7
|
Piping installation
Installer reference guide
25
BEV2N-A
CO₂ Conveni-Pack: BEV2 unit
4P677928-1 – 2021.10
WARNING
▪
Use K65 piping for high-pressure applications with a working pressure of 120 bar
or 90 bar, depending on its location in the system.
▪
Use K65 unions and fittings approved for a working pressure of 120 bar or 90 bar,
depending on its location in the system.
▪
ONLY brazing is allowed for connection of pipes. No other types of connections
are allowed.
▪
Expanding of pipes is NOT allowed.
1
Insert the field pipe into the piping on the BEV2 unit side.
2
Connect refrigerant piping to the unit using only
brazed connections
.
NOTICE
When brazing, place a wet cloth on the insulation attached on the unit (
a
) and make
sure the temperature does not exceed 200°C.
a
d
c
b
e
a
BEV2 unit
b
Piping on the BEV2 unit side
c
Insulation attached on the unit
d
Brazed connection
e
Field piping
3
Insulate
the refrigerant piping on the BEV2 unit as follows:
b
3
a
c
d
e
f
a
b
b
b
c
e
2
1
3
1
2
a
Insulation material (field supply)
b
Tie wraps (accessory)
c
Insulation pieces (accessory)
d
Brazed connection
e
Refrigerant pipe connection (attached to the unit)
f
Unit
1
Turn up the seams of the insulation pieces.
2
Attach to the base of the unit.
3
Tighten the tie wrap on the insulation pieces.
a
a
Seam of the insulation piece (accessory) facing up
NOTICE
Make sure to insulate all refrigerant piping. Any exposed piping might cause
condensation.