. (

NOTE

: The subbase will not be

required if an air conditioning coil is installed between
the supply air opening on the furnace and the floor.)

POSITION*

SIDES

REAR

FRONT BOTTOM

FLUE

TOP

Upflow

0"

0"

3"

C

0"

1"

Horizontal

6"

0"

3"

C

0"

6"

C = If placed on combustible floor, floor MUST be wood only.

DM96VC MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS

(INCHES)

POSITION*

SIDES

REAR

FRONT BOTTOM

FLUE

TOP

Counterflow

0"

0"

3"

NC

0"

1"

Horizontal

6"

0"

3"

C

0"

6"

C = If placed on combustible floor, floor MUST be wood only.
NC = For installation on non-combustible floors only. A combustible subbase
         must be used for installations on combustible flooring.

DC96VC MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS

(INCHES)

TOP

BOTTOM

TOP

BOTTOM

Counterflow

Figure 1

C

LEARANCES

 

AND

 A

CCESSIBILITY

NOTES:

For servicing or cleaning, a 24” front clearance is required.

Unit connections (electrical, flue and drain) may necessitate
greater clearances than the minimum clearances listed above.

In all cases, accessibility clearance must take precedence
over clearances from the enclosure where accessibility
clearances are greater.

NOTES:

For servicing or cleaning, a 24” front clearance is required.

Unit connections (electrical, flue and drain) may necessitate
greater clearances than the minimum clearances listed above.

Summary of Contents for DM96VC

Page 1: ...ibutor or our website for the applicable Specification Sheet referred to in this manual TABLE OF CONTENTS SAFETY CONSIDERATIONS 3 SHIPPING INSPECTION 4 ELECTROSTATIC DISCHARGE ESD PRECAUTIONS 4 TO THE...

Page 2: ...BLESHOOTING 43 NORMAL SEQUENCE OF OPERATION 43 POWER UP 43 HEATING MODE 43 COOLING MODE 45 FAN ONLY MODE 45 OPERATIONAL CHECKS 45 SAFETY CIRCUIT DESCRIPTION 45 INTEGRATED CONTROL MODULE 45 PRIMARY LIM...

Page 3: ...IPMENT IF THE FURNACE ENVIRONMENT HAS THE POTENTIAL OF FREEZING THE DRAIN TRAP AND DRAIN LINE MUST BE PROTECTED THE USE OF ACCESSORY DRAIN TRAP HEATERS ELECTRIC HEAT TAPE AND OR RV ANTIFREEZE IS RECOM...

Page 4: ...ommages permanents au cerveau et meme la mort Cette ventilation est n cessaire pour viter le danger d intoxication au CO pouvant survenir si un appareil produisant du monoxyde de carbone continue de f...

Page 5: ...tions It must be installed per the installation instructions provided and per local and national codes It must be installed indoors in a building constructed on site It must be part of a ducted system...

Page 6: ...ow and the guidelines provided in the Combustion and Ventilation Air Requirements section when selecting a furnace location Centrallylocatethefurnacewithrespecttotheproposed or existing air distributi...

Page 7: ...ions the air conditioning coil must be downstream on the supply positive side of the furnace heat exchanger Counterflow Installation over a noncombustible floor Before setting the furnace over the ple...

Page 8: ...akage corrosion and other deficiencies which could cause an unsafe condition 3 As far as practical close all building doors and windows and all doors between the space in which the appliance s connect...

Page 9: ...rnace horizontally additional consideration must be given to the following FURNACE SUSPENSION If suspending the furnace from rafters or joists use 3 8 threaded rod and 2 x2 x1 8 angle iron as shown in...

Page 10: ...w c 6 0 w c None Gas Altitude Kit Orifice M anifold Pressure Pressure Switch Change 0 7000 1 LPM 08 supports both Honeywell and White Rodgers 2 stage valves N OT E In Canada gas furnaces are only cert...

Page 11: ...fied and may be installed as a non direct vent single pipe or direct vent dual pipe appliance A non direct vent installation requires only a vent flue pipe while a direct vent installation requires bo...

Page 12: ...own in this manual or in unheated areas must be insulated with 1 2 thick closed cell foam Inspect piping for leaks prior to installing insulation TERMINATION LOCATIONS NOTE Refer to Location Requireme...

Page 13: ...d to obtain a permit IPEX System 636 is a trademark of IPEX Inc Carefully follow the pipe manufacturers instructions for cut ting cleaning and solvent cementing PVC and or ABS The vent can be run thro...

Page 14: ...lockage ALTERNATE VENT FLUE LOCATION The alternate vent flue location is the large hole directly in line with the induced draft blower outlet To use the alternate vent flue location refer to the follo...

Page 15: ...llowing table for applicable length elbows and pipe diameter for construction of the vent flue pipe system of a non direct vent installation In addition to the vent flue pipe a single 90 elbow should...

Page 16: ...ings must be joined per material manufacturer s specifications to prevent separation and flue gas leaks Both Pipes Terminated Outside Structure 1 4 per foot min slope 6 MAX Field Supplied Drain Tee on...

Page 17: ...e insulation of the combustion air pipe may be required Use 1 2 thick closed cell foam insulation such as Armaflex or Insultube where required VENT FLUE AND COMBUSTION AIR PIPE TERMINATIONS The vent f...

Page 18: ...ain location must meet local and nation codes The drain line between furnace and drain location must maintain a 1 4 inch per foot downward slope toward the drain Do not trap the drain line in any othe...

Page 19: ...ow and secure with 1 clamp 5 Refer to Field Supplied Drain section for instructions on field supplied installed drain on outlet of furnace trap DRAIN EXITING LEFT SIDE 1 Install the 45 degree pipe hos...

Page 20: ...8 Locate hose 5 and cut 3 from the non grommet end Discard the section without the grommet 9 Insert the cut end of tube 5 through the lower cabinet drain hole 10 Connect hose 6 hose 5 using 100 elbow...

Page 21: ...m the right side requires re location of the trap to outside the cabinet Hose 4 x 3 Hose 5 Figure 27 DRAIN EXITING LEFT SIDE 1 Install a field supplied rubber coupling secured with a 1 1 4 clamp to en...

Page 22: ...100 elbow inserted and clamped in the vent drain elbow 2 Remove two 1 plugs from left side of cabinet 3 Draining the Collector Box Remove the cap from the left side of the collector box drain port bot...

Page 23: ...ect vent applications the cabinet opening to the junction box must be sealed air tight using either an UL approved bushing such as Heyco Liquid Tight or by applying non reactive UL approved sealant to...

Page 24: ...cool system This furnace is equipped with a 40 VA transformer to facilitate use with most cooling equipment Consult the wiring diagram located on the blower compartment door for further details of 11...

Page 25: ...nction is enabled during a combination call for cooling T Stat and dehumidification DEHUM Stat FOSSIL FUEL APPLICATIONS This furnace can be used in conjunction with a heat pump in a fossil fuel applic...

Page 26: ...enu 1 ON Humidifier is turned on with a heat demand 2 OFF Humidifier remains off relay never closes 3 IND Humidifier will cycle with humidification demand independent of heat demand This mode allows t...

Page 27: ...NS MUST BE PERFORMED BY A QUALIFIED INSTALLER OR SERVICE AGENCY This unit is configured for natural gas The appropriate manufacturer s propane gas conversion kit must be applied for propane gas instal...

Page 28: ...ere Use listed gas appliance connectors in accordance with their instructions Connectors must be fully in the same room as the furnace Protect connectors and semirigid tubing against physical and ther...

Page 29: ...48 kPa Isolate this unit from the gas supply piping system by closing its external manual gas shutoff valve before pressure testing supply piping system with test pressures equal to or less than 1 2 p...

Page 30: ...urn air chamber CHECKING DUCT STATIC NEVER ALLOW THE PRODUCTS OF COMBUSTION INCLUDING CARBON MONOXIDE TO ENTER THE RETURN DUCT WORK OR CIRCULATION AIR SUPPLY WARNING Refer to your furnace rating plate...

Page 31: ...that a sampling probe can be inserted into the airstream The access panel must be made to prevent air leaks when the furnace is in operation When the furnace is heating the temperature of the return...

Page 32: ...omfort products Air Cleaner Installation Location Maximum Heating Airflow Filter Media Dimensions Part Number Air Cleaner Family Side or bottom return 1200 CFM 16 in X 20 in x 5 AM11 1620 5 Side or bo...

Page 33: ...RE MEASUREMENT GAS PRESSURE TEST This test is to be used for field test mode only and it will allow gas valve pressure to be checked at 100 firing rate 1 If both FAULT RECALL and LEARN push buttons ar...

Page 34: ...leg or Honeywell VR9205 gas valve a field supplied hose barb fitting must be installed prior to making the hose connection If using the inlet pressure tap on the White Rodgers 36J54 gas valve then us...

Page 35: ...wise to decrease pressure Replace regulator cover screw 11 Turn off all electrical power and gas supply to the system 12 Remove the manometer hose from the hose barb fitting or outlet pressure tap 13...

Page 36: ...These blower speeds should be adjusted by the installer to match the installation requirements so as to provide the correct heating temperature rise and correct cooling CFM Use the dual 7 segment LED...

Page 37: ...demand for 30 seconds The motor then ramps to 100 of the required airflow Aone 1 minute OFF delay at 100 of the cooling airflow is provided 50 CFM 1 2 min 100 CFM 100 CFM 1 min OFF OFF Figure 51 Profi...

Page 38: ...must be connected as a traditional or non communicating system see Electrical Connections for wiring connections Model Tap Low Stage Cool High Stage Cool Low Stage Heat High Stage Heat A 403 596 422...

Page 39: ...t then sends the demand to the ECM motor The table below lists the various ComfortNet systems the operating mode and airflow demand source For example assume the system is an air conditioner matched w...

Page 40: ...n Furnace and Thermostat Figure 55 COMFORTNET COMPATIBLE FURNACE WITH NON COMFORTNET COMPATIBLE SINGLE STAGE AIR CONDITIONER Four wires are required between the furnace and thermostat Two wires are re...

Page 41: ...y s th e a p p lic a t io n s o ft w a re re vis io n ID E N T IF IC A T IO N Submenu Item User Modifiable Options Comments Heat Airflow Trim HT TRM 10 to 10 in 2 increments default is 0 Trims the he...

Page 42: ...FL A B C or D default is A Selects the airflow profile for the non communicating compatible single stage AC unit Cool ON Delay CL ON 5 10 20 or 30 seconds default is 5 seconds Selects the indoor blowe...

Page 43: ...codes possible causes and corrective actions FAULT RECALL SEQUENCE Only allowed in standby mode while display is showing ON Hold fault recall push button for 2 5 seconds until display is blank and th...

Page 44: ...r to repair Broken disconnected data wire s Furnace is installed as a legacy traditional system Check communications wiring data 1 data 2 wires Check wire connections at terminal block Verify furnace...

Page 45: ...Circulator blower is de energized Electronic air cleaner terminal is de energized Furnace awaits next call from thermostat OPERATIONAL CHECKS The burner flames should be inspected with the burner comp...

Page 46: ...MAINTENANCE WARNING DIAGNOSTIC CHART Refer to the Troubleshooting Chart in the back of this manual for assistance in determining the source of unit operational problems The dual 7 segment LED display...

Page 47: ...INDUCED DRAFT AND CIRCULATOR BLOWERS The bearings in the induced draft blower and circulator blower motors are permanently lubricated by the manufacturer No further lubrication is required Check moto...

Page 48: ...dd 5 Off Off Minus 5 On Off Add 10 Off On Minus 10 On On A Off Off B On Off C Off On D On On A Off Off B On Off C Off On D On On Disabled Off Enabled On Disabled Off Enabled On 25 Off Off 50 On Off 75...

Page 49: ...ALTERNATES WITH F L 0 b 1 b 6 1 2 b 9 L O b 7 F C 2 b 5 b 3 b 4 d 0 0140F01169 REV A C 1 HIGH STAGE HEAT PUMP HEAT P 1 P 2 E F AUXILIARY SWITCH OPEN P 1 O n E 4 H I INTERNAL CONTROL FAULT NO POWER NO...

Page 50: ...Call for Service icon illuminated ComfortNet thermostat scrolls Check Furnace message E0 Furnace lockout due to an excessive number of ignition retries 3 total LOCKOUT E0 Failure to establish fame Ca...

Page 51: ...rs and ductwork for blockage Clean flters or remove obstruction Check circulator blower speed and performance Correct speed or replace blower motor if necessary Check burners for proper alignment Chec...

Page 52: ...d improperly Blocked fue and or inlet air pipe blocked drain system or weak induced draft blower Incorrect pressure switch set point or malfunctioning switch contacts Loose or improperly connected wir...

Page 53: ...ontrol module has lost communications with circulator blower motor MOTOR COMM b1 Loose wiring connection at circulator motor control leads Failed circulator blower motor Failed integrated control modu...

Page 54: ...t scrolls Check Furnace message b7 MOTOR PARAMS b7 Furnace operates at reduced performance or Integrated control module LED display provides b9 error code b9 LOW ID AIRFLOW B9 Blocked filters Restrict...

Page 55: ...AMPS LIMIT CONTROL AUXILIARY AUTO RESET PK WARNING DISCONNECT TRANSFORMER 40 VA PU GY N NO 3 BR 4 UNIT MUST BE PERMANENTLY GROUNDED AND CONFORM TO N E C AND LOCAL CODES COLOR CODES 1 E SWITCH PRESSUR...

Page 56: ...e no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS 4 INSPECTION The state or local gas inspector of the side wall horizontally vented gas fueled equipment...

Reviews: