BSVQ-P

BS Units

Summary of Contents for BSVQ-P

Page 1: ...EDUS 39 800 F8 AMERICAS BSVQ P BS Units ...

Page 2: ...EDUS39 800 F8 BSVQ P 1 BSVQ P BS Units 1 Specifications 2 2 Dimensions 3 3 Piping Diagrams 5 4 Wiring Diagrams 6 5 Electric Characteristics 7 6 Sound Levels 8 7 Installation 9 8 Accessories 24 ...

Page 3: ...ed Steel Plate Galvanized Steel Plate Dimensions H W D in 8 1 8 15 1 4 12 13 16 8 1 8 15 1 4 12 13 16 Sound Absorbing Thermal Insulation Material Foamed Polyurethane Frame Resisting Needle Felt Foamed Polyurethane Frame Resisting Needle Felt Piping Connection Indoor Unit Liquid Pipes φ 3 8 C1220T Brazing Connection 1 φ 3 8 C1220T Brazing Connection Gas Pipes φ 5 8 C1220T Brazing Connection 1 φ 5 8...

Page 4: ...r more 3 or more Servicing space 10 or more Servicing space 10 or more In case of use Attached pipe Servicing space 12 or more Suspension bolt pitch Suspension bolt pitch Servicing space 18 Note 2 8 5 8 12 6 3 16 16 7 8 6 5 16 Inspection door Location of unit s Name Plate Right side of electric box Note 1 1 7 8 2 5 8 8 3 8 4 5 16 8 1 8 6 5 8 1 7 8 15 1 4 7 8 2 1 16 10 3 16 2 13 16 4 5 16 4 5 8 2 1...

Page 5: ...de of the unit 2 Be sure to install a inspection door at electric box side 3 Attached pipe is only used in case of connecting with indoor unit capacity indey 54 or more and 60 or less 4 Small sound of refrigerant will be made which may be disturbing Do not install it at the place such as bedroom under roof φ 3 8 brazing connection Description φ 3 8 brazing connection Liquid pipe connection port Su...

Page 6: ...EDUS39 800 F8 Piping Diagrams BSVQ P 5 3 Piping Diagrams 4D057985A ...

Page 7: ...RIC EXPANSION VALVE SUB SUCTION DS1 DS2 ELECTRIC EXPANSION VALVE MAIN SUCTION TERMINAL STRIP C H SELECTOR SWITCHING POWER SUPPLY A1P TERMINAL STRIP POWER X2A HAP CONNECTOR WIRING EXTERNAL CONTROL ADAPTOR FOR OUTDOOR UNIT BSVQ60PVJU BSVQ36PVJU OFF ON DS1 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 DS2 DS2 DS1 OFF ON FOR USING DIP SWITCH DS1 2 REFER TO INSTALLATION MANUAL OR SERVICE PRECAUTION LABEL ON EL COMPO...

Page 8: ...EDUS39 800 F8 Electric Characteristics BSVQ P 7 5 Electric Characteristics 4D058238 ...

Page 9: ...ls Overall Octave Band Level 208V 230V Ceiling Mounted Type Notes Operation noise differs with operation and ambient conditions dBA Model 208 230V 60Hz Operating Sound Stoppage Sound BSVQ36PVJU 42 32 BSVQ60PVJU 43 32 BSVQ36P BSVQ60P 4D059692 4D059693 ...

Page 10: ...otentially hazardous situation which if not avoided may result in minor or moderate injury It may also be sued to alert against unsafe practices NOTE Indicates situation that may result in equipment or property damage only accidents DANGER Refrigerant gas is heavier than air and replaces oxygen A massive leak could led to oxygen deple tion especially in basements and an asphyxiation hazard could o...

Page 11: ...ocal laws and regulations and this installation manual An insufficient power supply capacity or improper electrical construction may lead to electric shocks or fire Make sure that all wiring is secured the specified wires are used and no external forces act on the terminal connections or wires Improper connections or installation may result in fire When wiring the power supply and connecting the r...

Page 12: ...tions for keeping the system clean dry and tight A Clean and dry Foreign materials including mineral oils such as SUNISO oil or moisture should be prevented from getting mixed into the system B Tight R410A does not contain any chlorine does not destroy the ozone layer and does not reduce the earth s protection against harmful ultraviolet radiation R410A can contribute slightly to the greenhouse ef...

Page 13: ...nsulation tube Explanation Document BSVQ36 only BSVQ60 only Quantity 1 pc 1 pc 1 pc 2 pcs 16 pcs 2 pcs 1 pc 2 pcs 1 copy Shape 1 1 φ3 8 1 2 φ5 8 1 1 φ1 2 1 2 φ5 8 3 1 Small 3 2 Medium 3 3 Large Installation manual Model Total capacity of all downstreem indoor units Max number of all downstreem indoor units BSVQ36PVJU A 36 5 BSVQ60PVJU 36 A 60 8 Capacity expressed as indoor unit s model No 07 09 12...

Page 14: ...ise in those devices Noise may still be introduced at this dis tance depending on the electromagnetic wave conditions 4 PREPARATIONS BEFORE INSTALLATION Refer the figure 3 and install the suspension bolts and hanging brackets Suspension bolts For supporting the product Use M8 M10 suspension bolts When holes are to be made anew used embedded inserts and embedded foundation bolts When holes are alre...

Page 15: ...COMPO BOX lid 2 Attach the hooks to the suspension bolts Be sure to use the nuts M8 or M10 3 pcs 4 locations and washers field supply from both the top and bottom sides of the hanging bracket and make sure they are tightened correctly NOTES The BS unit has a top and a bottom so install it so that the diagonal lines in the figure 4 are where the top is Failing to do so may prevent the unit from ope...

Page 16: ...or HVAC systems Reinforce the insulation material when necessary for the installation environment Refer to the following as a guideline For 86 F RH75 to 80 Thickness at least 5 8 in For 86 F over RH80 Thickness at least 13 16 in If not reinforced condensation could form on the surface of the insulation For details refer to the Engineer ing data book NOTES This product only uses the new refrigerant...

Page 17: ...rogen 1 or perform brazing while nitrogen is flowing in the refrigerant piping 2 Refer to Fig 5 and at the end made the indoor unit and BS unit flare or flange connections 1 For details on nitrogen replacement see the VRV Installation Manual available at any Daikin dealer 2 The pressure regulator for the nitrogen released when doing the brazing should be set to about 2 9 psi Enough to feel a sligh...

Page 18: ...r units Piping size outer diameter Gas pipe Liquid pipe 07 09 12 18 φ1 2 φ1 4 24 30 36 48 φ5 8 φ3 8 in BS unit Piping size outer diameter Gas pipe Liquid pipe BSVQ36P φ5 8 φ3 8 BSVQ60P To refrigerant branch kit or outside unit Suction gas pipe Upstream Downstream Gas pipe Indoor unit Liquid pipe HP LP gas pipe Liquid pipe Determine using Table 1 based on the total capacity of the indoor units conn...

Page 19: ...se the insulation required for the reinforcement work Suction gas pipe Site piping HP LP gas pipe Site piping Gas pipe Site piping Liquid pipe Site piping Liquid pipe Site piping BS unit Top BSVQ36P type When the downstream indoor unit total capacity is 36 or less and when one indoor unit with a capacity of 24 to 36 is connected downstream When one indoor unit with a capacity of 07 to 18 is connec...

Page 20: ...not be grounded if hard vinyl pipes are used Telephone ground and lightning rods the ground potential when struck by lightning gets extremely high A circuit breaker capable of shutting down the power supply to the entire system must be installed This system consists of multiple BS units Mark each BS unit as unit A unit B and be sure the terminal board wiring to the outside unit and indoor unit are...

Page 21: ...egulations Use vinyl cord with sheath or cable 2 wire of AWG 18 16 for transmission wiring Table 3 MCA Min Circuit Amps A MFA Max Fuse Amps A NOTES The above Table 3 of Electrical Characteristics refers to one BS unit See the Engineering data book for other details 7 4 WIRING EXAMPLE Here is shown a wiring example for one system transmission wiring Connect terminals F1 and F2 TO IN D UNIT on the c...

Page 22: ...the unit through the wiring through hole left and use the included clamps 2 to securely hold the wires in 2 places Power supply wiring and ground wire Remove the EL COMPO BOX lid and connect the power supply wiring to the power terminal block X1M Also connect the ground wire to the ground wire terminal Pass both the power supply wire and the ground wire together through the wire through hole right...

Page 23: ...Always use the wire through hole to protect the wires Do not pass the transmission wiring and power supply wiring through the same locations and outside of the unit keep them separated by at least 2 in Not doing so could cause the transmission wiring to pick up electric noise external noise and result in a malfunction or breakdown After the wiring working is complete use sealer field supply to sea...

Page 24: ...tion refer to the Engineering data book Setting method The setting is made using the Local Setting Mode by the remote controller of indoor unit connected to the BS unit For information regarding the setting method refer to Engineering data book The following table gives a list of the MODE NO FIRST CODE NO and SECOND CODE NO NOTES This setting is operated by the operation remote controller while th...

Page 25: ...or KRC19 26A 1 1 Fixing Box KJB111A Check the following accessories are includced with your unit Name 1 Accessory pipes 1 Accessory pipes 2 Clamp 3 Insulation tube Explanation Document BSVQ36 only BSVQ60 only Quantity 1 pc 1 pc 1 pc 2 pcs 16 pcs 2 pcs 1 pc 2 pcs 1 copy Shape 1 1 φ3 8 1 2 φ5 8 1 1 φ1 2 1 2 φ5 8 3 1 Small 3 2 Medium 3 3 Large Installation manual ...

Page 26: ...lton TX75006 info daikinac com www daikinac com EDUS39 800 F8 Printed in U S A 03 2008 K AK FS AMERICAS Specifications designs and other content appearing in this brochure are current as of March 2008 but subject to change without notice ...