Fancoil address
Destination
Address 001
Leave free!
Address 002
Kitchen
Address 003
Living room
Address 004
Bedroom 1
...
...
Do not assign any fancoil to 001. This precaution will allow
any replacements and/or additions of network devices in
the future.
Troubleshooting
Problem
Cause
Solution
You cannot turn the unit on with the but-
ton
The button is disabled and the program-
ming has set the status to off
Check that flag 1 of the WEB register (247)
is not active
The CP input of the board is closed
If the E_SAVING (209) register is set to 0
when the CP contact presence closes, the
PCB goes into standby mode.
Check the input status.
You cannot turn off the appliance using
the
button or change function
All the keys are disabled
Check that Flag 6 of the WEB register (247)
is not active
It is not possible to increase or decrease
the temperature setting outside of set
values
The programming imposes a limit range
for adjusting the temperatures
Check that Flag 5 of the WEB register (247)
is not active and, if necessary, change the
values of the SPL_W (245) and SPH_W
(246) registers