2. BEFORE INSTALLATION

2-1 ABOUT THIS PRODUCT

1.

This product uses R744 (CO

2

) refrigerant.

The utmost attention is required to handle R744 refrigerant, and strict measures must be taken to keep 
impurities (including mineral oil and other types of oil as well as moisture) out of the system. Be sure to 
follow the instructions in “

7. REFRIGERANT PIPING WORK

”.

2.

The design pressure is 12.3 MPa (4.0 MPa for R410A). Therefore, the following conventional parts cannot 
be used.

• Connection pipes

Thick-walled pipes are required. Refer to “

7. REFRIGERANT PIPING WORK

” for the specifications of 

the pipes.

• Flare nut connections

Unavailable. Perform brazing connections.

• Pipe brazing joints

Pipes with a maximum diameter of 12.7mm .... Make brazing connections with sleeve flare processing.
Pipes with a diameter of 15.9mm ..................... Use sockets sold as optional accessories.

• Elbows

Use products sold as optional accessories.

• Installation instruments that must withstand high pressures, such as charge hoses and pressure gauges

Use pressure-resistant instruments that withstand a minimum pressure of 12.3 MPa.

3.

The indoor unit is an R744-dedicated unit. The following indoor unit models are connectable.
(Do not connect other indoor unit models, or otherwise an inner piping rupture will result.)

2-2 COMBINATION

Attach a BEV unit to the indoor unit. As shown in the below table.

2-3 ACCESSORIES

Check  if the following accessories are included with your unit.

BEV unit

BEVN32AV1

BEVN50AV1

BEVN125AV1

Indoor unit

FXSN20AV1
FXSN25AV1
FXSN32AV1

FXSN40AV1
FXSN50AV1

FXSN63AV1

FXSN100AV1

Name

Clamp

(3) Insulation for fitting

(4) Installation manual

Quantity

10 pcs.

2 pcs.

1 pc.

Shape

(1) 6 short pieces

(2) 4 long pieces

For liquid piping × 2

(I. D. 

φ

35)

(5) Caution label

1 pc.

Attach this to the EL. COMPO. BOX 
lid of the indoor unit after installation.

01_EN_3P233622-3F.fm  Page 3  Monday, December 22, 2008  10:59 AM

Summary of Contents for BEVN32AV1

Page 1: ...DE MAIN POUR REFERENCE ULTERIEURE LEA CUIDADOSAMENTE ESTAS INSTRUCCIONES ANTES DE INSTALAR GUARDE ESTE MANUAL EN UN LUGAR A MANO PARA LEER EN CASO DE TENER ALGUNA DUDA PRIMA DELL INSTALLAZIONE LEGGERE...

Page 2: ...urata Manager Quality Control Department 1st of October 2008 DAIKIN TCF 024C19 07 2008 T V Rheinland EPS B V 0510260101 RXYN10AY1 FXSN20AV1 FXSN25AV1 FXSN32AV1 FXSN40AV1 FXSN50AV1 FXSN63AV1 FXSN100AV1...

Page 3: ...nnel to carry out installation work Do not attempt to install the air conditioner yourself Improper installation may result in water leakage electric shocks or fire Install the air conditioner in acco...

Page 4: ...an earth leakage breaker Failure to install an earth leakage breaker may result in electric shocks or fire CAUTION Install the BEV units power cord and connecting wires at least 1 meter away from tele...

Page 5: ...5 9mm Use sockets sold as optional accessories Elbows Use products sold as optional accessories Installation instruments that must withstand high pressures such as charge hoses and pressure gauges Use...

Page 6: ...not exposed to rain or direct sunlight places with little dust or places with an ambient temperature of 60 C or below Where is resistible against weight of BEV unit Where the false ceiling is not noti...

Page 7: ...ing refrigerant and wiring including both power supply and transmission wiring up to the piping and wiring connections in the unit See 7 REFRIGERANT PIPING WORK and 8 ELECTRIC WIRING WORK for details...

Page 8: ...oduct withstanding 12 3 MPa Pipe wall thickness examples length mm Be sure to use pipes with clean outer and inner surfaces free of contaminants such as sulfides oxides dust chip oil and fat and moist...

Page 9: ...giving an adverse influence on a variety of valves and the compressor in the refrigerant system and obstructing the normal operation of the air con ditioner At the time of brazing with nitrogen being...

Page 10: ...tting 3 upward Use a clamp 2 to tighten both ends of the insulation for fitting Refer to Fig 4 Attached to the root Insulation for fitting 3 accessory Insulation for fitting 3 accessory Attached to th...

Page 11: ...r unit and BEV unit are properly matched If wiring and piping between the outdoor unit and an indoor unit and BEV unit are mismatched the system may cause a mal function A circuit breaker capable of s...

Page 12: ...he outdoor unit to ter minals F1 and F2 for the outdoor side of the first BEV unit 1 Model Units Power supply Hz Voltage Min Max MCA MFA BEVN32AV1 BEVN50AV1 BEVN125AV1 50 230 207 253 0 1 15 Model Powe...

Page 13: ...ground wire so that the cup washer will come out of the cutout part Otherwise the effect of grounding may be lost due to the insufficient contact of the ground wire Transmission wiring can be branche...

Page 14: ...supply wires into the equipment along with the ground wire through the wiring through hole and bundle and fix the wires securely with the accessory clamp 1 Clasp Clasp Clasp Ground terminal EL COMPO B...

Page 15: ...MPO BOX lid pay the utmost attention so that the wires will not be caught between the EL COMPO BOX lid After the wires are connected seal the wiring extraction part with putty or heat insulation mater...

Page 16: ...0901 HT 3P233622 3F EM08A070B...

Reviews: