10
|
Configuration
Installer reference guide
209
EPRA14~W1 + ETV23EA6V
Daikin Altherma 3 H HT F
4P644738-1 – 2021.02
In case power consumption control is ENABLED, the setting [4‑01] defines the
priority of the electrical heaters depending on applicable limitation.
BBR16
See
"6.6.4 BBR16 power limitation"
62] for detailed information about this
functionality.
INFORMATION
Restriction:
BBR16 settings are only visible when the language of the user interface is
set to Swedish.
NOTICE
2 weeks to change.
After you activated BBR16, you only have 2 weeks to change its
settings (
BBR16 activation
and
BBR16 power limit
). After 2 weeks, the unit
freezes these settings.
Note:
This is different from the permanent power limitation, which is always
changeable.
BBR16 activation
#
Code
Description
[9.9.F]
[7-07]
BBR16 activation
:
▪
0:
disabled
▪
1:
enabled
BBR16 power limit
#
Code
Description
[9.9.G]
[N/A]
BBR16 power limit
: This setting can only
be modified via the menu structure.
▪
0 kW~25 kW, step 0.1 kW
Energy metering
Energy metering
If energy metering is performed by the use of external power meters, configure the
settings as described below. Select the pulse frequency output of each power
meter in accordance with the power meter specifications. It is possible to connect
up to 2 power meters with different pulse frequencies. If only 1 or no power meter
is used, select '
None
' to indicate the corresponding pulse input is NOT used.
#
Code
Description
[9.A.1]
[D‑08]
Electricity meter 1
:
▪
0
None
: NOT installed
▪
1
1/10kWh
: Installed
▪
2
1/kWh
: Installed
▪
3
10/kWh
: Installed
▪
4
100/kWh
: Installed
▪
5
1000/kWh
: Installed