Troubleshooting by Error Code
SiUS341802E
253
Service Diagnosis
2.56 Refrigerant Shortage
Error Code
U0
Applicable
Models
All outdoor unit models
Method of Error
Detection
Detect refrigerant shortage according to a low pressure level or a difference in heat exchanging
temperature from the suction pipe.
Error Decision
Conditions
Low pressure becomes 0.1 MPa (14.5 psi) or less.
∗
Error is not determined. The unit continues the operation.
Supposed
Causes
Refrigerant shortage and refrigerant clogging (wrong piping)
Defective thermistor
Defective low pressure sensor
Defective outdoor unit main PCB
Troubleshooting
Notes:
∗
1. Check the low pressure value by using pressure gauge in operation.
∗
2. Compare the actual measurement value by pressure sensor with the value by the pressure
gauge.
(To gain actual measurement value by pressure sensor, measure the voltage at the connector
[between (2)-(3)] and then convert the value into pressure.
)
Is the low
pressure 0.1 MPa
(14.5 psi) or less?
(
∗
1)
Is the
characteristics of
low pressure sensor
normal? (
∗
2)
Replace the low pressure
sensor (S1NPL).
Replace the outdoor unit
main PCB (A1P).
NO
NO
YES
YES
Remove the factor of
decreasing low pressure.
CHECK 2
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
(1) Mount a pressure gauge at the service port on the low
pressure side.
(2) Reset the operation using the remote controller then
restart.
CHECK 12
CHECK 2
CHECK 12
Summary of Contents for Aurora Series
Page 317: ...SiUS341802E Wiring Diagrams Appendix 304 RXLQ96 120TATJU 2D112581A ...
Page 318: ...Wiring Diagrams SiUS341802E 305 Appendix RXLQ72TAYDU 2D112582A ...
Page 319: ...SiUS341802E Wiring Diagrams Appendix 306 RXLQ96 120TAYDU 2D112583A ...
Page 331: ...SiUS341802E Wiring Diagrams Appendix 318 VAM1200GVJU 3D073270C ...
Page 332: ...Revision History Month Year Version Revised contents 04 2018 SiUS341802E First edition ...