background image

10

airborne bacteria and spores. Periodic cleaning is necessary to 

prevent this build-up from plugging the drain.

STARTUP, ADJUSTMENTS, AND CHECKS

WARNING

HIGH VOLTAGE

To avoid personal injury or death due to 

electrical shock, bond the frame of this unit 

to the building electrical ground by use of 

the grounding terminal provided or other ac

-

ceptable means. Disconnect all power before 

servicing or installing this unit.

CAUTION

To prevent property damage or personal injury, Do not start 

the unit until all necessary pre-checks and test have been 

performed. 

WARNING

MOVING MACHINERY HAZARD!

To prevent possible personal injury or death, disconnect 

power to the unit and padlock in the “OFF” position before 

servicing fans.

Heating Startup

On new installations, or if a major component has been replaced, 

the operation of the unit must be checked.
Check unit operation as outlined in the following instructions. If 

any sparking, odors, or unusual sounds are encountered, shut off 

electrical power and recheck for wiring errors, or obstructions in 

or near the blower motors. 
The Startup, Adjustments, and Checks procedure provides a step-

by-step sequence which, if followed, will assure the proper startup 

of the equipment in the minimum amount of time. Air balancing 

of duct system is not considered part of this procedure. However, 

it is an important phase of any air conditioning system startup and 

should be performed upon completion of the Startup, Adjustments, 

and Checks procedure. The Startup, Adjustments, and Checks 

procedure at outside ambients below 55°F should be limited to 

a readiness check of the refrigeration system with the required 

final check and calibration left to be completed when the outside 

ambient rises above 55°F.

Temporary Heating Or Cooling

If the unit is to be used for temporary heating or cooling, a “Startup, 

Adjustments, and Checks” must first be performed in accordance 

with this manual. Damage or repairs due to failure to comply with 

these requirements are not covered under the warranty. 

After 

the 

machines are used for temporary heating or cooling, inspect the 

coils, fans, and motors for unacceptable levels of construction dust 

and dirt and install new filters.

Contractor Responsibility

The installing contractor must be certain that:

•  All supply and return air ductwork is in place, properly 

sealed, and corresponds with installation instructions.

•  All thermostats are mounted and wired in accordance 

with installation instructions.

•  All  electric  power,  all  gas,  hot  water  or  steam  line 

connections, and the condensate drain installation have 

been made to each unit on the job. These main supply 

lines must be functional and capable of operating all units 

simultaneously.

•  Clean Air filters are in place.

Roof Curb Installation Check

Inspect the roof curb for correct installation. The unit and curb 

assembly should be level. Inspect the flashing of the roof mounting 

curb to the roof, especially at the corners, for good workmanship. 

Also check for leaks around gaskets. Note any deficiencies in a 

separate report and forward to the contractor. 

Obstructions, Fan Clearance and Wiring

Remove any extraneous construction and shipping materials that 

may be found during this procedure.  Rotate all fans manually to 

check for proper clearances and that they rotate freely. Check for 

bolts and screws that may have jarred loose during shipment to the 

job site. Retighten if necessary. Re-tighten all electrical connections.

Field Duct Connections

Verify that all duct connections are tight and that there is no air 

bypass between supply and return.

Filter Section Check

Remove filter section access panels and check that filters are prop

-

erly installed. Note airflow arrows on filter frames.

Pre-startup Precautions

It is important to your safety that the unit has been properly 

grounded during installation. Check  ground lug connection in main 

control box for tightness prior to closing circuit breaker or discon

-

nect switch. Verify that supply voltage on line side of disconnect 

agrees with voltage on unit identification plate and is within the  

utilization voltage range as indicated in Appendix C Electrical Data.

System Voltage - 

That nominal voltage value assigned to a circuit 

or system for the purpose of designating its voltage class.

Nameplate Voltage - 

That voltage assigned to a piece of equip

-

ment for the purpose of designating its voltage class and for the 

purpose of defining the minimum and maximum voltage at which 

the equipment will operate. 

Utilization Voltage - 

The voltage of the line terminals of the equip

-

ment at which the equipment must give fully satisfactory perfor

-

mance. Once it is established that supply voltage will be maintained 

within the utilization range under all system conditions, check 

and calculate if an unbalanced condition exists between phases. 

Calculate percent voltage unbalance as follows: 

Summary of Contents for DFC Series

Page 1: ...on model shown in picture 20 ton model has 4 fans 15 ton model has 3 fans INSTALLATION INSTRUCTIONS 2022 19001 Kermier Rd Waller TX 77484 www daikincomfort com ONLY PERSONNEL THAT HAVE BEEN TRAINED TO...

Page 2: ...iance REPLACEMENT PARTS Ordering Parts When reporting shortages or damages or ordering repair parts give the complete unit model and serial numbers as stamped on the unit s nameplate Replacement parts...

Page 3: ...s 4 File the claim with the following supporting documents a Original Bill of Lading certified copy or indemnity bond b Original paid freight bill or indemnity in lieu thereof c Original invoice or ce...

Page 4: ...rface for service personnel should be provided As indicated on the unit data plate a minimum clearance of 36 to any combustible material is required on the furnace access side of the unit All combusti...

Page 5: ...d using industry guidelines The duct work must be placed into the roof curb before mounting the package unit Our full perimeter curbs include duct connection frames to be assembled with the curb Canti...

Page 6: ...uded in the unit base frame No other fork locations are approved WARNING To prevent possible equipment damage property damage personal injury or death the following bullet points must be observed when...

Page 7: ...ARNING HIGH VOLTAGE TO AVOID PROPERTY DAMAGE PERSONAL INJURY OR DEATH DUE TO ELECTRICAL SHOCK DO NOT TAMPER WITH FACTORY WIRING THE INTERNAL POWER AND CONTROL WIRING OF THESE UNITS ARE FACTORY INSTALL...

Page 8: ...LTAGE TERMINAL LOCATIONS NOTE Depending on the options installed the location of the components may vary in some models WARNING Failure of unit due to operation on improper line voltage or with excess...

Page 9: ...AWG wire may be required before entering thermostat sub base NOTE Refer to unit wiring diagrams for thermostat hookups CIRCULATING AIR AND FILTERS Ductwork The supply duct from the unit through a wal...

Page 10: ...d and corresponds with installation instructions All thermostats are mounted and wired in accordance with installation instructions All electric power all gas hot water or steam line connections and t...

Page 11: ...n by default Taps T1 and T2 are for low cool operation cooling stage 1 and Taps T3 to T5 are for high cool operation cooling stage 2 Taps T6 and T7 are for low heat operation heating stage 1 and taps...

Page 12: ...ed during heating stage 1 operation Do not move wires WH and BR to the same taps Move PURPLE PU wire from TB1 T3 to T4 or T5 to change blower speed during cooling stage 2 operation Do not move wires Y...

Page 13: ...heck ing superheat run the unit in cooling for 15 20 minutes or until refrigerant pressures stabilize Use the following guidelines and methods to check unit operation and ensure that the refrigerant c...

Page 14: ...ards check the power wiring for that motor and correct any leads that have been interchanged at the contactor or at the motor 7 With all safety devices closed the system will continue cooling operatio...

Page 15: ...E must be completely cleaned following the cleaning procedure This practice must also be performed during short shut down periods where corrosive deposits accumulate on the MCHE Cleaning Procedure Rel...

Page 16: ...should be increased depending on the level of dirt dust accumulation and the environment e g coastal areas with chlorides and salts or industrial areas with aggressive substances WARNING Field applie...

Page 17: ...2 0 4 7527 764 782 1 47 1 51 0 6 7247 805 821 1 55 1 58 0 8 6941 848 857 1 63 1 65 1 6620 892 893 1 72 1 72 1 2 6275 946 932 1 82 1 79 T6 T7 T8 T9 T5 T10 DFC1803DStandardStatic T1 T2 T3 T4 SpeedTap St...

Page 18: ...10162 1132 1061 3 37 3 16 1 10002 1152 1097 3 44 3 27 1 2 9806 1179 1132 3 52 3 38 0 2 10958 1088 1013 3 38 3 15 0 4 10701 1112 1038 3 45 3 22 0 6 10521 1140 1058 3 54 3 29 0 8 10359 1164 1089 3 61 3...

Page 19: ...0 89 0 88 0 4 8969 851 848 2 78 1 73 0 6 7516 814 811 0 93 0 93 0 6 8688 886 884 2 90 1 80 0 8 7185 852 849 0 97 0 97 0 8 8398 923 920 3 02 1 88 1 6864 887 885 1 01 1 01 1 8132 956 952 3 12 1 94 1 2...

Page 20: ...6 9153 954 897 2 27 2 13 0 8 8724 966 925 2 19 2 10 0 8 8974 988 942 2 35 2 24 1 8554 992 980 2 25 2 22 1 8814 1013 995 2 41 2 37 1 2 8298 1025 1027 2 33 2 33 1 2 8568 1045 1042 2 48 2 48 1 4 8015 10...

Page 21: ...1042 3 48 3 25 0 6 8911 930 878 2 11 1 99 0 6 10544 1144 1062 3 57 3 31 0 8 8724 966 925 2 19 2 10 0 8 10382 1168 1093 3 65 3 41 1 8554 992 980 2 25 2 22 1 10209 1190 1123 3 71 3 51 1 2 8298 1025 102...

Page 22: ...6 RPM1 RPM2 DDC BHP1 BHP2 RPM1 RPM2 DDC BHP1 BHP2 RPM1 RPM2 DDC BHP1 BHP2 RPM1 RPM2 DDC BHP1 BHP2 4200 683 665 13 0 04 0 01 762 747 16 0 11 0 14 850 845 20 0 32 0 34 928 929 23 0 51 0 53 4500 718 695...

Page 23: ...6 RPM1 RPM2 DDC BHP1 BHP2 RPM1 RPM2 DDC BHP1 BHP2 RPM1 RPM2 DDC BHP1 BHP2 RPM1 RPM2 DDC BHP1 BHP2 4200 683 665 13 0 04 0 01 762 747 16 0 11 0 14 850 845 20 0 32 0 34 928 929 23 0 51 0 53 4500 718 695...

Page 24: ...4 0 6 RPM1 RPM2 DDC BHP1 BHP2 RPM1 RPM2 DDC BHP1 BHP2 RPM1 RPM2 DDC BHP1 BHP2 RPM1 RPM2 DDC BHP1 BHP2 4200 689 688 17 1 72 0 41 761 770 20 1 89 0 54 836 838 22 1 77 0 60 994 948 27 2 26 0 81 4500 704...

Page 25: ...RPM1 RPM2 DDC BHP1 BHP2 RPM1 RPM2 DDC BHP1 BHP2 RPM1 RPM2 DDC BHP1 BHP2 RPM1 RPM2 DDC BHP1 BHP2 5600 881 830 35 0 98 0 93 937 886 36 1 12 1 06 990 947 38 1 26 1 21 1039 1000 39 1 41 1 37 6000 907 849...

Page 26: ...RPM1 RPM2 DDC BHP1 BHP2 RPM1 RPM2 DDC BHP1 BHP2 RPM1 RPM2 DDC BHP1 BHP2 RPM1 RPM2 DDC BHP1 BHP2 5600 881 830 35 0 98 0 93 937 886 36 1 12 1 06 990 947 38 1 26 1 21 1039 1000 39 1 41 1 37 6000 907 849...

Page 27: ...M1 RPM2 DDC BHP1 BHP2 RPM1 RPM2 DDC BHP1 BHP2 RPM1 RPM2 DDC BHP1 BHP2 RPM1 RPM2 DDC BHP1 BHP2 5600 775 789 22 0 86 0 88 842 861 24 0 99 1 04 889 918 27 1 14 1 21 938 985 30 1 31 1 41 6000 789 797 25 0...

Page 28: ...RE DROP SCFM 4500 5000 5500 6000 6500 7000 7500 8000 8500 9000 9500 10000 In WG 0 15 0 18 0 22 0 27 0 32 0 37 0 42 0 48 0 55 0 61 0 69 0 76 Airflow Pressure Drop of Downflow Economizer for 15 to 25 To...

Page 29: ...00 9 6 8 7 4 8 204 192 225 200 9 6 8 7 13 9 216 203 225 225 44 4 50 2 4 46 8 50 8 1 52 5 60 4 3 48 7 60 4 3 2 4 51 1 60 4 3 8 1 56 8 60 61 3 70 2 4 64 3 70 8 1 71 4 80 4 3 66 7 70 4 3 2 4 69 7 70 4 3...

Page 30: ...7 189 211 200 225 9 6 8 7 4 8 195 217 200 225 9 6 8 7 13 9 207 229 225 250 103 103 125 125 4 8 108 108 125 125 13 9 117 117 125 125 9 6 8 7 113 112 125 125 9 6 8 7 4 8 118 117 125 125 9 6 8 7 13 9 127...

Page 31: ...3 74 8 80 3 5 68 8 70 3 5 2 71 3 80 3 5 8 3 79 2 80 67 9 70 2 70 4 80 8 3 78 3 80 3 5 72 3 80 3 5 2 74 8 80 3 5 8 3 82 7 90 81 8 90 2 84 3 90 8 3 92 2 100 3 5 86 2 90 3 5 2 88 7 90 3 5 8 3 96 5 100 43...

Page 32: ...8 167 183 200 200 9 6 8 7 13 9 178 194 200 200 186 175 200 175 4 8 192 181 200 200 13 9 204 192 225 200 9 6 8 7 198 186 200 200 9 6 8 7 4 8 204 192 225 200 9 6 8 7 13 9 216 203 225 225 186 209 200 22...

Page 33: ...89 8 90 8 3 97 7 100 3 5 91 7 100 3 5 2 94 2 100 3 5 8 3 102 110 52 6 60 2 54 6 60 8 3 60 9 70 3 5 56 1 70 3 5 2 58 1 70 3 5 8 3 64 4 70 52 6 60 2 55 1 60 8 3 63 0 70 3 5 57 0 70 3 5 2 59 5 70 3 5 8...

Page 34: ...NSIONS VERTICAL DISCHARGE TOP VIEW 21 60 7 48 22 NOTE 15 ton models have 3 fans 20 ton models have 4 fans 25 ton models have 5 fans Model A B C D 15 Ton 133 7 8 88 1 2 51 11 16 5 5 32 20 Ton 25 Ton 13...

Page 35: ...ITIONAL DEVICES IN SERIES PLUG IN JUMPER PLUG AT THE LAST SAFETY DEVICE INSTALLED IF A THIRD PARTY SAFETY DEVICE IS FIELD INSTALLED CUT WIRE ON THE JUMPER PLUG AND WIRE IT IN SERIES WITH THE SAFETY CI...

Page 36: ...TAP AT THE FACTORY AND BLACK WIRES TO COM TERMINAL FOR 208V SUPPLY POWER MOVE RED WIRES FROM 240V TAP TO THE 208V TAP SEE CONTROL DIAGRAM FOR CONTROL TRANSFORMER LOW VOLTAGE CONNECTIONS OPTIONAL FACTO...

Page 37: ...ITIONAL DEVICES IN SERIES PLUG IN JUMPER PLUG AT THE LAST SAFETY DEVICE INSTALLED IF A THIRD PARTY SAFETY DEVICE IS FIELD INSTALLED CUT WIRE ON THE JUMPER PLUG AND WIRE IT IN SERIES WITH THE SAFETY CI...

Page 38: ...H VOLTAGE CONNECTIONS RED WIRES CONNECTED TO 240 460 575V TAP AT THE FACTORY AND BLACK WIRES TO COM TERMINAL FOR 208V SUPPLY POWER MOVE RED WIRES FROM 240V TAP TO THE 208V TAP ON BOTH TRANSFORMERS SEE...

Page 39: ...IES PLUG IN JUMPER PLUG AT THE LAST SAFETY DEVICE INSTALLED IF A THIRD PARTY SAFETY DEVICE IS FIELD INSTALLED CUT WIRE ON THE JUMPER PLUG AND WIRE IT IN SERIES WITH THE SAFETY CIRCUIT FOR HIGHER TORQU...

Page 40: ...CTED TO 240 460 575V TAP AT THE FACTORY AND BLACK WIRES TO COM TERMINAL FOR 208V SUPPLY POWER MOVE RED WIRES FROM 240V TAP TO THE 208V TAP ON BOTH TRANSFORMERS SEE CONTROL DIAGRAM FOR CONTROL TRANSFOR...

Page 41: ...ORMER LINE VOLTAGE CONNECTIONS V2 V1 TB1 AG TB1 ALM ALM CFS TB1 CFS TB1 XS2 TB1 XS2 RSS TB1 RSS TB1 XS2 TB1 LDS LDS TB1 XS2 TB1 AG TB1 CO2 CO2 VIN COM VOUT TB1 AG TB1 IAH TB1 XS2 VIN IAH COM VOUT 1 2...

Page 42: ...FOR CONTROL TRANSFORMER LOW VOLTAGE CONNECTIONS OPTIONAL FACTORY INSTALLED EQUIPMENT NOTES BC BLOWER CONTACTOR BM BLOWER MOTOR CB CIRCUIT BREAKER CC COMPRESSOR CONTACTOR CCH CRANKCASE HEATER CCX COMPR...

Page 43: ...ORMER LINE VOLTAGE CONNECTIONS V2 V1 TB1 AG TB1 ALM ALM CFS TB1 CFS TB1 XS2 TB1 XS2 RSS TB1 RSS TB1 XS2 TB1 LDS LDS TB1 XS2 TB1 AG TB1 CO2 CO2 VIN COM VOUT TB1 AG TB1 IAH TB1 XS2 VIN IAH COM VOUT 1 2...

Page 44: ...TAP ON BOTH TRANSFORMERS SEE CONTROL DIAGRAM FOR CONTROL TRANSFORMER LOW VOLTAGE CONNECTIONS FUSE BLOCKS ARE OPTIONAL FACTORY INSTALLED EQUIPMENT BK OR RD BK RD OR BK RD OR BK OR RD OR BK F1 F1 F1 F2...

Page 45: ...R LINE VOLTAGE CONNECTIONS V2 V1 TB1 AG TB1 ALM ALM CFS TB1 CFS TB1 XS2 TB1 XS2 RSS TB1 RSS TB1 XS2 TB1 LDS LDS TB1 XS2 TB1 AG TB1 CO2 CO2 VIN COM VOUT TB1 AG TB1 IAH TB1 XS2 VIN IAH COM VOUT 1 2 3 6...

Page 46: ...CONTROL DIAGRAM FOR CONTROL TRANSFORMER LOW VOLTAGE CONNECTIONS FUSE BLOCKS ARE OPTIONAL 1 2 4 3 BK OR RD BK RD OR BK RD OR BK OR RD F1 F1 F1 F2 F2 F3 F3 F3 POWER WIRING DIAGRAM DFC300 LINE VOLTAGE 20...

Page 47: ...47...

Page 48: ...48...

Page 49: ...49 THIS PAGE INTENTIONALLY LEFT BLANK...

Page 50: ...50 THIS PAGE INTENTIONALLY LEFT BLANK...

Page 51: ...51 THIS PAGE INTENTIONALLY LEFT BLANK...

Page 52: ...form on the following link https daikincomfort com contact us You can also scan the QR code on the right to be directed to the feedback page Our continuing commitment to quality products may mean a c...

Reviews: