40
Installation Manual 3P291714-7H
DCM601B51 intelligent Touch Manager
English
NOTE
The “Group No. setting” menu is not displayed when the intelligent Touch Manager is
not powered on. Power on the intelligent Touch Manager and wait for a while before
trying to operate the remote controller. The “Group No. setting” menu is not displayed
also when the intelligent Touch Manager is not communicating with the indoor units
normally. Make sure that the cables are connected correctly.
3.
Using the Up/Down buttons, select “Group No. setting (Group)” and press the Menu/
Enter button.
The current address setting is displayed.
<Step 3>
Group No. setting(Unit)
Return
Setting
Group No. setting
Group No. setting(Group)
4. Press the Menu/Enter button to release the current address setting.
The mode indication changes from “Setting” to “Release”. You are now ready to change
the DIII-NET address.
<Step 4>
Group No
Set
1-00
Return
Release
Group No. setting(Group)
5. Using the Up/Down buttons, select the address you want to set.
<Step 5>
Group No
Release
1-00
Return
Change
Group No. setting(Group)
6. Press the Menu/Enter button.
The DIII-NET address has been set.
<Step 6>
Group No
Set
1-03
Return
Release
Group No. setting(Group)