2
|
Components
Service manual
59
FTXF20~71A + FTXF20~25B + FTXF20~42C + ATXF20~71A + ATXF20~42C
+ RXF20~71A + RXF20~60B + RXF20~42C + ARXF20~71A + ARXF20~42C
Split Sensira R32
ESIE18-12E – 2021.02
3
Wrap a wet rag around the expansion valve body and solder the expansion
valve pipes to the refrigerant pipes.
CAUTION
Overheating the valve will damage or destroy it.
4
After soldering is done, stop the nitrogen supply after the component has
cooled‑down.
a
b
c
a
Putty
b
Expansion valve pipe
c
Expansion valve body
a
b
a
Expansion valve pipe
b
Expansion valve body
INFORMATION
The expansion valve and motor can have a different configuration / layout.
5
Reinstall the putty.
6
To install the expansion valve motor, see
56].
7
Add
refrigerant
to
the
refrigerant
circuit,
see
133].
About the installation of the expansion valve motor
NOTICE
Select the correct type.