background image

3

LOW VOLTAGE WIRE HARNESS

HIGH VOLTAGE WIRE HARNESS

POWER EXHAUST ASSEMBLY

TO HV POWER BLOCK

ECONOMIZER

PULL WIRE HARNESSES

THRU WIRE GROMMET

Figure 2 – 3-6 Ton Power Exhaust Wiring

LOW VOLTAGE WIRE HARNESS

HIGH VOLTAGE WIRE HARNESS

POWER EXHAUST ASSEMBLY

TO HV POWER BLOCK

ECONOMIZER

PULL WIRE HARNESSES

THRU WIRE GROMMET

Figure 3 – 7½-12½ Ton Power Exhaust Wiring

5.  Plug the other end of the high voltage harness into 

the unit single point connection on the partition panel. 

(Fig. 4) 

Figure 4 - Single Point Connection

NOTE: If the unit is not equipped with single point 

connection, external power must be supplied to 

the power exhaust. DO NOT CONNECT TO UNIT 

POWER. Unit MCA and MOP calculated based on 

factory installed equipment, so components may 

not be sized appropriately. 

6.  Remove the unit control panel and securely terminate 

the single point connection leads to the unit power 

block (line side of compressor contactor on 3-6 ton 

DBG) and ground lug. Replace the unit control panel 

when complete. (Fig. 5) 

Figure 5 - Single Point Connection Leads 

Summary of Contents for DBC

Page 1: ...fely and to know it well enough to be able to instruct a customer in its safe use Safety is a matter of common sense a matter of thinking before acting Most dealers have a list of specific good safety...

Page 2: ...t 2 Cut a rectangular opening in the return air duct with the opening edge 36 inches from the horizontal return opening on the RTU Drill pilot holes around perimeter of opening using a 27 0 144 inch d...

Page 3: ...the unit single point connection on the partition panel Fig 4 Figure 4 Single Point Connection NOTE If the unit is not equipped with single point connection external power must be supplied to the powe...

Page 4: ...ure wiring harnesses are properly secured GASKET AROUND FLANGE SHEETMETAL SCREWS Figure 6 Power Exhaust Installed on Duct 5 Return power to unit and remove lockout tag For gas units turn on the gas su...

Page 5: ...0 HORIZONTAL RETURN AIR PANEL O 144 19 25 I D 18 00 I D 7 12 7 12 7 12 7 12 7 12 34 50 I D 16 75 I D 3 38 5 40 6 67 69 6 88 6 88 6 88 6 88 6 88 69 3 38 5 40 6 67 36 00 O 144 HORIZONTAL RETURN AIR PANE...

Page 6: ...Wiring Diagram Power Exhaust Propeller Non DDC 1PH 3PH 230V NOTE Wiring is subject to change Always refer to the unit wiring diagram and accessory wiring diagram booklet for the most up to date wirin...

Page 7: ...7 Wiring Diagram Power Exhaust Propeller Non DDC 3PH 460V NOTE Wiring is subject to change Always refer to the unit wiring diagram and accessory wiring diagram booklet for the most up to date wiring...

Page 8: ...form on the following link https daikincomfort com contact us You can also scan the QR code on the right to be directed to the feedback page Our continuing commitment to quality products may mean a c...

Reviews: