105
TROUBLESHOOTING
Troubleshooting Error Code - 02, L2
Cycle power
Error Code:
02, L2 - High side fault
Applicable Models:
Outdoor units
Method of Error Detection:
Integrated control module LED
display provides the indicated
error code
Error Decision Conditions:
Four consecutive compressor
protector trips with average run
time between trips greater than 1
minute and less than 15 minutes.
Low pressure and high pressure
switches are closed. Integrated
control module diagnostic/ status
LED display shows the indicated
code
Check the
resistance of high
pressure switch, is
it open?
No
Board is
reading 02, L2
Check and clean condenser
coil, check outdoor fan motor,
repair/replace as needed.
Check capacitor , check wire
Yes
No
Repalce pressure switch
Yes
Read pressure
on a guage, is
the pressure
high?
ERROR CODE - 02, L2