Indoor Unit Installation
1.
Installing the mounting plate
• The mounting plate should be installed on a wall which can support the weight of the indoor unit.
1) Temporarily secure the mounting plate to the wall, make sure that the panel is completely level, and mark the boring
points on the wall.
2) Secure the mounting plate to the wall with screws.
Recommended mounting plate retention spots and dimensions
780
Use tape measure
as shown.
Keep here the piece cut out
from the unit for piping
unit: mm
Gas pipe end
Removed pipe
port cover
Recommended mounting plate
retention spots (5 spots in all)
Place a leveler
on raised tab.
59
330.5
241.7
47.3
160
59.5
50
160
241.7
47.3
106
125.5
331
203
247
Drain hose position
Liquid pipe end
A
Mounting plate
* The removed pipe port cover can be
kept in the mounting plate pocket.
Position the end of
a tape measure at .
Through-
the-wall
hole
ϕ
65mm
2.
Boring a wall hole and installing wall embedded pipe
• For walls containing metal frame or metal board, be sure to use a wall
embedded pipe and wall cover in the feed-through hole to prevent possible
heat, electrical shock, or fire.
• Be sure to caulk the gaps around the pipes with caulking material to prevent
water leakage.
1) Bore a feed-through hole of 65mm in the wall so it has a down slope toward the outside.
2) Insert a wall pipe into the hole.
3) Insert a wall cover into wall pipe.
4) After completing refrigerant piping, wiring, and drain piping, caulk pipe
hole gap with putty.
Inside
Outside
Caulking
Wall embedded pipe
(field supply)
Wall hole cover
(field supply)
Wall embedded pipe
(field supply)
ϕ
65
3.
Installing indoor unit
• In the case of bending or curing refrigerant pipes, keep the following
precautions in mind.
Abnormal sound may be generated if improper work is conducted.
1) Do not strongly press the refrigerant pipes onto the bottom frame.
2) Do not strongly press the refrigerant pipes on the front grille, either.
1)
2)