3 About the box

Installation manual

5

RXQ-A_ARXQ-A
R32 split series
3P664524-2A – 2021.07

WARNING

Use  an  all-pole  disconnection  type  breaker  with  at  least
3  mm  between  the  contact  point  gaps  that  provide  full
disconnection under overvoltage category III.

WARNING

If the supply cord is damaged, it MUST be replaced by the
manufacturer,  its  service  agent  or  similarly  qualified
persons in order to avoid a hazard.

WARNING

Do NOT connect the power supply to the indoor unit. This
could result in electrical shock or fire.

WARNING

▪ Do  NOT  use  locally  purchased  electrical  parts  inside

the product.

▪ Do  NOT  branch  the  power  supply  for  the  drain  pump,

etc.  from  the  terminal  block.  This  could  result  in
electrical shock or fire.

WARNING

Keep  the  interconnection  wiring  away  from  copper  pipes
without thermal insulation as such pipes will be very hot.

DANGER: RISK OF ELECTROCUTION

All  electrical  parts  (including  thermistors)  are  powered  by
the power supply. Do NOT touch them with bare hands.

DANGER: RISK OF ELECTROCUTION

Disconnect  the  power  supply  for  more  than  10  minutes,
and  measure  the  voltage  at  the  terminals  of  main  circuit
capacitors  or  electrical  components  before  servicing.  The
voltage MUST be less than 50 V DC before you can touch
electrical  components.  For  the  location  of  the  terminals,
see the wiring diagram.

Finishing indoor unit installation (see 

"8 Finishing the outdoor

unit installation"

 [

4

 11])

DANGER: RISK OF ELECTROCUTION

▪ Make sure that the system is earthed properly.

▪ Turn OFF the power supply before servicing.

▪ Install  the  switch  box  cover  before  turning  ON  the

power supply.

Commissioning (see 

"9 Commissioning"

 [

4

 11])

DANGER: RISK OF ELECTROCUTION

DANGER: RISK OF BURNING/SCALDING

CAUTION

Do  NOT  perform  the  test  operation  while  working  on
the indoor units.

When  performing  the  test  operation,  NOT  ONLY  the
outdoor unit, but the connected indoor unit will operate as
well.  Working  on  an  indoor  unit  while  performing  a  test
operation is dangerous.

CAUTION

Do  NOT  insert  fingers,  rods  or  other  objects  into  the  air
inlet  or  outlet.  Do  NOT  remove  the  fan  guard.  When  the
fan is rotating at high speed, it will cause injury.

Maintenance and service (see 

"10 Maintenance and

service"

 [

4

 11])

DANGER: RISK OF ELECTROCUTION

DANGER: RISK OF BURNING/SCALDING

WARNING

▪ Before  carrying  out  any  maintenance  or  repair  activity,

ALWAYS  switch  off  the  circuit  breaker  on  the  supply
panel, remove the fuses or open the protection devices
of the unit.

▪ Do NOT touch live parts for 10 minutes after the power

supply is turned off because of high voltage risk.

▪ Please  note  that  some  sections  of  the  electric

component box are hot.

▪ Make sure you do NOT touch a conductive section.

▪ Do NOT rinse the unit. This may cause electric shocks

or fire.

About the compressor

DANGER: RISK OF ELECTROCUTION

▪ Use this compressor on a grounded system only.

▪ Turn the power off before servicing the compressor.

▪ Reattach  the  switch  box  cover  and  service  lid  after

servicing.

CAUTION

Always wear safety goggles and protective gloves.

DANGER: RISK OF EXPLOSION

▪ Use a pipe cutter to remove the compressor.

▪ Do NOT use the brazing torch.

▪ Use approved refrigerants and lubricants only.

DANGER: RISK OF BURNING/SCALDING

Do NOT touch the compressor with bare hands.

3

About the box

3.1

Outdoor unit

3.1.1

To remove the accessories from the
outdoor unit

1

Lift the outdoor unit.

2

Remove the accessories at the bottom of the package.

b

c

d

a

e

a

General safety precautions

b

Outdoor unit installation manual

c

Fluorinated greenhouse gases label

d

Multilingual fluorinated greenhouse gases label

e

Energy label

Summary of Contents for ARXQ25AMV1B

Page 1: ...Installation manual R32 split series English Installation manual R32 split series RXQ25AMV1B RXQ35AMV1B ARXQ25AMV1B ARXQ35AMV1B ...

Page 2: ...ašimi navodili on vastavuses järgmis t e standardi te ga või teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele съответстват на следните стандарти или други нормативни документи при условие че се използват съгласно нашите инструкции atitinka žemiau nurodytus standartus ir arba kitus norminius dokumentus su sąlyga kad yra naudojami pagal mūsų nurodymus tad ja lietoti...

Page 3: ...lation servicing maintenance repair and applied materials follow the instructions from Daikin and in addition comply with applicable legislation and are performed by qualified persons only In Europe and areas where IEC standards apply EN IEC 60335 2 40 is the applicable standard INFORMATION This document only describes installation instructions specific to the outdoor unit For installation of the ...

Page 4: ... the valves before flaring is complete This would cause refrigerant gas leakage DANGER RISK OF EXPLOSION Do NOT start the unit if it is vacuumed Charging refrigerant see 6 Charging refrigerant 48 WARNING The refrigerant inside the unit is mildly flammable but normally does NOT leak If the refrigerant leaks in the room and comes in contact with fire from a burner a heater or a cooker this may resul...

Page 5: ...CALDING CAUTION Do NOT perform the test operation while working on the indoor units When performing the test operation NOT ONLY the outdoor unit but the connected indoor unit will operate as well Working on an indoor unit while performing a test operation is dangerous CAUTION Do NOT insert fingers rods or other objects into the air inlet or outlet Do NOT remove the fan guard When the fan is rotati...

Page 6: ...ound reflections INFORMATION The sound pressure level is less than 70 dBA The outdoor unit is designed for outdoor installation only and for ambient temperatures within the following ranges unless otherwise specified in the operation manual of the connected indoor unit Cooling mode Heating mode 10 46 C DB 15 24 C DB 4 1 2 Additional installation site requirements of the outdoor unit in cold climat...

Page 7: ...g material Piping material Phosphoric acid deoxidised seamless copper Flare connections Only use annealed material Piping temper grade and thickness Outer diameter Ø Temper grade Thickness t a 6 4 mm 1 4 Annealed O 0 8 mm t Ø 9 5 mm 3 8 Annealed O a Depending on the applicable legislation and the maximum working pressure of the unit see PS High on the unit name plate larger piping thickness might ...

Page 8: ... 5 3 1 To check for leaks NOTICE Do NOT exceed the unit s maximum working pressure see PS High on the unit name plate NOTICE ALWAYS use a recommended bubble test solution from your wholesaler NEVER use soap water Soap water may cause cracking of components such as flare nuts or stop valve caps Soap water may contain salt which absorbs moisture that will freeze when the piping gets cold Soap water ...

Page 9: ...unt 6 4 To charge additional refrigerant WARNING Only use R32 as refrigerant Other substances may cause explosions and accidents R32 contains fluorinated greenhouse gases Its global warming potential GWP value is 675 Do NOT vent these gases into the atmosphere When charging refrigerant ALWAYS use protective gloves and safety glasses Prerequisite Before charging refrigerant make sure the refrigeran...

Page 10: ...ge at the terminals of main circuit capacitors or electrical components before servicing The voltage MUST be less than 50 V DC before you can touch electrical components For the location of the terminals see the wiring diagram DC DC h g f e b a c d a DB1 diode bridge b Multimeter DC voltage range c S80 reversing solenoid valve lead wire d S71 fan motor lead wire e S30 compressor motor lead wire f ...

Page 11: ...ant leaks The refrigerant pipes gas and liquid are thermally insulated The correct pipe size is installed and the pipes are properly insulated The stop valves gas and liquid on the outdoor unit are fully open Drainage Make sure drainage flows smoothly Possible consequence Condensate water might drip The indoor unit receives the signals of the user interface The specified wires are used for the int...

Page 12: ...overview below by in the part code Symbol Meaning Symbol Meaning Circuit breaker Protective earth Connection Protective earth screw Connector A Rectifier Earth Relay connector Field wiring Short circuit connector Fuse Terminal INDOOR Indoor unit Terminal strip OUTDOOR Outdoor unit Wire clamp Residual current device Symbol Colour Symbol Colour BLK Black ORG Orange BLU Blue PNK Pink Symbol Colour Sy...

Page 13: ...switch low S T Thermostat S RH Humidity sensor S W SW Operation switch SA F1S Surge arrester SR WLU Signal receiver SS Selector switch SHEET METAL Terminal strip fixed plate T R Transformer TC TRC Transmitter V R V Varistor V R Diode bridge Insulated gate bipolar transistor IGBT power module WRC Wireless remote controller X Terminal X M Terminal strip block Y E Electronic expansion valve coil Y R ...

Page 14: ......

Page 15: ......

Page 16: ...3P664524 2A 2021 07 Copyright 2021 Daikin Verantwortung für Energie und Umwelt ...

Reviews: