Pump Down Operation
In order to protect the environment, be sure to pump down when relocating or disposing of the unit.
1) Remove the valve cap from liquid stop valve and gas stop valve.
2) Carry out forced cooling operation.
3) After 3 to 4 minutes, close the liquid stop valve with a hexagonal wrench.
4) After 5 to 6 minutes, close the gas stop valve and stop forced cooling operation.
Forced cooling operation
Using the indoor unit ON/OFF switch
Press the indoor unit ON/OFF switch for at least 5 seconds. (The operation will start.)
• Forced cooling operation will stop automatically after around 15 minutes.
To stop the operation, press the indoor unit ON/OFF switch.
Using the indoor unit’s remote controller
1) Press “MODE” button and select the cooling mode.
2) Press “ON/OFF” button to turn on the system.
3) Press both the “TEMP” button and “MODE” button at the same time.
4) Press “MODE” button twice. (
will be displayed and the unit will enter forced cooling operation.)
• Forced cooling operation will stop automatically after around 30 minutes.
To stop the operation, press “ON/OFF” button.
CAUTION
• When pressing the switch, do not touch the terminal block. It has a high voltage, and touching it could cause electric shock.
• After closing the liquid stop valve, close the gas stop valve within 3 minutes, then stop the forced operation.
Liquid stop valve
Gas stop valve
Service port
Valve cap
Close
Hexagonal
wrench