1-12

SPECIAL PRECAUTIONS WHEN DEALING WITH R410A UNIT

R410A is a new HFC refrigerant which does not damage the 
ozone layer. The working pressure of this new refrigerant is 
1.6 times higher than conventional refrigerant (R22), thus 
proper installation/servicing is essential.

Never use refrigerant other than R410A in an air conditioner 
which is designed to operate with R410A.
POE or PVE oil is used as lubricant for R410A compressor, 
which is different from the mineral oil used for R22 
compressor. During installation or servicing, extra precaution 
must be taken not to expose the R410A system too long 
to moist air. Residual POE or PVE oil in the piping and 
components can absorb moisture from the air.
To prevent mischarging, the diameter of the service port on 
the 

fl

 are valve is different from that of R22.

Use tools and materials exclusively for refrigerant R410A. 
Tools exclusively for R410A are manifold valve, charging 
hose, pressure gauge, gas leak detector, 

fl

 are tools, torque 

wrench, vacuum pump and refrigerant cylinder.
As an R410A air conditioner incurs higher pressure 
than R22 units, it is essential to choose the copper pipes 
correctly. 
If the refrigerant gas leakage occurs during installation/
servicing, be sure to ventilate fully. If the refrigerant gas 
comes into contact with 

fi

 re, a poisonous gas may occur.

When installing or removing an air conditioner, do not 
allow air or moisture to remain in the refrigerant cycle.

VACUUMING AND CHARGING

Vacuuming is necessary to eliminate all moisture and air from the system. 

Vacuuming The Piping And The Indoor Unit

Except for the outdoor unit which is pre-charged with 
refrigerant, the indoor unit and the refrigerant connection 
pipes must be air-purged because the air containing moisture 
that remains in the refrigerant cycle may cause malfunction 
of the compressor.

Remove the caps from the valve and the service port.
Connect the center of the charging gauge to the vacuum 
pump.
Connect the charging gauge to the service port of the 3-way 
valve.
Start the vacuum pump. Evacuate for approximately 30 
minutes. The evacuation time varies with different vacuum 
pump capacity. Con

fi

 rm that the charging gauge needle has 

moved towards -760mmHg.

Caution

If the gauge needle does not move to -760mmHg, be sure 
to check for leakage at 

fl

 are type connection of the indoor 

and outdoor unit and repair the leak before proceeding to 
the next step.
Close the valve of the changing gauge and stop the vacuum 
pump.
On the outdoor unit, open the suction valve (3 way) and 
liquid valve (2 way) (in anti-clockwise direction) with 4mm 
key for hexagon sacked screw.

Charge Operation

This operation must be done by using a gas cylinder and a 
precise weighing machine. The additional charge is topped-up 
into the outdoor unit using the suction valve via the service 
port.

Remove the service port cap.
Connect the low pressure side of the charging gauge to the 
suction service port center of the cylinder tank and close 
the high pressure side of the gauge. Purge the air from the 
service hose.
Start the air conditioner unit.
Open the gas cylinder and low pressure charging valve.
When the required refrigerant quantity is pumped into 
the unit, close the low pressure side and the gas cylinder 
valve.
Disconnect the service hose from service port. Put back 
the service port cap.





Refrigerant Piping

Outdoor Unit 3 ways valve

Allen key

Service Port

Flare nut

HIGH PRESSURE GAUGE

GAUGE MANIFOLD

LOW PRESSURE GAUGE

HANDLE 

HI 

(ALWAYS CLOSED)

CHARGE HOSE

-760mmHg

HANDLE 

LO

CHARGE HOSE

VACUUM PUMP 
ADAPTER FOR 
COUNTER FLOW 
PREVENTION

CHECK VALVE

LIQUID VALVE

HIGH PRESSURE GAUGE

LOW PRESSURE GAUGE

GAUGE MANIFOLD

-760mmHg

HANDLE 

LO

HANDLE 

HI 

(ALWAYS CLOSED)

CHARGE HOSE

CHARGE HOSE

CHECK VALVE

LIQUID VALVE

GAS VALVE 
(3-WAY)

CONFIGURATION OF AIR 
PURGE BY CHARGING

CONFIGURATION OF AIR 
PURGE BY CHARGING

GAS VALVE 
(3-WAY)

1 IM-5WMJR-0515(0)-DAIKIN SIESTA12   12

1 IM-5WMJR-0515(0)-DAIKIN SIESTA12   12

6/1/15   3:20:43 PM

6/1/15   3:20:43 PM

Интернет

-

магазин

 «

Мистер

 

Климат

» 

Тел

.: 8-800-5555-710

www.mrklimat.ru

Summary of Contents for ARYN20L

Page 1: ...DITIONER IM 5WMJR 0515 0 DAIKIN SIESTA Part No R08019043338 Installation Manual R410A Split Type Air Conditioner Руководство по установке R410A разделить Кондиционер воздуха типа English Русский CVR IM 5WMJR 0515 0 DAIKIN SIES1 1 CVR IM 5WMJR 0515 0 DAIKIN SIES1 1 6 3 15 1 54 19 PM 6 3 15 1 54 19 PM Интернет магазин Мистер Климат Тел 8 800 5555 710 www mrklimat ru ...

Page 2: ...CVR IM 5WMJR 0515 0 DAIKIN SIES2 2 CVR IM 5WMJR 0515 0 DAIKIN SIES2 2 6 1 15 3 20 21 PM 6 1 15 3 20 21 PM Интернет магазин Мистер Климат Тел 8 800 5555 710 www mrklimat ru ...

Page 3: ...INSIDE NAME PLATE TERMINAL BLOCK WITH EARTH TERMINAL F E J G G L D B K M A Gas pipe end INSTALLATION PLATE 20 25 35J Liquid pipe end Through the wall hole Ø 65mm All dimensions are in mm Drain hose position F Recommended mounting plate retention spots 5 spots in all Use tape measure as shown Position the end of a tape measure at Ñ Dimension Model A B C D E F G H I J K L M 20 25 35J 800 288 206 166...

Page 4: ...spots 7 spots in all Dimension Model A B C D E F G H I J K L M 20 25 35J 800 288 206 104 141 30 46 55 56 153 181 207 52 Recommended mounting plate retention spots 5 spots in all Through the wall hole Ø 65mm Drain hose position Gas pipe end Liquid pipe end E F G I K M L J H G F B D A ALTERNATIVE INSTALLATION PLATE 20 25 35J 1 IM 5WMJR 0515 0 DAIKIN SIESTA2 2 1 IM 5WMJR 0515 0 DAIKIN SIESTA2 2 6 1 1...

Page 5: ...All dimensions are in mm B A Q P R S D O K L L M N F E C G H I J N Dimension Model A B C D E F G H I J K L 50C 855 628 328 520 179 46 93 149 101 113 603 126 60C 855 730 328 520 179 46 93 149 101 113 603 126 Dimension Model M N O P Q R S 50C 164 15 34 23 362 73 75 60C 164 15 34 23 362 73 75 Outdoor Unit ARYN All dimensions are in mm 1 IM 5WMJR 0515 0 DAIKIN SIESTA3 3 1 IM 5WMJR 0515 0 DAIKIN SIESTA...

Page 6: ...source of the electrical waves static may be heard even when more than 1m away Please take note of the following important points when installing Do not install the unit where leakage of flammable gas may occur If gas leaks and accumulates around the unit it may cause fire ignition Ensure that drainage piping is connected properly If the drainage piping is not connected properly it may cause water...

Page 7: ... down INSTALLATION DIAGRAM Indoor unit Service lid Cut thermal insulation pipe to an appropriate length and wrap it with tape making sure that no gap is left in the insulation pipe s cut line Caulk pipe hole gap with putty Wrap the insulation pipe with the finishing tape from bottom to top Outdoor Unit 500mm from wall 1 IM 5WMJR 0515 0 DAIKIN SIESTA5 5 1 IM 5WMJR 0515 0 DAIKIN SIESTA5 5 6 1 15 3 2...

Page 8: ... UP BASE A DRAIN ELBOW DRAIN ELBOW PLUG INSTALLATION OF THE OUTDOOR UNIT The outdoor unit must be installed in such a way so as to prevent short circuit of the hot discharged air or obstruction to the smooth air flow Please follow the installation clearances shown in the figure Select the coolest possible place where intake air temperature is not greater than the outside air temperature please ref...

Page 9: ...ottom piping Right side piping Remove pipe port cover here for right side piping Left back piping Left side piping Left bottom piping Left Side Left Back or Left Bottom Piping INSTALLATION OF THE INDOOR UNIT Remove pipe port cover here for right bottom piping Bind coolant pipe and drain hose together with insulating tape Remove pipe port cover here for left side piping Remove pipe port cover here ...

Page 10: ...ws Mounting plate Interconnecting wires Hang indoor unit s hook here Wire guide When stripping the ends of interconnecting wires in advance bind right ends of wires with insulating tape Through the wall hole Ø 65mm Drain hose position Gas pipe end Liquid pipe end Recommended Mounting Plate Retention SpotsAnd Dimensions 166 184 181 7 55 5 54 5 153 8 263 51 9 800 45 9 42 2 288 42 2 45 9 Hole With Co...

Page 11: ...8 9 52 3 8 12 70 1 2 12 70 1 2 15 88 5 8 Liquid Pipe Size mm in 6 35 1 4 6 35 1 4 6 35 1 4 6 35 1 4 6 35 1 4 Heat Pump Model If the pipe is too long both the capacity and reliability of the unit will drop As the number of bends increases resistance to the flow of refrigerant system increases thus lowering cooling capacity As a result the compressor may become defective Always choose the shortest p...

Page 12: ...punch then tighten the flaring punch fully Piping Connection To The Units Align the center of the piping and tighten the flare nut sufficiently with fingers See Figure IV Finally tighten the flare nut with torque wrench until the wrench clicks When tightening the flare nut with the torque wrench ensure that the tightening direction follows the arrow indicated on the wrench The refrigerant pipe con...

Page 13: ...es must be firmly connected All wires must not touch the refrigerant piping compressor or any moving parts of the fan motor The connecting wires between the indoor unit and the outdoor unit must be clamped on the wire clamps The power supply cord must be equivalent to H07RN F which is the minimum requirement Make sure no external pressure is applied to the terminal connectors and wires Make sure a...

Page 14: ...harging gauge to the vacuum pump Connect the charging gauge to the service port of the 3 way valve Start the vacuum pump Evacuate for approximately 30 minutes The evacuation time varies with different vacuum pump capacity Confirm that the charging gauge needle has moved towards 760mmHg Caution If the gauge needle does not move to 760mmHg be sure to check for leakage at flare type connection of the...

Page 15: ...automatically to either cool or heat mode according to the temperature set by the user ON OFF Cool Heat Timer Sleep ON OFF switch The refrigerant is pre charged in the outdoor unit If the piping length is less than 7 5m then additional charge after vacuuming is not necessary If the piping length is more than 7 5m then use the additional charge value as indicated in the table IR Receiver INDICATOR ...

Page 16: ...oil sensor open Call your dealer Blink E3 2 times Indoor coil sensor open Call your dealer Blink E2 1 time Compressor overload Indoor coil sensor short outdoor coil sensor short Call your dealer Blink E4 Red Defrost operation 3 times Gas leak Call your dealer Blink E5 6 times Hardware error tact switch pin short Call your dealer Blink E8 4 times No feedback from indoor fan Call your dealer Blink E...

Page 17: ... and or the external temperature is too high or that the filter is dirty and clogged up the refrigerant may be overheated The compressor will cut out when the condensing temperature reaches 62 C 143 6 F Frost Prevention When the air filter is dirty the evaporating temperature will decrease and eventually cause frosting If the evaporating temperature reaches 1 C 33 8 F the unit will trip Fan Speed ...

Page 18: ...nt side to remove it 2 Attach the front panel Align the right and left rotating shafts of the front panel with the grooves and push them all the way in Gently close the front panel Push both ends and the center on the front panel 3 CAUTION Avoid direct contact of any coil treatment cleaners on plastic part This may cause plastic part to deform as a result of chemical reaction Service Parts Mainten...

Page 19: ...igarettes smoke particles perfume etc which might have adhered onto the coil Condensation on the front air grille of the indoor unit 5 This is caused by air humidity after an extended long period of operation The set temperature is too low increase the temperature setting and operate the unit at high fan speed Water flowing out from the air conditioner unit 6 Switch off unit and call dealer If the...

Page 20: ...MEMO 1 IM 5WMJR 0515 0 DAIKIN SIESTA18 18 1 IM 5WMJR 0515 0 DAIKIN SIESTA18 18 6 1 15 3 20 44 PM 6 1 15 3 20 44 PM Интернет магазин Мистер Климат Тел 8 800 5555 710 www mrklimat ru ...

Page 21: ...ИГНАЛА КОМНАТНЫЙ БЛОК ПЕРЕКЛЮЧАТЕЛЬ ВКЛ ВЫКЛ ТЕРМОРЕЗИСТОР КОМНАТНОЙ ТЕМПЕРАТУРЫ ВНУТРИ ЗАВОДСКАЯ БИРКА ТЕРМИНАЛ С КЛЕММОЙ ЗАЗЕМЛЕНИЯ F E J G G L D B K M A Конец газовой трубы МОНТАЖНАЯ ПЛИТА 20 25 35J Конец жидкостной трубы Сквозное отверстие в стене Ø 65мм Все размеры указаны в мм Позиция дренажного шланга F Рекомендуемые позиции закрепления установочной платы всего 5 позиций Используйте мерную ...

Page 22: ...ой платы всего 7 позиций Рекомендуемые позиции закрепления установочной платы всего 5 позиций Сквозное отверстие в стене Ø 65мм Позиция дренажного шланга Конец газовой трубы Конец жидкостной трубы E F G I K M L J H G F B D A АЛЬТЕРНАТИВНЫЙ ВАРИАНТ УСТАНОВКИ ПЛАСТИНА 20 25 35J Все размеры указаны в мм Сквозное отверстие в стене Ø 65мм Позиция дренажного шланга 2 IM 5WMJR 0515 0 DAIKIN SIESTA2 2 2 I...

Page 23: ...се размеры указаны в мм B A Q P R S D O K L L M N F E C G H I J N Размер Модель A B C D E F G H I J K L 50C 855 628 328 520 179 46 93 149 101 113 603 126 60C 855 730 328 520 179 46 93 149 101 113 603 126 Размер Модель M N O P Q R S 50C 164 15 34 23 362 73 75 60C 164 15 34 23 362 73 75 Hаружного блок ARYN Все размеры указаны в мм 2 IM 5WMJR 0515 0 DAIKIN SIESTA3 3 2 IM 5WMJR 0515 0 DAIKIN SIESTA3 3...

Page 24: ...ки начнут вращаться и обслуживающий персонал или пользователь подвергнется опасности Не устанавливайте блоки в дверном проеме или в непосредственной близости с ним Не допускайте работы каких либо обогревательных приборов в непосредственнойблизостисблокомкондиционеравоздухаинеиспользуйте впомещении вкоторомимеетсяминеральноемасло парынефтиилимасла таккакэтоможетпривестикрасплавлениюилидеформациипла...

Page 25: ...Комнатного блок Наружный блок Сервисная крышка Обрежьте трубу тепловой изоляции до требуемой длины и обмотйте ее лентой тледя за отсутствием зазоров по линии обреза трубы обмотайте изоляционную трубу лентой наружного покрытия снизу доверху заделайте зазор в месте отверстия для трубы шпатлевкой 500мм от стены Обмотайте изоляционную трубу лентой наружного покрытия снизу доверху 2 IM 5WMJR 0515 0 DAI...

Page 26: ...соединительного шнура следует снять боковую пластину НАДАВИТЬ И ПОТЯНУТЬ УСТАНОВКА НАРУЖНОГО БЛОКА Наружный блок должен быть установлен таким образом чтобы предотвратить замыкание горячего выпускаемого воздуха или образование препятствия для воздушного потока Пожалуйста соблюдайте установочные габариты показанные на рисунке Выберите самое прохладное место где температура воздуха на впуске не превы...

Page 27: ... труб справа снизу Подвод труб с правой стороны Подвод труб слева сэади Подвод труб c левой стороны Подвод труб слева сниэу Левый боковой левый задний или левый нижний трубопровод УСТАНОВКА КОМНАТНОГО БЛОКА Для подвода труб справа снизу снпмите концевую крышку трубы на данной позиции Для подвода труб с правой стороны снпмите концевую крышку трубы на данной позиции Свяжите трубy oxлаждения и дренаж...

Page 28: ...как внутренний так и наружный блоки на высоте более 2000м над уровнем моря 190 173 61 310 61 конецгазовойтрубы конец жидкостной трубы 48 45 580 1065 219 40 40 91 45 Сквозноеотверстие встенеØ65мм Позициядренажного шланга Конец газовой трубы Конец жидкостной трубы Рекомендуемая Разметка Крепления Установочной Пластины И Размеры 166 184 181 7 55 5 54 5 153 8 263 51 9 800 45 9 42 2 288 42 2 45 9 Пpocв...

Page 29: ...е 7 5м Проконтролируйте добавление требуемого количества допо лнительного хладагента Невыполнение данного требования чревато ухудшением качества функционирования Модель Комнатный ATYN 20J 25J 35J 50J 60J Наружный ARYN 20C 25C 35C 50C 60C Mин допустимая длина L м 3 Maкс допустимая длина L м 12 12 12 20 20 Максимальная допустимое поднятие E м 5 5 5 15 15 РазмерТрубы Для Г аза мм дюймах 9 52 3 8 9 52...

Page 30: ...чном пробойнике а затем полностью затяните развальцовочный пробойник СоединениеТрубопроводов К блокам Отцентрируйте положение трубы и до конца затяните штуцерную гайку усилием пальцев Смотрите Рисунок IV Затем затяните штуцер динамометрическим гаечным ключом до щелчка ключа Призатягиваниимуфтыдинамометрическимгаечнымключом удостоверьтесь что затягивание происходит в указанном стрелкой направлении ...

Page 31: ...тропроводка должна не приходить в соприкосновение с хладагентом насоса или лопастей двигателя Соединительные провода между комнатным и наружным блоками должны быть закреплены на зажимах для проводов Шнур сети питания должен отвечать параметрам шнура H07RN F который представляет собой минимальные предъявляемые требования Убедитесь что соединительные зажимы и провода не подвергаются излишней нагрузк...

Page 32: ...оробки к вакуумному насосу Cоедините нагнетательную коробку к 3 ходовому клапану входа технического обслуживания Включите вакуумный насос Проводите откачку в течение примерно 30 минут Время откачки зависит от мощности вакуумного насоса Удостоверьтесь что стрелка манометра нагнетательной коробки установилась на 760мм ртутного столба Осторожно Если стрелка указателя не перемещается в 760мм ртутного ...

Page 33: ...т заправлен заводом изготовителем на внешнем модуле Если длина трубопроводов меньше чем 7 5м то в дозаправке после откачки воздуха нет необходимости Если длина трубопровода превышает 7 5м используйте значение дозаправки указанное в таблице Приемник ИК сигналов ПОКАЗАНИЯ ИНДИКАТОРОВ ВКЛ на ВЫКЛ 1 долгий звуковой сигнал ВЫКЛ на ВКЛ Откачка Воздействие Охлаждением 2 коротких звуковых сигнала Дополнит...

Page 34: ...ого змеевика открыт Обратитесь к своему дилеру Мигает E3 2 раза Датчик внутреннего змеевика открыт Обратитесь к своему дилеру Мигает E2 1 времена Перегрузка компрессора Короткое замыкание датчика внутреннего змеевика Обратитесь к своему дилеру Мигает E4 Красный Процесс размораживания 3 раза Утечка газа Обратитесь к своему дилеру Мигает E5 6 раза Аппаратная ошибка тактовый переключатель вывод замкн...

Page 35: ...м высокая внутренняя и или внешняя температура загрязненность или засорение фильтра могут привести к перегреву хладагента При достижении температурой конденсации 62 C 143 6 F компрессор выключится Предотвращение Замерзания При загрязнении воздушного фильтра температура испарения будет уменьшаться что приведет со временем к замерзанию Еслитемператураиспарениядостигает 1 C 33 8 F модульавтоматически...

Page 36: ...дней стороне для снятия 2 Прикрепите лицевую панель Выровняйте правую и левую оси вращения лицевой панели с пазами и протолкните их Осторожно закройте лицевую панель Нажмите на лицевую панель c обоих концов и по центру 3 ОCTOPOЖHO Не допускайте контакта средств применяемых для очистки змеевика с пластмассовыми деталями Они вступают в реакцию с пластмассой а это может стать причиной деформации дета...

Page 37: ...ержки установлен неправильно Если неисправность не удается устранить после проведения всех проверок обратитесь к Вашему установщику кондиционера Очень незначительный поток воздуха 3 Воздушный фильтр загрязнен Открыты двери или окна Забился впуск и выпуск воздуха Установленная температура недостаточно высока При выпуске воздуха имеется неприятный запах 4 Неприятный запах может быть вызван сигаретам...

Page 38: ...ПАМЯТКА 2 IM 5WMJR 0515 0 DAIKIN SIESTA18 18 2 IM 5WMJR 0515 0 DAIKIN SIESTA18 18 6 10 15 9 16 20 AM 6 10 15 9 16 20 AM Интернет магазин Мистер Климат Тел 8 800 5555 710 www mrklimat ru ...

Page 39: ...CVR IM 5WMJR 0515 0 DAIKIN SIES3 3 CVR IM 5WMJR 0515 0 DAIKIN SIES3 3 6 1 15 3 20 21 PM 6 1 15 3 20 21 PM Интернет магазин Мистер Климат Тел 8 800 5555 710 www mrklimat ru ...

Page 40: ...авляет за собой право изменять характеристики и конструкцию в любое время без предварительного уведомления P O Box 18674 Galleries 4 11th Floor Downtown Jebel Ali Dubai UAE Zandvoordestraat 300 B 8400 Oostende Belgium Importer for Turkey Allianz Plaza Kucukbakkalkoy Mah Kayısdagi Cad No 1 34750 Atasehir ISTANBUL TURKIYE Head office Umeda Center Bldg 2 4 12 Nakazaki Nishi Kita ku Osaka 530 8323 Jap...

Reviews: