APPENDIX A BLOWER PERFORMANCE DATA
8.5 TON HP
DBH102*V STANDARD STATIC HORIZONTAL
CFM
RPM
BHP
CFM
RPM
BHP
CFM
RPM
BHP
CFM
RPM
BHP
CFM
RPM
BHP
CFM
RPM
BHP
0.1
4038
699
1.63
3759
656
1.37
3485
615
1.16
0.2
4161
743
1.83
3846
699
1.54
3559
655
1.29
3269
617
1.09
0.3
3969
743
1.74
3631
699
1.45
3334
659
1.20
3018
617
1.01
0.4
4075
788
1.94
3775
745
1.63
3428
704
1.35
3095
661
1.11
0.5
3883
788
1.83
3571
749
1.54
3194
704
1.26
2784
661
1.01
0.6
4017
832
2.08
3682
789
1.73
3340
749
1.43
2877
704
1.13
0.7
3806
832
1.96
3462
793
1.61
3039
749
1.30
0.8
3589
835
1.82
3170
793
1.47
DBH102*S HIGH STATIC HORIZONTAL
1
CFM
RPM
BHP
CFM
RPM
BHP
CFM
RPM
BHP
CFM
RPM
BHP
CFM
RPM
BHP
CFM
RPM
BHP
0.8
4012
943
2.53
3592
893
2.05
3125
842
1.62
0.9
3832
945
2.40
3366
895
1.93
1.0
4035
997
2.80
3645
948
2.27
3155
897
1.80
1.1
3833
998
2.65
3399
948
2.13
2881
897
1.68
1.2
4067
1044
3.06
3663
998
2.51
3235
950
2.01
1.3
3866
1047
2.90
3469
1001
2.38
2966
952
1.86
1.4
3720
1051
2.77
3273
1003
2.24
1.5
3527
1051
2.61
1.6
3826
1107
3.14
3320
1052
2.45
1.7
3664
1110
2.98
3188
1055
2.31
1.8
3471
1110
2.83
2797
1058
2.10
DBH102*V STANDARD STATIC DOWNSHOT
1
CFM
RPM
BHP
CFM
RPM
BHP
CFM
RPM
BHP
CFM
RPM
BHP
CFM
RPM
BHP
CFM
RPM
BHP
0.1
3933
610
1.29
0.2
4039
655
1.46
3658
611
1.20
0.3
4172
693
1.66
3763
655
1.35
3355
611
1.10
0.4
3914
698
1.54
3473
655
1.24
3006
612
0.99
0.5
4032
742
1.73
3629
698
1.42
3138
657
1.12
0.6
4169
787
1.95
3740
743
1.60
3287
699
1.28
0.7
3908
787
1.81
3428
743
1.46
2875
704
1.14
0.8
4038
832
2.05
3597
792
1.66
3071
748
1.32
DBH102*S HIGH STATIC DOWNSHOT
CFM
RPM
BHP
CFM
RPM
BHP
CFM
RPM
BHP
CFM
RPM
BHP
CFM
RPM
BHP
CFM
RPM
BHP
0.8
3841
837
1.98
0.9
4060
890
2.33
3532
840
1.82
1.0
3846
893
2.19
3253
843
1.67
1.1
4128
941
2.61
3521
893
2.00
1.2
3903
942
2.44
3223
895
1.83
1.3
3611
945
2.25
1.4
3904
994
2.67
3320
948
2.07
1.5
3643
998
2.48
1.6
3943
1042
2.94
3356
1002
2.28
1.7
3685
1046
2.74
3175
1004
2.11
1.8
4151
1102
3.49
3444
1053
2.56
ESP, In H
2
O
TURNS OPEN
0
1
2
3
4
5
2
3
4
5
ESP, In H
2
O
TURNS OPEN
0
1
2
3
4
5
1
To operate below 0.8" H
2
O external static pressure, motor and blower sheave must be changed to 1VL40 and AK794H respectively, or equivalents
1
To operate below 0.8" H
2
O external static pressure, motor and blower sheave must be changed to 1VL40 and AK794H respectively, or equivalents
ESP, In H
2
O
TURNS OPEN
0
1
2
3
4
5
ESP, In H
2
O
TURNS OPEN