5 Installation

Installation manual

5

BRBRP069A62
Daikin Altherma LAN adapter
4P463935-1E – 2018.10

4.2.3

Electricity meter

If the LAN adapter is connected to an electricity meter, make sure it
is an 

electrical pulse meter

.

Requirements:

Item

Specification

Type

Pulse meter

 

(5 V DC pulse

detection)

Possible number of pulses

▪ 100 pulse/kWh

▪ 1000 pulse/kWh

Pulse duration

Minimum On
time

10 ms

Minimum OFF
time

100 ms

Measurement type

Depends on the installation:

▪ Single‑phase AC meter

▪ Three‑phase 

AC 

meter

(balanced loads)

▪ Three‑phase 

AC 

meter

(unbalanced loads)

INFORMATION

It  is  required  that  the  electricity  meter  has  a  pulse  output
that can measure the total energy injected INTO the grid.

Suggested electricity meters

Phase

ABB reference

Single

2CMA100152R1000 B21 212-100

Three

2CMA100166R1000 B23 212-100

4.2.4

Solar inverter/energy management
system

INFORMATION

Before  installation,  confirm  that  the  solar  inverter/energy
management  system  is  equipped  with  the  digital  outputs
required  to  connect  it  to  the  LAN  adapter.  For  more
information, see the installer reference guide.

Connector X1A is for the connection of the LAN adapter to the digital
outputs  of  a  solar  inverter/energy  management  system,  and  allows
for  the  integration  of  the  Daikin  Altherma  system  in  a  Smart  Grid
application.

X1A/N+L supply a 230 V AC detection voltage to the input contact of
X1A.  The  230  V  AC  detection  voltage  enables  the  detection  of  the
state  (open  or  close)  of  the  digital  inputs  and  does  NOT  supply
power to the rest of the LAN adapter PCB.

Make  sure  X1A/N+L  are  protected  by  a  fast  acting  circuit  breaker
(rated current 100 mA~6 A, type B).

The rest of the wiring to X1A differs depending on the digital outputs
available on the solar inverter/energy management system and/or on
the Smart Grid operation modes that you want the system to run in.

Smart Grid operation mode

SG0

(X1A/1+2)

SG1

(X1A/3+4)

Normal operation/Free running

NO Smart Grid application

Open

Open

Recommended ON

Energy buffering in the domestic
hot water tank and/or the room,
WITH power limitation.

Closed

Open

Smart Grid operation mode

SG0

(X1A/1+2)

SG1

(X1A/3+4)

Forced OFF

Deactivation of outdoor unit and
electrical heater operation in
case of high energy tariffs.

Open

Closed

Forced ON

Energy buffering in the domestic
hot water tank and/or the room,
WITHOUT power limitation.

Closed

Closed

For more information, see the installer reference guide.

5

Installation

5.1

Mounting the LAN adapter

The  LAN  adapter  is  mounted  to  the  wall  by  way  of  the  mounting
holes (a) in the rear casing. Before mounting the rear casing to the
wall, you have to remove some knockout holes (b)(c), depending on
how you want to route the wiring and insert it into the adapter.

You can route and insert the wiring from the bottom or from the rear.
Respect the following rules and restrictions:

Wiring

Possibilities and restrictions

Wiring routed and inserted from
the bottom

▪ ONLY for surface wiring routed

from the bottom.

▪ When  routing  wiring  from  the

bottom,  ALWAYS  let  it  enter
the adapter via the holes in the
bottom  of  the  casing

 

(b).  It  is

NOT  allowed  to  clamp  this
wiring between the casing and
the wall and let it enter via the
holes in the rear

 

(c).

▪ The  wiring  for  X1A  and  X4A

MUST  be  routed  and  inserted
from the bottom. The wiring for
X2A  and  X3A  CAN  be  routed
and  inserted  from  the  bottom
(or from the rear).

▪ When  routing  and  inserting

wiring 

from 

the 

bottom,

remove  the  required  knockout
holes  in  the  bottom  of  the
casing  (b)

 

and  replace  them

with  the  grommets  from  the
accessory bag.

Wiring routed and inserted from
the rear

▪ ONLY 

for 

in‑wall 

wiring

entering  the  adapter  from  the
rear.

▪ The  wiring  for  X2A  and  X3A

CAN  be  routed  and  inserted
from  the  rear  (or  from  the
bottom).  The  wiring  for  X1A
and  X4A  CANNOT  be  routed
and inserted from the rear.

▪ It  is  NOT  allowed  to  route

wiring  from  the  bottom,  clamp
it  between  the  casing  and  the
wall,  and  let  it  enter  via  the
holes in the rear

 

(c).

Summary of Contents for BRP069A61

Page 1: ...Installation manual Daikin Altherma LAN adapter English Installation manual Daikin Altherma LAN adapter BRP069A61 BRP069A62...

Page 2: ...door unit Installation manual Installation instructions Format Paper supplied in the kit Installer reference guide Installation instructions configuration application guidelines Format Digital files o...

Page 3: ...he LAN adapter application system layout App control Item Requirement LAN adapter software It is recommended to ALWAYS keep the LAN adapter software up to date Unit control method Make sure user inter...

Page 4: ...w of electrical connections Connectors X4A 4 N L 3 2 1 2 1 X1A X2A X3A a1 A b c a2 d A BRP069A61 only a1 To solar inverter energy management system a2 230 V AC detection voltage b To electricity meter...

Page 5: ...tion mode SG0 X1A 1 2 SG1 X1A 3 4 Normal operation Free running NO Smart Grid application Open Open Recommended ON Energy buffering in the domestic hot water tank and or the room WITH power limitation...

Page 6: ...and mark the position of the holes 2 Drill the holes 1 2 3 Mount the rear casing to the wall with the screws and plugs from the accessory bag 3 1 2 3 3 5 1 2 To mount the PCB to the rear casing 4 NOT...

Page 7: ...larity of the cable The positive wire MUST be connected to X2A 1 the negative wire to X2A 2 WARNING Make sure to connect the electricity meter in the correct direction so that it measures the total en...

Page 8: ...iguration of the LAN adapter For more information see the installer reference guide 5 3 2 To close the LAN adapter 1 Put the front casing to the rear casing and tighten the screw 1 2 3 1 6 Starting up...

Page 9: ......

Page 10: ......

Page 11: ......

Page 12: ...4P463935 1E 2018 10 Copyright 2017 Daikin 4P463935 1 E 00000004...

Reviews: