4 Installation

Installation manual

8

RXF50+60B2_RXF71A2_RXP50~71L2_(A)RXM42~71N2_RXJ50N2_

RXA42+50B2

R32 split series

3P512025-5E – 2018.05

b

c

d

a

a

Drain port

b

Bottom frame

c

Drain plug

d

Hose (field supply)

To close the drain holes and attach the drain
socket

NOTICE

In cold areas, do NOT use a drain socket, hose and caps
(1,  2)  with  the  outdoor  unit.  Take  adequate  measures  so
that the evacuated condensate CANNOT freeze.

1

Install drain caps 1 and 2 (accessory). Make sure the edges of
the drain caps close off the holes completely.

a

b

a

Bottom frame

b

Drain cap

2

Install the drain socket.

a

c

b

b

b

a

a

a

Drain hole. Install a drain cap (2).

b

Drain hole. Install a drain cap (1).

c

Drain hole for drain socket

4.2

Connecting the refrigerant piping

DANGER: RISK OF BURNING

4.2.1

To connect the refrigerant piping to the
outdoor unit

Piping length.

 Keep field piping as short as possible.

Piping  protection.

  Protect  the  field  piping  against  physical

damage.

WARNING

Connect the refrigerant piping securely before running the
compressor. If the refrigerant piping is NOT connected and
the stop valve is open when the compressor is run, air will
be  sucked  in.  This  will  cause  abnormal  pressure  in  the
refrigeration cycle, which may result in equipment damage
and even injury.

CAUTION

▪ Use the flare nut fixed to the unit.

▪ To  prevent  gas  leakage,  apply  refrigeration  oil  only  to

the inside of the flare. Use refrigeration oil for R32.

▪ Do NOT reuse joints.

1

Connect the liquid refrigerant connection from the indoor unit to
the liquid stop valve of the outdoor unit.

a

b

c

a

Liquid stop valve

b

Gas stop valve

c

Service port

2

Connect  the  gas  refrigerant  connection  from  the  indoor  unit  to
the gas stop valve of the outdoor unit.

NOTICE

It  is  recommended  that  the  refrigerant  piping  between
indoor  and  outdoor  unit  is  installed  in  a  ducting  or  the
refrigerant piping is wrapped with finishing tape.

4.3

Checking the refrigerant piping

4.3.1

To check for leaks

NOTICE

Do NOT exceed the unit's maximum working pressure (see
"PS High" on the unit name plate).

NOTICE

Make  sure  to  use  a  recommended  bubble  test  solution
from  your  wholesaler.  Do  not  use  soap  water,  which  may
cause cracking of flare nuts (soap water may contain salt,
which  absorbs  moisture  that  will  freeze  when  the  piping
gets  cold),  and/or  lead  to  corrosion  of  flared  joints  (soap
water  may  contain  ammonia  which  causes  a  corrosive
effect between the brass flare nut and the copper flare).

1

Charge the system with nitrogen gas up to a gauge pressure of
at  least  200  kPa  (2  bar).  It  is  recommended  to  pressurize  to
3000 kPa (30 bar) in order to detect small leaks.

2

Check  for  leaks  by  applying  the  bubble  test  solution  to  all
connections.

3

Discharge all nitrogen gas.

4.3.2

To perform vacuum drying

DANGER: RISK OF EXPLOSION

Do NOT start the unit if it is vacuumed.

1

Vacuum the system until the pressure on the manifold indicates
−0.1 MPa (−1 bar).

2

Leave as is for 4-5 minutes and check the pressure:

If the pressure…

Then…

Does not change

There is no moisture in the
system. This procedure is
finished.

Increases

There is moisture in the
system. Go to the next step.

3

Vacuum the system for at least 2 hours to a manifold pressure
of −0.1 MPa (−1 bar).

4

After  turning  the  pump  OFF,  check  the  pressure  for  at  least
1 hour.

5

If  you  do  NOT  reach  the  target  vacuum  or  CANNOT  maintain
the vacuum for 1 hour, do the following:

▪ Check for leaks again.
▪ Perform vacuum drying again.

Summary of Contents for ARXM50N2V1B

Page 1: ...al R32 split series English Installation manual R32 split series RXF50B2V1B RXF60B2V1B RXF71A2V1B RXP50L2V1B RXP60L2V1B RXP71L2V1B ARXM50N2V1B RXM42N2V1B RXM50N2V1B RXM60N2V1B RXM71N2V1B RXJ50N2V1B RXA42B2V1B RXA50B2V1B ...

Page 2: ...in ne ovat muutettuina v platném znění Smjernice kako je izmijenjeno irányelv ek és módosításaik rendelkezéseit z późniejszymi poprawkami 18 19 20 21 22 23 24 25 Directivelor cu amendamentele respective Direktive z vsemi spremembami Direktiivid koos muudatustega Директиви с техните изменения Direktyvose su papildymais Direktīvās un to papildinājumos Smernice v platnom znení Değiştirilmiş halleriyl...

Page 3: ...n sallittu lämpötila TS TSmin Alhaisin matalapainepuolen lämpötila L C TSmax Suurinta sallittua painetta PS vastaava kyllästyslämpötila M C Kylmäaine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maximální přípustný tlak PS K bar Minimální maximální přípustná teplota TS TSmin Minimální teplota na nízkotlaké straně L C TSmax Saturovaná teplota odpovída...

Page 4: ...ellaisina kuin ne ovat muutettuina v platném znění Smjernice kako je izmijenjeno irányelv ek és módosításaik rendelkezéseit z późniejszymi poprawkami 18 19 20 21 22 23 24 25 Directivelor cu amendamentele respective Direktive z vsemi spremembami Direktiivid koos muudatustega Директиви с техните изменения Direktyvose su papildymais Direktīvās un to papildinājumos Smernice v platnom znení Değiştirilm...

Page 5: ...allittu lämpötila TS TSmin Alhaisin matalapainepuolen lämpötila L C TSmax Suurinta sallittua painetta PS vastaava kyllästyslämpötila M C Kylmäaine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maximální přípustný tlak PS K bar Minimální maximální přípustná teplota TS TSmin Minimální teplota na nízkotlaké straně L C TSmax Saturovaná teplota odpovídajíc...

Page 6: ... 1 Piping diagram Outdoor unit 14 1 About the documentation 1 1 About this document INFORMATION Make sure that the user has the printed documentation and ask him her to keep it for future reference Target audience Authorised installers Documentation set This document is part of a documentation set The complete set consists of General safety precautions Safety instructions that you MUST read before...

Page 7: ...e pipe length 3 m Maximum allowable height distance 20 m 4 Installation 4 1 Mounting the outdoor unit 4 1 1 To provide the installation structure Use a vibration proof rubber field supply in cases where vibrations may be transmitted to the building Prepare 4 sets of M8 or M10 anchor bolts nuts and washers field supply 20 mm 353 6 0 0 2 4 0 mm 2 4 0 300 In any case provide at least 300 mm of free s...

Page 8: ...vice port 2 Connect the gas refrigerant connection from the indoor unit to the gas stop valve of the outdoor unit NOTICE It is recommended that the refrigerant piping between indoor and outdoor unit is installed in a ducting or the refrigerant piping is wrapped with finishing tape 4 3 Checking the refrigerant piping 4 3 1 To check for leaks NOTICE Do NOT exceed the unit s maximum working pressure ...

Page 9: ... to the inside of the outdoor unit 4 4 2 About the refrigerant This product contains fluorinated greenhouse gases Do NOT vent gases into the atmosphere Refrigerant type R32 Global warming potential GWP value 675 WARNING FLAMMABLE MATERIAL The refrigerant inside this unit is mildly flammable WARNING The appliance shall be stored in a room without continuously operating ignition sources example open...

Page 10: ...aker with at least 3 mm between the contact point gaps that provide full disconnection under overvoltage category III WARNING If the supply cord is damaged it MUST be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid a hazard WARNING Do NOT connect the power supply to the indoor unit This could result in electrical shock or fire WARNING Do NOT use loca...

Page 11: ...y installed protection devices are installed according to this document and have NOT been bypassed The power supply voltage matches the voltage on the identification label of the unit There are NO loose connections or damaged electrical components in the switch box There are NO damaged components or squeezed pipes on the inside of the indoor and outdoor units There are NO refrigerant leaks The ref...

Page 12: ...s If the LED is ON again the outdoor unit PCB is faulty OFF 1 Supply voltage for power saving 2 Power supply fault 3 Turn the power OFF and back ON and check the LED within approximately 3 minutes If the LED is ON again the outdoor unit PCB is faulty DANGER RISK OF ELECTROCUTION When the unit is not operating the LEDs on the PCB are turned off in order to save power Even when the LEDs are off the ...

Page 13: ...R MR _A MR _B S U V W X A K R_ D V D DIODE DB DIODE BRIDGE DS DIP SWITCH E H HEATER F U FU FOR CHARACTERISTICS FUSE REFER TO PCB INSIDE YOUR UNIT FG CONNECTOR FRAME GROUND H HARNESS H P LED V L PILOT LAMP LIGHT EMITTING DIODE HAP LIGHT EMITTING DIODE SERVICE MONITOR GREEN HIGH VOLTAGE HIGH VOLTAGE IES INTELLIGENT EYE SENSOR IPM INTELLIGENT POWER MODULE K R KCR KFR KHuR K M MAGNETIC RELAY L LIVE L ...

Page 14: ...or temperature Thermistor Refrigerant flow Cooling Heating PED categories of equipment High pressure switch category IV Compressor category II Other equipment art 4 3 Applicable for RXP60L RXP71L RXF60B RXF71A M HPS High pressure switch Automatic reset Heat exchanger 7 0 CuT 7 0 CuT 7 0 CuT 7 0 CuT 7 0 CuT 7 0 CuT 12 7 CuT 12 7 CuT 12 7 CuT 12 7 CuT 12 7 CuT 12 7 CuT 9 5 CuT 6 4 CuT 9 5 CuT 6 4 Cu...

Page 15: ...set Automatic reset High pressure switch Muffler PED categories of equipment High pressure switch category IV Compressor category II Other equipment art 4 3 Applicable for RXM42N RXM50N RXM60N ARXM50N RXJ50N RXA42B RXA50B M HPS High pressure switch Automatic reset Heat exchanger 7 0 CuT 7 0 CuT 7 0 CuT 7 0 CuT 7 0 CuT 7 0 CuT 12 7 CuT 12 7 CuT 12 7 CuT 12 7 CuT 12 7 CuT 12 7 CuT 6 4 CuT 9 5 CuT 6 4...

Page 16: ...3P512025 5E 2018 05 Copyright 2018 Daikin ...

Reviews: