Daikin BRP069A61 Installation Manual Download Page 7

5 Installation

Installation manual

7

BRBRP069A62
Daikin Altherma LAN adapter
4P463935-1E – 2018.10

5.2.1

To connect the indoor unit

INFORMATION

▪ In the indoor unit switch box, the cable is connected to

the  same  terminals  the  user  interface  is  connected  to
(P1/P2).  For  more  information,  see  the  installation
manual of the indoor unit.

▪ The  2  wires  from  the  cable  are  NOT  polarised.  When

connecting  them  to  the  terminals,  their  polarity  does
NOT matter.

1

When  entering  the  wiring  from  the  bottom:  inside  the  LAN
adapter  casing,  ensure  strain  relief  by  routing  the  cable  along
the indicated cable path.

2

Connect  indoor  unit  terminals  P1/P2  to  LAN  adapter  terminals
X3A/1+2.

X4A

X1A

X2A

X3A

P2

P1

5.2.2

To connect the router

X4A

X1A

X2A

X3A

NOTICE

To  prevent  communication  problems  due  to  cable
breakdown,  do  NOT  exceed  the  minimum  bend  radius  of
the Ethernet cable.

5.2.3

To connect the electricity meter

INFORMATION

This  connection  is  ONLY  supported  by  LAN  adapter
BRP069A61.

1

When  entering  the  wiring  from  the  bottom:  inside  the  LAN
adapter  casing,  ensure  strain  relief  by  routing  the  cable  along
the indicated cable path.

2

Connect  the  electricity  meter  to  LAN  adapter  terminals
X2A/1+2.

S1S

2

1

X4A

X1A

X2A

X3A

INFORMATION

Mind the polarity of the cable. The positive wire MUST be
connected to X2A/1; the negative wire to X2A/2.

WARNING

Make  sure  to  connect  the  electricity  meter  in  the  correct
direction,  so  that  it  measures  the  total  energy  injected
INTO the grid.

5.2.4

To connect the solar inverter/energy
management system

INFORMATION

This  connection  is  ONLY  supported  by  LAN  adapter
BRP069A61.

INFORMATION

How  the  digital  inputs  are  connected  to  X1A  depends  on
the  Smart  Grid  application.  The  connection  described  in
the  instructions  below  is  for  the  system  to  run  in  the
"Recommended 

ON" 

operation 

mode. 

For 

more

information, see the installer reference guide.

WARNING

Make  sure  X1A/N+L  are  protected  by  a  fast  acting  circuit
breaker (rated current 100 mA~6 A, type B).

WARNING

When connecting the wiring to LAN adapter terminal X1A,
make  sure  each  wire  is  securely  fastened  to  the
appropriate  terminal.  Use  a  screwdriver  to  open  the  wire
clamps.  Make  sure  the  bare  copper  wire  is  fully  inserted
into the terminal (bare copper wire CANNOT be visible).

1

3

2

1

Ensure strain relief by fastening the cable with a cable tie to the
cable tie mounting.

2

Provide  a  detection  voltage  to  X1A/N+L.  Make  sure  X1A/N+L
are protected by a fast acting circuit breaker (100 mA~6 A, type
B).

3

For  the  system  to  run  in  the  "Recommended  ON"  operation
mode (Smart Grid application), connect the digital outputs of the
solar  inverter/energy  management  system  to  LAN  adapter
digital inputs X1A/1+2 LAN.

Summary of Contents for BRP069A61

Page 1: ...Installation manual Daikin Altherma LAN adapter English Installation manual Daikin Altherma LAN adapter BRP069A61 BRP069A62...

Page 2: ...door unit Installation manual Installation instructions Format Paper supplied in the kit Installer reference guide Installation instructions configuration application guidelines Format Digital files o...

Page 3: ...he LAN adapter application system layout App control Item Requirement LAN adapter software It is recommended to ALWAYS keep the LAN adapter software up to date Unit control method Make sure user inter...

Page 4: ...w of electrical connections Connectors X4A 4 N L 3 2 1 2 1 X1A X2A X3A a1 A b c a2 d A BRP069A61 only a1 To solar inverter energy management system a2 230 V AC detection voltage b To electricity meter...

Page 5: ...tion mode SG0 X1A 1 2 SG1 X1A 3 4 Normal operation Free running NO Smart Grid application Open Open Recommended ON Energy buffering in the domestic hot water tank and or the room WITH power limitation...

Page 6: ...and mark the position of the holes 2 Drill the holes 1 2 3 Mount the rear casing to the wall with the screws and plugs from the accessory bag 3 1 2 3 3 5 1 2 To mount the PCB to the rear casing 4 NOT...

Page 7: ...larity of the cable The positive wire MUST be connected to X2A 1 the negative wire to X2A 2 WARNING Make sure to connect the electricity meter in the correct direction so that it measures the total en...

Page 8: ...iguration of the LAN adapter For more information see the installer reference guide 5 3 2 To close the LAN adapter 1 Put the front casing to the rear casing and tighten the screw 1 2 3 1 6 Starting up...

Page 9: ......

Page 10: ......

Page 11: ......

Page 12: ...4P463935 1E 2018 10 Copyright 2017 Daikin 4P463935 1 E 00000004...

Reviews: