10

English

(1) Electrical characteristics

MCA: Min. Circuit Amps (A); 

MFA: Max. Fuse Amps (A) 

NOTES

• The above Table of Electrical characteristics refers to the BEV unit only.
• See the technical documents for other details.

(2) Specifications for field supplied wire

*Use wire type H07RN-F when protected pipes are not used. 

NOTES

1.

Select the particular size of electrical wire for power line in accordance with the standards of the given nation and region.

2.

Specifications for local wiring are in compliance with IEC60245.

3.

Insulated thickness:1 mm or more

4.

Allowable length of the transmission wiring should be as follows.
Between outdoor unit, BEV unit and indoor unit:Max. 1000m (Total wiring length: 2000m)
Between BEV unit and remote controller: Max. 500m

5.

Up to 16 branches are possible for unit-to-unit cabling. No branching is allowed after branching.

8-2 EXAMPLE OF ENTIRE SYSTEM WIRING

An example of single-system wiring is shown here.

• Connect terminals F1 and F2 (the indoor-to-outdoor terminals) in the switchbox of the outdoor unit to ter-

minals F1 and F2 (for the outdoor side) of the first BEV unit 1.

Model

Units

Power supply

Hz

Voltage

Min.

Max.

MCA

MFA

BEVN32AV1
BEVN50AV1

BEVN125AV1

50

230

207

253

0.1

15

Model

Power supply wiring

Transmission wiring

Wire

Size

Wire

Size

BEVN32AV1
BEVN50AV1

BEVN125AV1

*H05VV

Size must comply with 
local codes.

Vinyl cord with

sheath or cable

(2 wire) (NOTE 2)

0.75 - 1.25 mm

2

F2

F1 F2 F1

A B C

IN/D OUT/D

F2

F1 F2

F1

Outdoor unit side Indoor unit side

F2

F1 F2

F1

Outdoor unit side Indoor unit side

Use two-conductor transmission 
wirings (with no polarity).

EL. COMPO. BOX 1

A B C

F1 F2

F1 F2

Indoor unit

Indoor unit

BEV unit 1

BEV unit 2

Do not open the lid of EL. COMPO. BOX 2 
(on the left-hand side), which is 
not touched during the installation work.

230V

16V

16V

16V

400V

B

B

Outdoor unit

BEV unit

Remote controller

COOL/HEAT selector

Indoor unit

Power supply

Power supply

Earth leakage breaker 
(used for ground fault, overload, 
and short-circuit protection)

B

Connect the line (with polarity-sensitive terminals) 
so that the terminal signs coincide.

COOL/HEAT selector

A1P

A5P

To outdoor unit of another 
refrigerant system

EL. 
COMPO.
BOX 2

Prohibited

Do not connect 
power supply wirings 
by any means.

Prohibited

01_EN_3P233622-3F.fm  Page 10  Monday, December 22, 2008  10:59 AM

Summary of Contents for BEVN32AV1

Page 1: ...DE MAIN POUR REFERENCE ULTERIEURE LEA CUIDADOSAMENTE ESTAS INSTRUCCIONES ANTES DE INSTALAR GUARDE ESTE MANUAL EN UN LUGAR A MANO PARA LEER EN CASO DE TENER ALGUNA DUDA PRIMA DELL INSTALLAZIONE LEGGERE...

Page 2: ...urata Manager Quality Control Department 1st of October 2008 DAIKIN TCF 024C19 07 2008 T V Rheinland EPS B V 0510260101 RXYN10AY1 FXSN20AV1 FXSN25AV1 FXSN32AV1 FXSN40AV1 FXSN50AV1 FXSN63AV1 FXSN100AV1...

Page 3: ...nnel to carry out installation work Do not attempt to install the air conditioner yourself Improper installation may result in water leakage electric shocks or fire Install the air conditioner in acco...

Page 4: ...an earth leakage breaker Failure to install an earth leakage breaker may result in electric shocks or fire CAUTION Install the BEV units power cord and connecting wires at least 1 meter away from tele...

Page 5: ...5 9mm Use sockets sold as optional accessories Elbows Use products sold as optional accessories Installation instruments that must withstand high pressures such as charge hoses and pressure gauges Use...

Page 6: ...not exposed to rain or direct sunlight places with little dust or places with an ambient temperature of 60 C or below Where is resistible against weight of BEV unit Where the false ceiling is not noti...

Page 7: ...ing refrigerant and wiring including both power supply and transmission wiring up to the piping and wiring connections in the unit See 7 REFRIGERANT PIPING WORK and 8 ELECTRIC WIRING WORK for details...

Page 8: ...oduct withstanding 12 3 MPa Pipe wall thickness examples length mm Be sure to use pipes with clean outer and inner surfaces free of contaminants such as sulfides oxides dust chip oil and fat and moist...

Page 9: ...giving an adverse influence on a variety of valves and the compressor in the refrigerant system and obstructing the normal operation of the air con ditioner At the time of brazing with nitrogen being...

Page 10: ...tting 3 upward Use a clamp 2 to tighten both ends of the insulation for fitting Refer to Fig 4 Attached to the root Insulation for fitting 3 accessory Insulation for fitting 3 accessory Attached to th...

Page 11: ...r unit and BEV unit are properly matched If wiring and piping between the outdoor unit and an indoor unit and BEV unit are mismatched the system may cause a mal function A circuit breaker capable of s...

Page 12: ...he outdoor unit to ter minals F1 and F2 for the outdoor side of the first BEV unit 1 Model Units Power supply Hz Voltage Min Max MCA MFA BEVN32AV1 BEVN50AV1 BEVN125AV1 50 230 207 253 0 1 15 Model Powe...

Page 13: ...ground wire so that the cup washer will come out of the cutout part Otherwise the effect of grounding may be lost due to the insufficient contact of the ground wire Transmission wiring can be branche...

Page 14: ...supply wires into the equipment along with the ground wire through the wiring through hole and bundle and fix the wires securely with the accessory clamp 1 Clasp Clasp Clasp Ground terminal EL COMPO B...

Page 15: ...MPO BOX lid pay the utmost attention so that the wires will not be caught between the EL COMPO BOX lid After the wires are connected seal the wiring extraction part with putty or heat insulation mater...

Page 16: ...0901 HT 3P233622 3F EM08A070B...

Reviews: