18
Installation Manual 3P291714-7H
DCM601B51 intelligent Touch Manager
English
<DIII MASTER>
To set the intelligent Touch Manager to SLAVE, use
the DIII MASTER switch located under the front slide
cover. Placing the DIII MASTER switch in the upper
position (labeled as “SLAVE”) changes it to a SLAVE.
To install multiple centralized controllers, set only the highest priority controller to MAS-
TER and all other controllers to SLAVE according to the following order of priority:
High
(1)
Interface for use in BACnet
(2) Interface for use in LONWORKS
(3)
intelligent Touch Manager (Main),
iTM plus adaptor (Main),
DGE601A51 (Main), DGE601A52 (Main), DGE601A53 (Main)
(4) Central Remote Controller (Main)
(5)
intelligent Touch Manager (Sub),
iTM plus adaptor (Sub),
DGE601A51 (Sub), DGE601A52 (Sub), DGE601A53 (Sub)
(6) Central Remote Controller (Sub)
(7) ON/OFF Controller (Main)
(8) ON/OFF Controller (Sub)
Priority
Low
Centralized con-
trollers that cannot
be installed in
parallel with intel-
ligent Touch Man-
ager
•
CALCULATE UNIT
• intelligent Processing Unit
• Parallel Interface
• Intelligent Touch Controller
•
DIII-NET Plus Adapter
• Residential Central Remote Controller
• Schedule Timer
•
Wiring Adaptor for Electrical Appendices (1) (KRP2)
2.3
Connecting a LAN cable
Connecting your intelligent Touch Manager with a PC network enables you to set up the
operation of air conditioning system or perform maintenance work on it from a remote
location.
WARNING
Do not clamp the cables with high-current lines such as a power cable.
NOTE
For how to connect the intelligent Touch Manager to a PC network, contact your net-
work administrator.