Specific installer safety instructions
Installer reference guide
17
EPRA14~W1 + ETV23EA6V
Daikin Altherma 3 H HT F
4P644738-1 – 2021.02
Opening and closing the units (see
"7.2 Opening and closing the units"
DANGER: RISK OF ELECTROCUTION
Do NOT leave the unit unattended when the service cover is removed.
DANGER: RISK OF ELECTROCUTION
DANGER: RISK OF BURNING/SCALDING
)
WARNING
Field piping method MUST be in accordance with the instructions from this manual.
See
83].
WARNING
The discharge pipes from the pressure relief valves MUST terminate in a safe and
visible position without forming any risk to persons in the vicinity.
WARNING
▪
Discharge piping, tundish, drain valves, etc. must be positioned away from any
electrical components.
▪
The discharge pipe away from the tundish must terminate in a safe, visible
position without forming any risk to persons in the vicinity.
WARNING
▪
Do not install any valves between the domestic hot water tank and relief valves/
expansion vessel.
▪
Do not install shut-off valves between the expansion relief valve and the domestic
hot water tank.
WARNING
Install the tundish away from any electrical device.
Possible consequence:
Electrical
shock or fire.
In case of freeze protection by glycol: