Daikin BRC1E52A7 Installation Manual Download Page 17

BRC1E52A7 

Installation manual

4PW71264-1 – 10.2011 

16

7. Test operation method (in the case of 

SkyAir)

 

*

In the case of VRV, see the manual attached to the outdoor unit. 

Also see installation manuals attached to the indoor unit and the outdoor 

unit.

 

● Check that wiring work of the indoor unit and the outdoor unit is completed. 

 

● Check that switch box cover of the indoor unit and the outdoor unit is closed. 

 

● After refrigerant piping, drain piping and electric wiring are completed, clean inside of the indoor unit 

and decorative panel.

 

Perform the test operation according to following procedure. 

7-1 

Make sure to turn on the power supply 

more than 6 hours before operation 

start with front panel closed to protect 

compressor. 

7-2 

Confirm that stop valves of both liquid 

and gas are opened.  

<Make sure that outer panel and 

piping cover is closed before 

operation (danger of electric 

shock). >

 

*

After air purge by vacuum pump, 

refrigerant pressure may not rise 

even though the stop valve is 

opened. The reason is that refriger-

ant system of the outdoor unit is 

blocked by electrical expansion valve 

or the like. Operation is no problem.

7-3 

Set the operation mode to cooling by 

using the remote controller.

7-4 

Press and hold Cancel button for  

4 seconds or longer. Service Settings 

menu is displayed.

7-5 

Select 

 Test operation 

 in the Service 

Settings menu, and press Menu/Enter 

button. Basic screen returns and "Test 

operation" is displayed.

 

● The backlight will be lit for approximately 

 

30 seconds by pressing any operation button.

 

● Operate the buttons during the backlight lit. 

 

However, On/Off can be operated concur

-

rently with the backlight lit. 

Notes for backlight

<Basic screen>

7-3

7-4

Cool

Set to

Cool

28

°C

Press and hold Cancel 

button for 4 seconds or 

longer during backlight lit. 

<Service Setting menu screen>

7-5

Return

Setting

Service Settings                   1/3

Test Operation

Maintenance Contact

Field Settings

Demand

Min Setpoints Differential

Group Address

Press Menu/Enter button.

Summary of Contents for BRC1E52A7

Page 1: ...Be sure to read this installation manual before conducting the installation of this product BRC1E52A7 WIRED REMOTE CONTROLLER INSTALLATION MANUAL...

Page 2: ...ions and menu items of remote controller buttons 10 5 Power on 12 6 Field settings 13 7 Test operation method in the case of SkyAir 16 8 Checking procedure of Error History 19 9 Registration method of...

Page 3: ...regarding relocation and reinstallation of the remote controller Improper installation work may result in leakage electric shocks or fire hazards Install the remote controller in accordance with the i...

Page 4: ...Corroding of copper pipes or soldered parts may result in refrigerant leakage 3 Near machinery emitting electromagnetic radiation Electromagnetic radiation may disturb the operation of the control sys...

Page 5: ...hole to the center of the wiring through hole on the controller lower case when making the hole 8 10 External view of the remote controller Through hole 8 10 Lower case Through hole 48 5 40 3 3 Remove...

Page 6: ...e burr with a file or the like 3 4 3 Upper outlet 3 4 4 Upper center outlet Cut off thin area hatched area with nippers or the like and then remove burr with a file or the like Cut off thin area hatch...

Page 7: ...of two wires Sheath stripping length 150 mm for upper outlet 200 mm for upper center outlet Connect the terminals P P1 N P2 of the remote controller upper case with the terminals P1 P2 of the indoor u...

Page 8: ...t P1P2 3 5 3 Upper outlet Install attached wiring retainer to prevent wiring pinch according to left figure PC board Indoor unit Wiring retainer Wiring retainer Upper case Lower case Upper case Wiring...

Page 9: ...lower case In the case of wiring center upward drawing or rearward drawing see wiring procedure first as wiring with the case is needed before fixing 3 6 1 In the case of installation on the wall Sec...

Page 10: ...ect flat place for installation face as possible And do not tighten the installation screws too much not to deform the lower case CAUTION 3 7 Install the upper case as original condition Align the upp...

Page 11: ...anguage Depending on connected model 4 Up button Used to raise the set temperature The next items on the upper side will be highlighted The highlighted items will be scrolled continuously when the but...

Page 12: ...or unit AirNet Address Outdoor unit AirNet Address Error History Indoor Unit Status Outdoor Unit Status Forced Fan ON Switch Main Sub Controller Filter Indicator Test Filter Auto Clean Brush Filter In...

Page 13: ...controlled by two remote controllers Error code U5 is displayed in the connection checking screen Select the sub remote controller by pressing the Operation mode selector button of either one of the r...

Page 14: ...SECOND CODE NO of the FIRST CODE NO to be changed and select desired SECOND CODE NO by using Up Down button Multiple identical mode number settings are available In the case of group setting all of S...

Page 15: ...COND CODE NO Note 2 01 02 03 04 10 20 0 Filter Contamination Heavy Light Setting for spacing time of display time to clean air filter Setting for when filter contamination is heavy and spacing time of...

Page 16: ...c pressure setting according to the connected duct resistance for FHYK follow the high ceiling setting Normal High static pressure Low static pressure Normal High ceiling 15 25 3 Drain pump operation...

Page 17: ...k After air purge by vacuum pump refrigerant pressure may not rise even though the stop valve is opened The reason is that refriger ant system of the outdoor unit is blocked by electrical expansion va...

Page 18: ...test operation finishes If interior work is not completed after the test operation finish explain to the customer that operation should not be performed until the interior work comple tion to protect...

Page 19: ...the indoor unit After the failure diagnosis finishes press and hold On Off button for 4 seconds or longer in the Mainte nance Information screen to erase the error code record Failure diagnosis metho...

Page 20: ...ic screen Service Settings menu is displayed 8 2 Select Error History in the Service Settings menu and press Menu Enter button The Error History menu screen is displayed 8 3 Select RC Error History in...

Page 21: ...ter button Setting confirmation screen is displayed 9 6 Select Yes and press Menu Enter button Setting details are determined and Service Settings menu screen returns 9 7 Press Cancel button once The...

Page 22: ...Enter button 10 2 Press Cancel button twice The basic screen returns Basic screen 10 1 Cool Set to Cool 28 C Press Menu Enter button Main menu screen Return Setting Main menu Quick Start Ventilation E...

Page 23: ...ric changes continuously Day of the week is set automatically 11 4 Press Menu Enter button Setting confirmation screen is displayed 11 5 Select Yes and press Menu Enter button Setting details are conf...

Page 24: ...Up Down buttons to select Language on the Language screen English Deutsch Fran ais Espa ol Italiano E Nederlands Portugues Pycc rk e Polski Pressing Menu Enter button Setting details are confirmed an...

Page 25: ...unit Make sure that this controller is set to main factory set first change the restrictions to the setting you prefer and only then set the remote controller to sub 13 7 To lock menu button in basic...

Page 26: ...s sub start with only connecting this controller to the unit Make sure that this controller is set to main factory set first change the restrictions to the setting you prefer and only then set the rem...

Page 27: ......

Page 28: ...Copyright 2011 Daikin 4PW71264 1 10 2011...

Reviews: