Daikin DAFU-1000 Installation, Operation And Maintenance Manual Download Page 13

 Page 

1

3

 

of 

1

5

DAFU-IOM—01

UV Light   

1.

Make sure the unit is disconnected from power supply.

2.

Fan is not running and spinning.

3.

UV lamp can be accessed by removing the front panel

.

 

(Refer Access to internal components and Figure 5)

4.

Maintain lamps free of dust that diminishes the potency of ultraviolet 
emissions by wiping them every 

2-3

 months with a clean cloth.

5.

Avoid touching UV lamp surfaces. Fingerprints contain oil that 
diminishes UV output and may cause the lamp to heat unevenly.

HEPA Filter

1.

Make sure the unit is disconnected from power supply.

2.

Fan is not running and spinning.

3.

Filter can be easily accessed by removing the front panel (Refer Access to internal 

components and Figure 5)

.

4.

Loosen the four spring type nuts and bolts on the H

EPA 

filter 

f

rame. After

 

l

oosening the nuts,  the frame will move upward, and filter can be easily slide out. 

(Figure 7 & 6)

.

5.

Examine the filter frame and filter cabin for any contamination moisture or 

any dust particles

. C

lean with dry cloth.

6.

Slide out the contaminated filter

put in the bin bag and dispose properly.

7.

Do not touch or damage the filter media when inserting the new filters. 

Hold the filter by the media frame to avoid damage.

8.

For inserting 

HEPA 

filter in the frame, make sure that the spring

-

type nuts are 

loose, then insert filter and tighten the four nuts of the spring

 

bolts from top of 

the filter. 

EC FAN

1.

Make sure the unit is disconnected from power supply.

2.

Fan is not running and spinning.

3.

Fans can be easily accessed by removing the front panel

.

 (Refer Access to 

internal components and Figure 2)

4.

Remove the cables connected to 

the f

an 

p

ower 

and c

ontrol area

.

5.

EC Fan are 

s

pider

-m

ounted on 

f

our bolts 

and n

uts for eas

y r

emoval. (Figure 8)

6.

Loosen the 

f

our nuts on the fan frame

. L

ift the 

f

an 

up

 and then pull out the 

f

an. 

Figure 8

Figure 

6

Figure 

7

Summary of Contents for DAFU-1000

Page 1: ...Page 1 of 15 DAFU IOM 01 DAIKIN AIR FILTRATION UNIT INSTALLATION OPERATION AND MAINTENANCE MANUAL DAFU IOM 01 ORIGINAL INSTRUCTIONS...

Page 2: ...troduction Guidelines Qualifications Safety Warning Warranty Environmental Conditions Technical Features and Specifications Dimensional Drawing Wiring Diagram Routine Maintenance Non Routine Maintenan...

Page 3: ...e unloading of the unit Any damage or non conformity with the order must be written on the delivery note and a written complaint must be forwarded to Complaints or contestations sent later than 10 day...

Page 4: ...RATION UNIT supplied is complete and conforms to the Packing List is delivered together with Installation Operation and Maintenance Manual DAIKIN MIDDLE EAST AFRICA FZE P O BOX 18674 JEBEL ALI FREE ZO...

Page 5: ...he unit Lack of maintenance Unauthorised modifications or repairs Use of non original or unsuitable spare parts QUALIFICATION REQUIRED FOR THE USE AND MAINTENANCE OF THE UNIT GENERAL OPERATOR Authoris...

Page 6: ...Every operation on the system or on the electrical appliances must be carried out only by a Qualified Maintenance Electrician Always switch off voltage to the electrical panel before opening the elect...

Page 7: ...on the part of the operators failure to respect the installation use and maintenance instructions given in this manual or failure to comply with the safety rulings in force for the protection of the...

Page 8: ...outdoor air changes ACH The air filtration unit can be operated in any of the following modes 1 100 Exhaust 2 100 Recirculating This powerful unit is equipped with an EC Fan that has variable speed co...

Page 9: ...with activated carbon media Minimum efficiency reporting value MERV 7 UL Classified UV Lamp High output UV lamp 254 nm to inactivate virus bacteria and fungi AstroCel III HEPA filters H14 HEPA Filters...

Page 10: ...Page 10 of 15 DAFU IOM 01 DIMENSIONAL DRAWING ELECTRICAL WIRING...

Page 11: ...not running and spinning Check for any damaged or broken cables Ensure that casters are locked properly and tightly Figure 3 If the HEPA filter is clogged then the red light will switch on meaning th...

Page 12: ...a frame to avoid damage MERV8 PRE Filter Usually the pre filter is installed in the lower position and is recommended to be changed every 2 3 months or as required for better performance For checking...

Page 13: ...move upward and filter can be easily slide out Figure 7 6 5 Examine the filter frame and filter cabin for any contamination moisture or any dust particles Clean with dry cloth 6 Slide out the contami...

Page 14: ...s panel properly Check Non Routine Maintenance Section Unusual Sound and Unit Vibration Check if the filters are clogged and replace it if necessary Check Non Routine Maintenance section Dirty Filter...

Page 15: ...Page 15 of 15 DAFU IOM 01 Africa P O Box 18674 Plot MO0426 JAFZA North Jebel Ali Free Zone Dubai UAE Tel 971 0 4 815 9300 Fax 971 0 4 815 9311 Toll Free 800 DAIKIN 324546 www daikinmea com...

Reviews: