background image

1-9

English

2

DRILLING A WALL HOLE AND INSTALLING WALL EMBEDDED PIPE

•  For walls containing metal frame or metal board, be sure to use a wall embedded pipe and wall  cover in the 

feed-through hole to prevent possible heat, electrical shock, or fire.

•  Be sure to caulk the gaps around the pipes  with 

caulking material to prevent water leakage. 

1) Drill a feed-through hole of 2-9/16" (65mm) in the wall 

so it has a down slope toward the outside.

2) Insert a wall pipe into the hole.

3) Insert a wall cover into wall pipe.

4) After completing refrigerant piping, wiring, and drain 

piping, caulk pipe hole gap with putty.

Wall embedded pipe 
(Field supply)

Caulking (Putty) 
(Field supply)

Inside

Outside

Wall embedded 
pipe (Field supply)

Ø 2-9/16" 
(65mm)

Wall hole cover 
(Field supply)

3

INSTALLING INDOOR UNIT

Right-side, right-back, or right-bottom piping.

Wire guide

Mounting plate

Hang indoor unit’s hook here.

mark

Remove pipe port cover 

here for right-bottom piping

Bind refrigerant pipe 

and drain hose together

with insulation tape.

Remove pipe port cover 

here for right-side piping

Right-side piping

Right-back piping

Right-bottom 

piping

Mounting plate

When stripping the 

ends of inter-unit wire 

in advance, bundle 

the wire lead ends 

with insulation tape.

Inter-unit wire

1) Attach the drain hose to the underside of the refrigerant 

pipes with adhesive vinyl tape.

2) Wrap the refrigerant pipes and drain hose together with

insulation tape.

3) Pass the drain hose and refrigerant pipes through the wall

hole, then set the indoor unit on the mounting plate

hooks by using the   markings at the top of the indoor unit as a guide.

4) Open the front panel, then open the service lid. 

(Refer to installation tips.)

5) Pass the inter-unit wire from the outdoor unit through the 

feed-through wall hole and then through the back of the indoor unit. 

Pull them through the front side. Bend the ends of tie wires 

upward for easier work in advance. (If the inter-unit wire ends are 

to be stripped first, bundle wire ends with adhesive tape.) 

6) Press the bottom frame of the indoor unit with both hands to

set it on the mounting plate hooks. Make sure the wires

do not catch on the edge of the indoor unit.

Left-side, left-back, or left-bottom piping.

How to replace the drain plug and drain hose

• Removal method 

1) Rotate to detach wire clip from hook on the right 

and remove the drain hose.

2) Remove the drain plug on the left side and attach it 

to the right side.

3) Insert the drain hose and tighten by rotating the 

wire clip to hook.

Forgetting to tighten this may cause water 

leakages.

Drain hose attachment position

The drain hose is on the back of the unit.

Attachment on the left side

Attachment on the right side 

(factory default) 

Back view of unit

Front side of unit

Left side

Right side

Wire clip

Wire clip

Drain hose

Drain hose

1) Attach the drain hose to the underside of the refrigerant 

pipes with adhesive vinyl tape.

2) Be sure to connect the drain hose to the drain port in place 

of a drain plug.

3) Shape the refrigerant pipe along the pipe path marking on 

the mounting plate.

4) Pass drain hose and refrigerant pipes through the wall hole,

then set the indoor unit on mounting plate hooks, using the

 markings at the top of indoor unit as a guide.

5) Pull in the inter-unit wiring.
6) Connect the inter-unit piping.

Do not apply lubricating oil (refrigerant 
machine oil) when inserting. 
Application causes deterioration and 
drain leakage of the plug.

Left-side piping

Remove pipe port 
cover here for 
left-side piping.

Remove pipe port cover 
here for left-bottom piping.

Left-back piping

Left-bottom piping

 How to set drain plug

Insert a hexagon 
wrench 5/32" 
(4mm)

No gap

Drain hose

Caulk this hole
with putty or
caulking material.

Bind with plastic tape.

Mounting plate

Wrap insulating tape around the 
bent portion of refrigerant pipe. 
Overlap at least half the width 
of the tape with each turn.

01_IM-BMS-CTX_2MX-DAIKIN_3P621387-1-EN.indb   9

01_IM-BMS-CTX_2MX-DAIKIN_3P621387-1-EN.indb   9

4/27/2021   2:37:23 PM

4/27/2021   2:37:23 PM

Summary of Contents for CTX07AXVJU

Page 1: ...ci n Serie Split R410A Espa ol Manuel d installation S rie split R410A Fran ais DAIKIN ROOM AIR CONDITIONER 3P621387 1 MODELS CTX07AXVJU CTX09AXVJU CTX12AXVJU 2MX18AXVJU 01_IM BMS CTX_2MX DAIKIN_3P621...

Page 2: ...01_IM BMS CTX_2MX DAIKIN_3P621387 1 EN indb 2 01_IM BMS CTX_2MX DAIKIN_3P621387 1 EN indb 2 4 27 2021 2 37 22 PM 4 27 2021 2 37 22 PM...

Page 3: ...AIN PIPING 10 5 WIRING 11 OUTDOOR INSTALLATION GUIDELINE 1 INSTALLING OUTDOOR UNIT 12 2 DRAIN WORK 12 3 FLARING THE PIPE END 12 4 REFRIGERANT PIPING 13 5 PURGING AIR AND CHECKING GAS LEAKAGE 14 6 REFI...

Page 4: ...UNIT ON OFF SWITCH SIGNAL RECEIVER ROOM TEMPERATURE THERMISTOR LEFT UP DOWN FLAP FRONT VIEW SIDE VIEW 9 27 32 250 11 1 3 288 MODEL NAME PLATE All dimensions are in inch mm 01_IM BMS CTX_2MX DAIKIN_3P6...

Page 5: ...Model A B C D E F G H I J K L M N O 18 21 11 16 550 26 1 2 675 2 11 16 69 15 32 12 11 3 16 284 15 32 12 1 2 13 18 1 2 470 3 13 16 97 4 1 4 108 7 1 16 180 1 11 16 43 25 32 20 3 15 16 100 3 16 5 Dimensi...

Page 6: ...pply shared by another appliance Use a cable of suitable length Do not use tapped wires or an extension lead as this may cause overheating electric shocks or fire Make sure that all wiring is secured...

Page 7: ...f the flare nut is too tight it may crack after prolonged use causing refrigerant leakage Do not overcharge the unit This unit is factory pre charged Overcharge will cause over current or damage to th...

Page 8: ...ntially explosive atmosphere Wireless Remote Controller Do not expose the remote controller to direct sunlight this will hinder receiving signals from the indoor unit Turn on all the fluorescent lamps...

Page 9: ...both sides How to remove the stop valve cover Remove the screw on the stop valve cover Slide the lid upwards to remove it How to attach the stop valve cover Insert the stop valve cover into the outdoo...

Page 10: ...e should be installed on a wall which can support the weight of the indoor unit Mounting plate INDOOR UNIT CTX07 09 12 E B C A H I G H C B D 2 9 16 65 2 9 16 65 F Recommended mounting plate retention...

Page 11: ...in advance If the inter unit wire ends are to be stripped first bundle wire ends with adhesive tape 6 Press the bottom frame of the indoor unit with both hands to set it on the mounting plate hooks M...

Page 12: ...or maintenance Space for performance Air flow Indoor All dimensions are in inch mm How to attach the indoor unit Hook the claws of the bottom frame to the mounting plate How to remove the indoor unit...

Page 13: ...ated wire for connections between indoor and outdoor units Local code always supersedes recommendation All wires must be firmly connected Make sure all the wire do not touch the refrigerant piping com...

Page 14: ...ipe cutter 2 Remove burrs with the cut surface facing downward so that the filings do not enter the pipe 3 Put the flare nut on the pipe 4 Flare the pipe 5 Check that the flaring is properly made Do n...

Page 15: ...insulation dimensions as below NOTICE Do NOT exceed the unit s maximum working pressure see Max Allowable Pressure on the unit name plate Inter unit wire Drain hose Liquid pipe insulation Gas pipe ins...

Page 16: ...n the liquid stop valve s rod 90 degrees counterclockwise with a hexagonal wrench to open valve Close it after 5 seconds and check for gas leakage Using soapy water check for gas leakage from indoor u...

Page 17: ...ck or fire Do not use locally purchased electrical parts inside the product Do not branch the power for the drain pump etc from the terminal block Doing so may cause electric shock or fire Be sure to...

Page 18: ...door and outdoor units There are NO refrigerant leaks The refrigerant pipes gas and liquid are thermally insulated The correct pipe size is installed and the pipes are properly insulated The stop valv...

Page 19: ...signal transmission ON to OFF 1 Long Beep OFF to ON Pump down Cool force on 2 Short Beep Others 1 Short Beep Heatpump Unit The table shows the LED indicator lights for the air conditioner unit under n...

Page 20: ...DANGER RISK OF BURNING NOTICE Risk of electrostatic discharge Before performing any maintenance or service work touch a metal part of the unit in order to eliminate static electricity and to protect t...

Page 21: ...E DRENAJE 10 5 CABLEADO 11 GU A DE INSTALACI N EXTERIOR 1 INSTALACI N DE LA UNIDAD EXTERIOR 12 2 TRABAJO DE DRENAJE 12 3 ABOCARDADO DEL EXTREMO DEL TUBO 12 4 TUBER A DE REFRIGERANTE 13 5 PURGA DE AIRE...

Page 22: ...ENCENDIDO APAGADO RECEPTOR DE SE ALES TEMPERATURAAMBIENTE TERMISTOR IZQUIERDA ALETA ARRIBA ABAJO VISTA FRONTAL VISTA LATERAL 9 27 32 250 11 1 3 288 PLACA DE NOMBRE DE MODELO Todas las dimensiones est...

Page 23: ...mensi n Modelo A B C D E F G H I J K L M N O 18 21 11 16 550 26 1 2 675 2 11 16 69 15 32 12 11 3 16 284 15 32 12 1 2 13 18 1 2 470 3 13 16 97 4 1 4 108 7 1 16 180 1 11 16 43 25 32 20 3 15 16 100 3 16...

Page 24: ...cable de extensi n ya que esto podr a causar sobrecalentamiento descargas el ctricas o incendios Aseg rese de que todo el cableado est asegurado que se usen los cables especificados y que no haya tens...

Page 25: ...i la tuerca c nica est demasiado apretada puede agrietarse despu s de un uso prolongado causando fugas de refrigerante No sobrecargue la unidad Esta unidad viene precargada de f brica La sobrecarga ca...

Page 26: ...u uso en una atm sfera potencialmente explosiva Control remoto inal mbrico No exponga el control remoto a la luz solar directa esto dificultar la recepci n de se ales de la unidad interior Encienda to...

Page 27: ...s en ambos lados C mo quitar la tapa de la v lvula de cierre Retire el tornillo de la tapa de la v lvula de cierre Deslice la tapa hacia arriba para retirarla C mo colocar la tapa de la v lvula de cie...

Page 28: ...Coloque un nivelador en estas pesta as Use una cinta m trica como se muestra Coloque el extremo de la cinta m trica en Orificio a trav s de la pared de 65mm Posici n de la manguera de desag e Todas la...

Page 29: ...s cables entre unidades junte los extremos de los cables con cinta adhesiva 6 Presione el marco inferior de la unidad interior con ambas manos para colocarla en los ganchos de la placa de montaje Aseg...

Page 30: ...r Todas las dimensiones est n en inch mm Espacio para mantenimiento Espacio necesario 4 TUBER A DE DRENAJE Conecte la manguera de desag e como se describe a continuaci n La manguera de drenaje debe es...

Page 31: ...r La legislaci n local tiene prioridad sobre esta recomendaci n 2MX18 15A Habitaci n B Habitaci n A Sujete firmemente los cables con los tornillos de los bornes Todos los alambres deben estar conectad...

Page 32: ...a tuber a 3 Coloque la tuerca c nica en el tubo 4 Ensanche el tubo 5 Verifique que el abocardado est bien hecho No use aceite mineral en la parte ensanchada Evite que el aceite mineral ingrese al sist...

Page 33: ...n Aislamiento de tuber as de gas Cinta de acabado Tuber a de gas Tuber a de l quido 4 TUBER A DE REFRIGERANTE Pared Lluvia Aseg rese de colocar una tapa Si no hay una tapa c nica disponible cubra la b...

Page 34: ...GERANTE Compruebe el tipo de refrigerante que debe usarse en la placa de especificaciones t cnicas del aparato Precauciones al agregar R410A Llene desde la tuber a para l quido en forma l quida Este e...

Page 35: ...dentro del producto No desv e la potencia de la bomba de drenaje etc desde el bloque de terminales De lo contrario podr a provocar una descarga el ctrica o un incendio Aseg rese de instalar un interru...

Page 36: ...s de refrigerante Las tuber as de refrigerante gas y l quido est n aisladas t rmicamente El tama o correcto de la tuber a est instalado y las tuber as est n aisladas adecuadamente Las v lvulas de cier...

Page 37: ...de la se al ACTIVADO o DESACTIVADO 1 pitido largo DESACTIVADO o ACTIVADO Vaciado por bombeo Fuerza de refrigeraci n activada 2 pitido corto Otros 1 pitido corto Unidad De Bomba De Calor La tabla que s...

Page 38: ...AVISO Riesgo de descarga electrost tica Antes de realizar cualquier trabajo de mantenimiento o servicio toque una parte met lica de la unidad para eliminar la electricidad est tica y proteger la PCB A...

Page 39: ...ION DE DRAINAGE 10 5 C BLAGE 11 RECOMMANDATION D INSTALLATION L EXT RIEUR 1 INSTALLATION DE L UNIT EXT RIEURE 12 2 TRAVAUX DE VIDANGE 12 3 VASEMENT DE L EXTR MIT DU TUYAU 12 4 RACCORDEMENTS DES TUYAUT...

Page 40: ...N THERMISTOR DE TEMP RATURE DE LA PI CE VUE DE DEVANT VUE LAT RALE 9 27 32 250 11 1 3 288 ARRI RE ARRI RE BAS GAUCHE CAPOT AMOVIBLE PLAQUE SIGNAL TIQUE DU MOD LE BAS Toutes les dimensions sont donn es...

Page 41: ...Dimension Mod le A B C D E F G H I J K L M N O 18 21 11 16 550 26 1 2 675 2 11 16 69 15 32 12 11 3 16 284 15 32 12 1 2 13 18 1 2 470 3 13 16 97 4 1 4 108 7 1 16 180 1 11 16 43 25 32 20 3 15 16 100 3...

Page 42: ...e rallonge car cela pourrait entra ner une surchauffe des chocs lectriques voire un incendie S assurer que tout le c blage est s curis que les c bles sp cifi s ont t utilis s et que les connexions ou...

Page 43: ...st trop serr il pourrait se fendre apr s une utilisation prolong e entra nant une fuite de r frig rant Ne pas surcharger l unit Cette unit est pr charg e en usine Une surcharge pourrait entra ner une...

Page 44: ...st pas con u pour une utilisation dans une atmosph re potentiellement explosive Support de la t l commande Ne pas exposer la t l commande la lumi re directe du soleil cela pourrait g ner la r ception...

Page 45: ...ne 2 Cadre du filtre Filtre air Vis M4 x 12L Le couvercle de service et amovible M thode d ouverture 1 Enlevez les vis du couvercle de service 2 Abaissez le couvercle de service en diagonale dans le s...

Page 46: ...7 points en tout Placer un niveleur sur ces onglets Utiliser un m tre comme indiqu Positionner l extr mit du m tre Trou perc dans le mur 65mm Position du tuyau d vacuation Toutes les dimensions sont d...

Page 47: ...re inf rieur de l unit int rieure deux mains pour l installer sur les crochets de la plaque de montage S assurer que les fils n accrochent pas sur le bord de l unit int rieure Guide de fil Plaque de m...

Page 48: ...r entretien Espace pour entretien Espace pour performance Flux d air Int rieur Toutes les dimensions sont donn es en inch mm 4 CANALISATION DE DRAINAGE Connecter le tuyau de drainage comme d crit ci d...

Page 49: ...lois locales priment toujours sur la recommandation 2MX18 Pi ce B Pi ce A Fixer fermement les fils avec les vis des bornes Unit Ext rieure 15A Tous les fils doivent tre fermement connect s Aucun fil l...

Page 50: ...l aide d un coupe tube 2 Enlevez les bavures avec la surface coup e vers le bas afin que la limaille ne p n tre pas dans le tuyau 3 Mettre l crou vas sur le tuyau 4 vaser le tuyau 5 V rifier que l vas...

Page 51: ...RDEMENTS DES TUYAUTERIES Appliquer de l huile Appliquer de l huile de r frig ration sur la surface interne de l vasement Ne pas appliquer d huile de r frig ration sur la surface externe Ne pas appliqu...

Page 52: ...ignal tique de la machine Pr cautions prendre lors de l ajout de R410A Remplir partir de la conduite de liquide sous forme liquide Il s agit d un r frig rant m lang L ajouter sous forme de gaz peut do...

Page 53: ...s lectriques achet es localement pour l int rieur du produit Ne pas d river l alimentation pour la pompe de vidange etc depuis le bornier Ceci pourrait entra ner un choc lectrique voire un incendie Ve...

Page 54: ...ge de terrain suivant entre l unit ext rieure et l unit int rieure a t effectu conform ment ce document et aux codes locaux Drainage S assurer que la vidange s coule r guli rement Cons quence possible...

Page 55: ...ARR T 1 bip long ARR T vers SUR Pompe bas Force de refroidissement activ e 2 bips courts Autres 1 bips courts Module Pompe Chaleur Le tableau ci dessous reprend en d tail la visualisation par led des...

Page 56: ...r sur le panneau d alimentation retirer les fusibles ou ouvrir les dispositifs de protection de l unit NE PAS toucher les parties sous tension pendant 10 minutes apr s coupure de l alimentation lectri...

Page 57: ...MEMO MEMOR NDUM LE M MO 03_IM BMS CTX_2MX DAIKIN_3P621387 1 FR indb 19 03_IM BMS CTX_2MX DAIKIN_3P621387 1 FR indb 19 4 27 2021 3 04 53 PM 4 27 2021 3 04 53 PM...

Page 58: ...MEMO MEMOR NDUM LE M MO 03_IM BMS CTX_2MX DAIKIN_3P621387 1 FR indb 20 03_IM BMS CTX_2MX DAIKIN_3P621387 1 FR indb 20 4 27 2021 3 04 53 PM 4 27 2021 3 04 53 PM...

Page 59: ...01_IM BMS CTX_2MX DAIKIN_3P621387 1 EN indb 19 01_IM BMS CTX_2MX DAIKIN_3P621387 1 EN indb 19 4 27 2021 2 37 25 PM 4 27 2021 2 37 25 PM...

Page 60: ...s pr alable En el caso de que exista alg n conflicto en la interpretaci n de este manual y cualquier traducci n del mismo en cualquier idioma prevalecer la versi n en ingl s de este manual El fabrican...

Reviews: