Installation
EDUS39-800-F8
20
BSVQ-P
7-2 EXAMPLE FOR THE WHOLE SYSTEM
7-3 POWER CIRCUIT, SAFETY DEVICE AND CABLE REQUIREMENTS
•
A power circuit (Refer to Table 3) must be provided for connection of the unit. This circuit must be protected
with the required safety devices, i.e. a main switch, a slow blow fuse on each phase and an earth leakage
circuit breaker.
•
When using residual current operated circuit breakers, be sure to use a high-speed type (0.1 second or
less) 30mA rated residual operating current.
•
Use copper conductors only.
•
Use insulated wire for the power cord.
•
Select the power supply cable type and size in accordance with relevant local and national regulations.
•
Use vinyl cord with sheath or cable (2 wire) of AWG 18-16 for transmission wiring.
Table 3
MCA: Min. Circuit Amps (A);
MFA: Max. Fuse Amps (A)
NOTES
•
The above Table 3 of Electrical Characteristics refers to one BS unit.
•
See the Engineering data book for other details.
7-4 WIRING EXAMPLE
•
Here is shown a wiring example for one system transmission wiring.
•
Connect terminals F1 and F2 (TO IN/D UNIT) on the control PCB (A1P) in the outside unit EL. COMPO.
BOX and terminals F1 and F2 (TO OUT/D UNIT) of the control PCB (A1P) of the first BS unit A.