Operation manual
BRC2E52C7 / BRC3E52C7
39
4P368042-1 - 2014.02
Menu Manipulation
Sensing Sensor(Low)
This function cannot be used when group control is active.
In case of a simultaneous operation system, the system is controlled by the
sensing sensor mounted in the master indoor unit.
Operation Method
1
1/2
Energy Saving List
Setpoint Range
Setback Condition
Sensing Sensor(Low)
Sensing Sensor(Stop)
Setpoint Auto Reset
Energy Saving Options
Setting
Return
• Display the Energy Saving Options (See
).
• Press the
(Up/Down) buttons to select
Sensing Sensor(Low)
and press the Menu/Enter
button.
2
Adjust Cool SP:
Adjust Time Cool:
Limit Cool SP:
Adjust Heat SP:
Adjust Time Heat:
Limit Heat SP:
Sensing Sensor(Low)
1.0
°C
15 min
35°C
1.0°C
15 min
15°C
Setting
Return
• Press the
(Up/Down) buttons to set the
energy saving operation when the sensor detects
an absence.
• Move the cursor using the (Left/Right)
buttons.
• Press the Menu/Enter button when all changes are
made. The confirmation screen will appear.
• Example (settings on the left apply):
If the sensor determines that there is no person in
the room during cooling operation, the cooling
setpoint temperature will automatically increase by
1°C every 15 minutes until the cooling setpoint
temperature is 35°C. On the Basic Screen, the
cooling setpoint temperature will not change.
3
No
Yes
Sensing Sensor(Low)
Save the settings?
Setting
Return
• Press the (Left/Right) buttons to select
Yes
.
•
Press the Menu/Enter button to confirm the
settings and to return to the Basic Screen.