37
1
Return
Setting
Energy Saving Options
Sensing Sensor (Low)
Sensing Sensor (Stop)
Setpoint Auto Reset
1/2
•
Display the Energy Saving Options screen (Refer
to page 34)
.
•
Press “
” buttons to select
Sensing Sensor (Low)
.
Press Menu/Enter button to display the Sensing
Sensor (Low) screen.
2
Return
Setting
Sensing Sensor (Low)
Adjust Cool SP:
Adjust Time Cool:
30 m
in
Limit Cool SP:
30
°C
Adjust Heat SP:
1.0°
C
Adjust Time Heat:
60 m
in
Limit Heat SP: 15°C
1.0
°C
•
Press “
” buttons to change the setting value
of saving energy operation when the sensor
detects the absence.
•
Press “ ” buttons to move the cursor.
Press Menu/Enter button after selecting the item.
(Example)
Adjust Cool SP :
1.0°C
Adjust Time Cool :
30 min
Limit Cool SP :
30°C
•
If it is determined that there is no person in the
room by sensor during Cooling Operation, the set
temperature will automatically shift by 1°C every
30 mi
nutes until the set temper
ature is 30°
C.
(On Basic screen, set temperature does not
change.)
3
Setting
Save the settings?
Sensing Sensor (Low)
Yes
No
Return
•
Press “ ” buttons to select
Yes
.
and return to the Basic screen.
Operation
This function cannot be used at the time of group control.
In case of the simultaneous operation system, the system is controlled by the sensing
sensor mounted in the master indoor unit.
Sensing Sensor (Low)
Energy Saving List
Setpoint Range
Setback Condition