Installation
EDUS39-800-F8
14
BSVQ-P
5. BS UNIT INSTALLATION
Use only accessories and parts which are of the designated specification when installing.
(1)
When necessary, use the following procedure to change the EL. COMPO. BOX mounting surface.
(
Refer to Fig. 4
)
1) Remove the EL. COMPO. BOX lid. (2 screws)
2) Remove the EL. COMPO. BOX. (2 screws)
3) Remove the top panel. (4 screws)
4) Remove the coil cover. (1 screw)
5) Change the pull out direction of the wire (motorized valve coil) between the body and the EL. COMPO. BOX.
6) Rotate the coil cover 180˚ and attach it.
7) Turn the top panel around 180˚ and attach it.
8) Attach the EL. COMPO. BOX.
9) Attach the EL. COMPO. BOX lid.
(2)
Attach the hooks to the suspension bolts.
Be sure to use the nuts (M8 or M10: 3 pcs, 4 locations) and washers
(field supply) from both the top and bottom sides of the hanging
bracket and make sure they are tightened correctly.
NOTES
•
The BS unit has a top and a bottom, so install it so that the diagonal lines in the figure 4 are where the top is.
(Failing to do so may prevent the unit from operating properly and increase the volume of the operating noise.)
16-7/8
8-5/8
Hanging
bracket
Suspension
bolt
Long nut or
turnbuckle
Anchor
40 in. or less
40 in. or less
Unit
proper
<Suspension bolt pitch>
<Example installation>
Note: All the above parts are part to be procured in the field.
Fig. 3
Washer
(Field supply)
Nut
(Field supply)
BS unit
proper
Hanging
bracket
3/8 – 9/16 in.
Nut
(Double nut)
(Field supply)
Suspension bolt
(Field supply)