Installation manual BRC1E52A7
17
4PW71264-1 – 10.2011
7-6
Press On/Off button within about
10 seconds. The test operation starts.
Check operation condition for
3 minutes.
*
Note) In the case of above-men
-
tioned procedures
7-5
and
7-6
in reverse order, test
operation can start as well.
7-7
Press Fan speed/airflow direction
button.
7-8
Select airflow direction setting by
pressing the button on the setting
screen.
Use the
buttons to change the
airflow direction.
7-9
After the operation of airflow direction
is confirmed, press Menu/Enter button.
Basic screen returns.
7-10
Press and hold Cancel button for
4 seconds or longer in the basic
screen.
Service Settings menu is displayed.
7-11
Select
Test operation
in the Service
Settings menu, and press Menu/Enter
button. Basic screen returns and
normal operation is conducted.
7-12
Check the functions according to the
operation manual.
7-13
When the decorative panel is not
installed, shut off the power supply
after the test operation finishes.
● If interior work is not completed after the
test operation finish, explain to the
customer that operation should not be
performed until the interior work comple
-
tion to protect the indoor unit.
(If the operation is performed, the
indoor unit may be contaminated with
the materials which arise from paints or
adhesives during the interior work, and
water splash or water leak may occur.)
7-6
Cool
Return
Setting
Test Operation
Press On/Off button
(within 10 seconds).
7-7
Return
Setting
Return
Setting
Air Volume/direction
Air Volume
Direction
Position 0
Low
Press Fan speed/airflow
direction button.
To select airflow direction
setting, press
(Right)
button on the setting screen.
7-9
Return
Setting
Return
Setting
Air Volume/direction
Air Volume
Direction
Low
Position 0
Change the airflow
direction by using
(Up/Down) button.
Press Menu/Enter button.
7-10
Cool
Return
Setting
Test Operation
Press and hold Cancel
button for 4 seconds or
longer during backlight lit.
7-11
Return
Setting
Service Settings 1/3
Test Operation
Maintenance Contact
Field Settings
Demand
Min Setpoints Differential
Group Address
Press Menu/Enter button.