PRESSURE PROBES S1 AND S2

By setting the type of pressure probe S1 for driver A and S2 for 

driver B, the measuring range and alarm range are defined based 

on the construction data of each model and generally indicated on 

the card placed in the probe.

Parameter

Description

S1

NTC temperature sensor

S2

Suction pressure transducer from 0 to 45 bar

NOTE:

 If two pressure probes S1 and S2 are installed, they 

must be of the same type. 

It is not possible to use 

one proportional and one electronic probe.

NOTE: In the case of ducted systems where the same 

pressure probe is shared between twin1 and twin2 

controllers, choose the normal option for driver A 

of the twin1 controller and the “remote” option for 

the other drivers.

Example: If you want to use for driver A and B the same pressure 

probe P1, type: 4...20mA, -0,5...7 barg

For driver A of twin 1 controller select: 4...20mA, -0.5...7 barg. 

For driver B of twin 1 controller and for driver A and B of twin 2 

controller select: remote 4...20mA, -0.5...7 barg.

NOTES:

• 

The default measurement range is always in bar gauge 

(barg). In the Manufacturer menu, you can customize the 

parameters corresponding to the measuring range and 

alarms if the probe used is not in the standard list. If the 

measuring range is modified, the driver will detect the 

modification and indicate the probe type S1 and S3 as 

“Custom”;

• 

The driver software takes the unit of measurement into 

account. If a measuring range is selected and then the 

unit  of  measurement  is  changed  (from  bar  to  psi),  the 

driver automatically updates the measuring range limits 

and alarm limits. By default, the main control probes S2 

and S4 are set to “NTC CAREL”. Other probe types can 

be selected in the service menu.

• 

Unlike  the  pressure  probes,  the  temperature  probes 

do  not  have  any  parameters  corresponding  to  the 

measuring  range  that  can  be  changed,  and  therefore 

only the models listed can be used (see the chapter on 

“Functions” and the parameter list). In any case, in the 

manufacturer’s programming mode, you can customize 

the probe alarm signal limits.

MAIN CONTROL 

When setting the main control, the operating mode of each driver 

is defined.

Parameter/description

Predet.

1= channeled counter/chamber

Counter/channeled camera 

The superheat set point and all the parameters relative to PID 

control, the operation of the protectors and the meaning and use 

of probes S1/S3 and S2/S4 will be automatically set to the values 

recommended by CAREL according to the selected application.

During this initial configuration phase, only the superheat control 

modes from 1 to 10 can be set, which differ according to the 

application (chiller, refrigerated counter, etc ). 

In case of errors in the initial settings, these parameters can be 

accessed later and changed in the service or manufacturer menu. 

If the default controller parameters are reset, the display will show 

the guided start-up procedure again at the next start-up.

CHECKS AFTER INITIAL START-UP 

After the first start-up:

• Check that the valve performs a complete closing cycle for 

alignment.

• Set, if necessary, in the Assistance or Manufacturer 

programming mode, the overheating set point (if you do not 

want to maintain the one recommended by CAREL depending 

on the application) and the protection thresholds (LOP, MOP, 

etc ).

STEPS FOR PARAMETER SETTING AND 

SEPOINT SUPER HEAT.

As mentioned in the display programming mode section, enter the 

regulation menu.

By pressing the 

down 

key, scroll the regulation menu to number 1.  

Press 

enter

 and use the 

up 

and 

down

 keys to select the desired 

super heat setpoint, then press the 

enter

 key and then the 

esc 

key 

to return to the menu selection.

Control

Summary of Contents for Clima-Flex CLIWP Series

Page 1: ...Control Manual CLIWP Series Direct Expansion Unit with Fixed Air Cooled Compressor Model 3 TR 5 TR Refrigerant HFC 410A 60 Hz CM Group Wall Attached Package Part Number CM CLIWP Date 23 March 2023...

Page 2: ...ion and data cover the Clima Flex product at the time of publication and we reserve the right to make changes in design and construction at any time without notice Manufactured in an ISO 9001 certifie...

Page 3: ...fire WARNING If refrigerant leaks from the unit there is a potential choking danger as the refrigerant will displace air in the immediate area Be sure to follow all applicable published industry relat...

Page 4: ...AL CAPACITY 036 36 000 Btu H Nominal Cooling 060 60 000 Btu H Nominal Cooling DISCHARGE AIR U Upper Discharge Air OPERATION AC Air Conditioner HP Heat Pump VENTILATION PACKAGES E Economizer Y None EVA...

Page 5: ...ngent quality standards ASTM B117 1500 hour salt spray test The selection of high end compressors and heat exchangers ensures the capacity and high efficiency of the equipment All our equipment has a...

Page 6: ...d Chemical resistance according to C5 I ISO 2812 1 Approved TECHNICAL FEATURES Insitu Spray Coat is a water based water thinnable synthetic flexible resin coating solvent free designed specifically fo...

Page 7: ...t the system to almost any cloud service either to upload historical data to analysis services deliver alarm messages to alarm processing services or to operate parts of the control system via a cloud...

Page 8: ...e next field 3 Finally navigate to Save and Restart and press 4 Confirm the reboot and the device will reboot with the new IP address To set the BACnet device ID through the LCD display 1 On the main...

Page 9: ...ograms LOYTEC LINX Configurator LOYTEC LINX Configurator The application starts and displays the data point manager screen as shown in Figure 7 2 When the device is online connect to the device by cli...

Page 10: ...2 1 AP Compressor APdx 24 VAC Relay DO 3 1 AC Free Cooling ACf 0 10 VDC AO 1 1 Zone Temp TZ LSTAT MODBUS RTU Total points per Ctrl 3 3 1 3 0 3 To adapt the I O name double click on the name in the Na...

Page 11: ...onfigured so that the equipment can be turned on and the system points can be modified The following describes the use of the LSTAT thermostat as shown in Fig 9 and the indicators it contains in this...

Page 12: ...RMS The CLIWP system has 3 alarms The first alarm is triggered by the low pressure switch and the second alarm is triggered by the high pressure switch these alarms are digital signals which are progr...

Page 13: ...ont keypad Access is different depending on the user level support installer and manufacturer parameters Modification of the Assistance parameters The Support parameters as well as the parameters for...

Page 14: ...dard display after 5 minutes NETWORK ADDRESS The network address assigns the controller an address for serial connection to a supervisory system via RS485 and to a pCO controller via pLAN tLAN Modbus...

Page 15: ...menu Unlike the pressure probes the temperature probes do not have any parameters corresponding to the measuring range that can be changed and therefore only the models listed can be used see the cha...

Page 16: ...nly when heating or cooling In the ON position the fan will run constantly at all times with or without a heating or cooling demand Multifunction slide switch It provides easy access to common setting...

Page 17: ...ime delay 5 default The thermostat waits 5 minutes before turning the system back on after the last time it was turned on This internal delay prevents rapid cycling and provides wallpack protection Th...

Page 18: ...cm cliwp cf eng www clima flex com...

Reviews: