To assist in determining rigging requirements, unit weights are
shown as follows:
A
B
C
D
CG
SUPPLY
RETURN
EVAPORATOR COIL
CONDENSER
COIL
COMPRESSOR
Y
X
Corner & Center of Gravity Locations
A
B
C
D
DCG036045*
37
30
550
525
100
165
100
165
DCG036090*
37
30
560
535
100
170
100
170
DCG048090*
37
30
600
575
110
180
110
180
DCG048115*
37
30
605
580
110
180
110
180
DCG060090*
37
30
635
610
113
187
118
192
DCG060140*
37
30
645
620
118
192
118
192
DCG072140*
37
30
700
675
127
210
127
211
Operating
Weight
(lbs)
Corner Weights ( lbs )
* Weights shown are belt drive with no accessories.
Model
X
(in)
Y
(in)
Shipping
Weight
(lbs)
T
O
PREVENT
SEVERE
DAMAGE
TO
THE
BOTTOM
OF
THE
UNIT
,
DO
NOT
FORK
LIFT
UNIT
AFTER
WOOD
STRUTS
HAVE
BEEN
REMOVED
.
CAUTION
Bring condenser end of unit into alignment with the curb. With
condenser end of the unit resting on curb member and using curb
as a fulcrum, lower opposite end of the unit until entire unit is
seated on the curb. When a rectangular cantilever curb is used,
care should be taken to center the unit. Check for proper align-
ment and orientation of supply and return openings with duct.
R
IGGING
R
EMOVAL
T
O
PREVENT
DAMAGE
TO
THE
UNIT
,
DO
NOT
ALLOW
CRANE
HOOKS
AND
SPREADER
BARS
TO
REST
ON
THE
ROOF
OF
THE
UNIT
.
CAUTION
Remove spreader bars, lifting cables and other rigging equipment.
ELECTRICAL WIRING
HIGH VOLTAGE!
D
ISCONNECT
ALL
POWER
BEFORE
SERVICING
OR
INSTALLING
THIS
UNIT
. M
ULTIPLE
POWER
SOURCES
MAY
BE
PRESENT
. F
AILURE
TO
DO
SO
MAY
CAUSE
PROPERTY
DAMAGE
,
PERSONAL
INJURY
OR
DEATH
.
WARNING
HIGH VOLTAGE!
T
O
AVOID
PERSONAL
INJURY
OR
DEATH
DUE
TO
ELECTRICAL
SHOCK
,
DO
NOT
TAMPER
WITH
FACTORY
WIRING
. T
HE
INTERNAL
POWER
AND
CONTROL
WIRING
OF
THESE
UNITS
ARE
FACTORY
-
INSTALLED
AND
HAVE
BEEN
THOROUGHLY
TESTED
PRIOR
TO
SHIPMENT
.
C
ONTACT
YOUR
LOCAL
REPRESENTATIVE
IF
ASSISTANCE
IS
REQUIRED
.
WARNING
T
O
PREVENT
DAMAGE
TO
THE
WIRING
,
PROTECT
WIRING
FROM
SHARP
EDGES
. F
OLLOW
NATIONAL
ELECTRICAL
CODE
AND
ALL
LOCAL
CODES
AND
ORDINANCES
. D
O
NOT
ROUTE
WIRES
THROUGH
REMOVABLE
ACCESS
PANELS
.
CAUTION
C
ONDUIT
AND
FITTINGS
MUST
BE
WEATHER
-
TIGHT
TO
PREVENT
WATER
ENTRY
INTO
THE
BUILDING
.
CAUTION
For unit protection, use a fuse or HACR circuit breaker that is in
excess of the circuit ampacity, but less than or equal to the maxi-
mum overcurrent protection device. DO NOT EXCEED THE MAXI-
MUM OVERCURRENT DEVICE SIZE SHOWN ON UNIT DATA PLATE.
All line voltage connections must be made through weatherproof
fittings. All exterior power supply and ground wiring must be in
approved weatherproof conduit.
The main power supply wiring to the unit and low voltage wiring
to accessory controls must be done in accordance with these in-
structions, the latest edition of the National Electrical Code (ANSI/
NFPA 70), and all local codes and ordinances. All field wiring shall
conform with the temperature limitations for Type T wire (63°F/
35°C rise).
The unit is factory wired for the voltage shown on the unit’s data
plate. Refer to model nomenclature in Appendix B for voltage re-
quirement for your unit.
NOTE:
If supply voltage is 208V, lead on primary of transformer
must be moved from the 230V to the 208V tap. Refer to wiring
diagram on unit for details.
Main power wiring should be sized for the minimum wire ampacity
shown on the unit’s database. Size wires in accordance with the
ampacity tables in Article 310 of the National Electrical Code. If
long wires are required, it may be necessary to increase the wire
size to prevent excessive voltage drop. Wires should be sized for a
maximum of 3% voltage drop.