19
APPENDIX A BLOWER PERFORMANCE DATA
7.5 TON AC
CFM
RPM
BHP
CFM
RPM
BHP
CFM
RPM
BHP
CFM
RPM
BHP
CFM
RPM
BHP
CFM
RPM
BHP
0.1
3636
652
1.11
3403
613
0.95
3165
600
0.74
0.2
3532
652
1.06
3193
613
0.87
2907
600
0.66
0.3
3654
692
1.17
3373
652
0.99
2983
613
0.78
2650
600
0.58
0.4
3748
732
1.24
3477
692
1.09
3161
652
0.90
2773
613
0.71
2392
600
0.51
0.5
3563
732
1.16
3251
692
0.99
2893
652
0.80
2563
613
0.63
0.6
3678
770
1.37
3345
732
1.06
2977
692
0.88
2572
652
0.68
2353
613
0.57
0.7
3465
770
1.26
3096
732
0.95
2656
692
0.76
0.8
3228
770
1.14
2815
732
0.84
2287
692
0.63
DBC090*V STANDARD STATIC HORIZONTAL
ESP, In H
2
O
TURNS OPEN
0
1
2
3
4
5
CFM
RPM
BHP
CFM
RPM
BHP
CFM
RPM
BHP
CFM
RPM
BHP
CFM
RPM
BHP
CFM
RPM
BHP
0.8
3444
838
1.26
0.9
3678
889
1.80
3228
840
1.16
1.0
3434
891
1.65
2984
842
1.04
1.1
3702
943
1.86
3162
895
1.49
2712
845
0.92
1.2
3467
944
1.71
2862
899
1.32
2412
849
0.80
1.3
3773
993
2.10
3216
945
1.56
2534
905
1.15
1.4
3542
996
1.94
2950
946
1.41
1.5
3737
1050
2.14
3297
1000
1.77
2668
947
1.26
1.6
3444
1053
1.93
3039
1003
1.61
2371
947
1.11
1.7
3125
1050
1.72
2767
1000
1.44
1.8
3732
1096
2.32
2781
1053
1.51
2481
1003
1.28
DBC090*S HIGH STATIC HORIZONTAL
1
ESP, In H
2
O
TURNS OPEN
0
1
2
3
4
5
1
To operate below 0.8" H
2
O external static pressure, motor and blower sheave must be changed to VL40 and AK84H respectively, or equivalents
CFM
RPM
BHP
CFM
RPM
BHP
CFM
RPM
BHP
CFM
RPM
BHP
CFM
RPM
BHP
CFM
RPM
BHP
0.1
3681
600
0.93
0.2
3708
613
0.94
3349
600
0.81
0.3
3773
652
1.17
3391
613
0.83
2986
600
0.69
0.4
3455
652
1.02
3037
613
0.71
2593
600
0.57
0.5
3574
692
1.13
3116
652
0.88
2645
613
0.59
0.6
3715
732
1.23
3236
692
0.98
2757
652
0.74
0.7
3403
732
1.08
2867
692
0.83
2376
652
0.61
0.8
3550
770
1.30
3068
732
0.94
2467
692
0.69
DBC090*V STANDARD STATIC DOWNSHOT
ESP, In H
2
O
TURNS OPEN
0
1
2
3
4
5
CFM
RPM
BHP
CFM
RPM
BHP
CFM
RPM
BHP
CFM
RPM
BHP
CFM
RPM
BHP
CFM
RPM
BHP
0.8
3676
1077
1.38
0.9
3391
1078
1.23
1.0
3708
1078
1.82
3017
1079
1.05
1.1
3347
1079
1.59
2556
1080
0.85
1.2
3586
1079
1.78
2908
1080
1.34
1.3
3287
1080
1.60
2391
1081
1.07
1.4
3539
1080
1.93
2973
1081
1.42
1.5
3175
1081
1.69
2645
1082
1.24
1.6
3690
1081
2.09
2777
1082
1.44
2302
1083
1.07
1.7
3426
1082
1.90
2347
1083
1.20
1.8
3745
1082
2.19
3152
1083
1.72
DBC090*S HIGH STATIC DOWNSHOT
1
1
To operate below 0.8" H
2
O external static pressure, motor and blower sheave must be changed to VL40 and AK84H respectively, or equivalents
ESP, In H
2
O
TURNS OPEN
0
1
2
3
4
5
Summary of Contents for DBC Series