background image

2 Specific installer safety instructions

Installation manual

5

ARXF20~42E5V1B
R32 split series
3P650253-12H – 2022.10

Installation site (see 

"4.1 Preparing the installation site"

 [

4

 7])

CAUTION

▪ Check  if  the  installation  location  can  support  the  unit's

weight. Poor installation is hazardous. It can also cause
vibrations or unusual operating noise.

▪ Provide sufficient service space.

▪ Do  NOT  install  the  unit  so  that  it  is  in  contact  with  a

ceiling or a wall, as this may cause vibrations.

WARNING

The  appliance  shall  be  stored  in  a  room  without
continuously  operating  ignition  sources  (example:  open
flames, an operating gas appliance or an operating electric
heater).

Connecting the refrigerant piping (see 

"5.2 Connecting the

refrigerant piping"

 [

4

 9])

CAUTION

▪ No  brazing  or  welding  on  site  for  units  with  R32

refrigerant charge during shipment.

▪ During installation of the refrigeration system, joining of

parts with at least one part charged shall be performed
taking  into  account  the  following  requirements:  inside
occupied  spaces  non-permanent  joints  are  NOT
allowed  for  R32  refrigerant  except  for  site  made  joints
directly connecting the indoor unit to piping. Site made
joints directly connecting piping to indoor units shall be
of non-permanent type.

NOTICE

▪ Use the flare nut fixed to the unit.

▪ To prevent gas leakage, apply refrigeration oil ONLY to

the  inside  of  the  flare.  Use  refrigeration  oil  for  R32
(FW68DA).

▪ Do NOT reuse joints.

NOTICE

▪ Do NOT use mineral oil on flared part.

▪ Do NOT reuse piping from previous installations.

▪ NEVER  install  a  drier  to  this  R32  unit  to  guarantee  its

lifetime. The drying material may dissolve and damage
the system.

WARNING

Connect the refrigerant piping securely before running the
compressor. If the refrigerant piping is NOT connected and
the stop valve is open when the compressor is run, air will
be  sucked  in.  This  will  cause  abnormal  pressure  in  the
refrigeration cycle, which may result in equipment damage
and even injury.

CAUTION

▪ Incomplete flaring may cause refrigerant gas leakage.

▪ Do  NOT  re-use  flares.  Use  new  flares  to  prevent

refrigerant gas leakage.

▪ Use  flare  nuts  that  are  included  with  the  unit.  Using

different flare nuts may cause refrigerant gas leakage.

CAUTION

Do  NOT  open  the  valves  before  flaring  is  complete.  This
would cause refrigerant gas leakage.

DANGER: RISK OF EXPLOSION

Do NOT open the stop valves before the vacuum drying is
finished.

Charging refrigerant (see 

"6 Charging refrigerant"

 [

4

 10])

WARNING

▪ The  refrigerant  inside  the  unit  is  mildly  flammable,  but

normally  does  NOT  leak.  If  the  refrigerant  leaks  in  the
room  and  comes  in  contact  with  fire  from  a  burner,  a
heater,  or  a  cooker,  this  may  result  in  fire,  or  the
formation of a harmful gas.

▪ Turn  OFF  any  combustible  heating  devices,  ventilate

the room, and contact the dealer where you purchased
the unit.

▪ Do  NOT  use  the  unit  until  a  service  person  confirms

that the part from which the refrigerant leaked has been
repaired.

WARNING

▪ Only  use  R32  as  refrigerant.  Other  substances  may

cause explosions and accidents.

▪ R32  contains  fluorinated  greenhouse  gases.  Its  global

warming  potential  (GWP)  value  is  675.  Do  NOT  vent
these gases into the atmosphere.

▪ When  charging  refrigerant,  ALWAYS  use  protective

gloves and safety glasses.

NOTICE

To  avoid  compressor  breakdown,  do  NOT  charge  more
than the specified amount of refrigerant.

WARNING

NEVER  directly  touch  any  accidental  leaking  refrigerant.
This could result in severe wounds caused by frostbite.

Electrical installation (see 

"7 Electrical installation"

 [

4

 11])

WARNING

The  appliance  MUST  be  installed  in  accordance  with
national wiring regulations.

WARNING

▪ All  wiring  MUST  be  performed  by  an  authorised

electrician  and  MUST  comply  with  the  applicable
national wiring regulation.

▪ Make electrical connections to the fixed wiring.

▪ All  components  procured  on-site  and  all  electrical

construction  MUST  comply  with  the  applicable
legislation.

Summary of Contents for ARXF20E5V1B

Page 1: ...Installation manual R32 split series English Installation manual R32 split series ARXF20E5V1B ARXF25E5V1B ARXF35E5V1B ARXF42E5V1B ...

Page 2: ...ва и или регламент и при условие че продуктите се използват в съответствие с нашите инструкции atitinka toliau nurodytas direktyvas arba reglamentus su sąlyga kad gaminiai bus eksploatuojami laikantis mūsų instrukcijų atbilst šādām direktīvām vai regulām ja vien šie izstrādājumi tiek lietoti saskaņā ar mūsu instrukcijām sú v zhode s nasledujúcou imi smernicou ami alebo predpisom mi za predpokladu ...

Page 3: ...are used in accordance with our instructions as amended S I 2016 1101 Electrical Equipment Safety Regulations 2016 S I 2016 1091 Electromagnetic Compatibility Regulations 2016 S I 2008 1597 Supply of Machinery Safety Regulations 2008 following the provisions of BS EN 60335 2 40 A B C TCF032E25 as set out in A and judged positively by B according to the Certificate C Daikin Europe N V is authorised...

Page 4: ...ical data 14 12 1 Wiring diagram 14 12 1 1 Unified wiring diagram legend 14 12 2 Piping diagram 16 12 2 1 Piping diagram Outdoor unit 16 1 About the documentation 1 1 About this document WARNING Make sure installation servicing maintenance repair and applied materials follow the instructions from Daikin including all documents listed in Documentation set and in addition comply with applicable legi...

Page 5: ...n This will cause abnormal pressure in the refrigeration cycle which may result in equipment damage and even injury CAUTION Incomplete flaring may cause refrigerant gas leakage Do NOT re use flares Use new flares to prevent refrigerant gas leakage Use flare nuts that are included with the unit Using different flare nuts may cause refrigerant gas leakage CAUTION Do NOT open the valves before flarin...

Page 6: ...al insulation as such pipes will be very hot DANGER RISK OF ELECTROCUTION All electrical parts including thermistors are powered by the power supply Do NOT touch them with bare hands DANGER RISK OF ELECTROCUTION Disconnect the power supply for more than 10 minutes and measure the voltage at the terminals of main circuit capacitors or electrical components before servicing The voltage MUST be less ...

Page 7: ...installation servicing maintenance and repair comply with instructions from Daikin and with applicable legislation and are executed ONLY by authorised persons 4 1 1 Installation site requirements of the outdoor unit Mind the following spacing guidelines 1200 150 150 50 300 300 mm mm a b b a a Air outlet b Air inlet It is recommended to install a baffle plate when the air outlet is exposed to wind ...

Page 8: ...d climate take adequate measures so that the evacuated condensate CANNOT freeze NOTICE If the drain holes of the outdoor unit are blocked up by a mounting base or floor surface place additional foot bases 30 mm under the outdoor unit s feet INFORMATION For information on the available options contact your dealer 1 Use a drain plug for drainage 2 Use a Ø16 mm hose field supply a c b d a Drain port ...

Page 9: ...ng Make sure the outdoor and indoor unit are mounted Typical workflow Connecting the refrigerant piping involves Connecting the refrigerant piping to the indoor unit Connecting the refrigerant piping to the outdoor unit Insulating the refrigerant piping Keeping in mind the guidelines for Pipe bending Flaring pipe ends Using the stop valves 5 2 2 Precautions when connecting the refrigerant piping D...

Page 10: ...charging additional refrigerant make sure the outdoor unit s external refrigerant piping is checked leak test vacuum drying INFORMATION Depending on the units and or the installation conditions it might be necessary to connect electrical wiring before you can charge refrigerant Typical workflow Charging additional refrigerant typically consists of the following stages 1 Determining if and how much...

Page 11: ...rying 1 Connect the refrigerant cylinder to the service port 2 Charge the additional refrigerant amount 3 Open the gas stop valve 6 6 To fix the fluorinated greenhouse gases label 1 Fill in the label as follows b Contains fluorinated greenhouse gases 2 1 1 1 2 2 kg tCO2 eq GWP kg 1000 kg kg GWP XXX RXXX a f c d e a If a multilingual fluorinated greenhouse gases label is delivered with the unit see...

Page 12: ...r 220 240 V Recommended field fuse 16 A Earth leakage circuit breaker MUST comply with applicable legislation 7 2 To connect the electrical wiring to the outdoor unit 1 Remove the service cover 2 Open the wire clamp 3 Connect the interconnection cable and power supply as follows f 50 Hz 220 240 V a b c d e a Interconnection cable b Power supply cable c Circuit breaker d Residual current device e P...

Page 13: ...run is finished set the temperature to a normal level In cooling mode 26 28 C in heating mode 20 24 C 3 The system stops operating 3 minutes after the unit is turned OFF INFORMATION Even if the unit is turned OFF it consumes electricity When the power turns back on after a power break the previously selected mode will be resumed 9 4 Starting up the outdoor unit See the indoor unit installation man...

Page 14: ...ctor D V D Diode DB Diode bridge DS DIP switch E H Heater FU F U for characteristics refer to PCB inside your unit Fuse FG Connector frame ground H Harness H P LED V L Pilot lamp light emitting diode Symbol Meaning HAP Light emitting diode service monitor green HIGH VOLTAGE High voltage IES Intelligent eye sensor IPM Intelligent power module K R KCR KFR KHuR K M Magnetic relay L Live L Coil L R Re...

Page 15: ...tallation manual 15 ARXF20 42E5V1B R32 split series 3P650253 12H 2022 10 Symbol Meaning X M Terminal strip block Y E Electronic expansion valve coil Y R Y S Reversing solenoid valve coil Z C Ferrite core ZF Z F Noise filter ...

Page 16: ...T 9 5CuT M 6 4CuT 6 4CuT 4 8CuT 6 4CuT 9 5CuT 9 5CuT 9 5CuT 9 5CuT 9 5CuT 7 9CuT Propeller fan 9 5CuT 9 5CuT 7 0CuT g2 g1 f f c a b d j l k g3 i e RXF20E RXF25E RXF35E ARXF20E ARXF25E ARXF35E h 7 0CuT 7 0CuT 9 5CuT M 4 8CuT 4 8CuT 6 4CuT 6 4CuT 4 8CuT 6 4CuT 9 5CuT 9 5CuT 9 5CuT 9 5CuT 9 5CuT 7 9CuT 9 5CuT 9 5CuT e f c a b g2 f h g1 d j l k g3 i RXF42E ARXF42E ...

Page 17: ......

Page 18: ......

Page 19: ......

Page 20: ...TANBUL TÜRKİYE Tel 0216 453 27 00 Faks 0216 671 06 00 Çağrı Merkezi 444 999 0 Web www daikin com tr Gülsuyu Mahallesi Fevzi Çakmak Caddesi Burçak Sokak No 20 34848 Maltepe 3P650253 12H 2022 10 Copyright 2022 Daikin Verantwortung für Energie und Umwelt ...

Reviews: