background image

EK EK80ABV1

Daikin Altherma indoor unit

4P404418-1 – 2015.04

Operation manual

10

4.7.

Other operation modes

Start up operation (

)

During start up, the 

 icon displays, indicating that the heat

pump is starting up and is not working in a steady state condition.

Defrost operation (

)

In space heating operation or domestic water heating operation,
freezing of the outdoor heat exchanger may occur due to low outdoor
temperature. If this risk occurs, the system goes into defrost
operation. During defrost operation, space heating or domestic hot
water operation is not possible.

Quiet mode operation (

)

Quiet mode operation means that the indoor unit works at reduced
compressor speed so that the noise produced by the indoor unit
drops. This implies that it will take longer till the required temperature
set point is reached. Beware of this when a certain level of heating is
required indoors.

Selecting quiet mode operation

1

Use the 

 button to activate quiet mode operation.

The 

 icon displays.

If the controller is set to permission level 2 or 3 (refer to "Field
settings" in the installation manual), the 

 button is not

operable.

2

Press the 

 button again to deactivate quiet mode operation.

The 

 icon disappears.

There are 3 different levels of quiet mode operation. The desired
quiet mode is set through a field setting. Refer to 

"4.15. Field

settings" on page 19

 for a detailed description how to set one or more

field settings.

[8-03] Status: defines the level of low noise operation (quiet
mode).

4.8.

Simultaneous demand of space heating and 
domestic water heating

The unit can not perform domestic water heating and space heating
at the same time. If both modes are requested at the same time, the
unit will heat up till the reheat maximum temperature in 1 time. During
this period, space heating is not possible.

If you are using the remote controller room temperature control:
When the reheat temperature is reached, the further heat up of
the domestic hot water tank will be decided by the remote
controller room thermostat in order to prevent the room
temperature to drop too much.

If you are using the external room thermostat:
When the reheat temperature is reached, the further heat up of
the domestic hot water tank will be decided by the external room
thermostat thermo conditions and running timers which are
programmed by your installer.

If you are using the remote controller leaving water temperature
control:
When the reheat temperature is reached, the further heating up
of the domestic hot water tank will be decided by the running
timers which are programmed by your installer.

4.9.

Simultaneous demand of space cooling and 
domestic water heating

The unit can perform simultaneous operation of cooling and domestic
water heating.

During cooling operation, the energy taken from the cooled water will
be transferred into energy to heat up the domestic water. It is a
recovery function and is controlled automatically by the system.

This heat recovery is only possible if heat recovery operation is
permitted (it is an installation related setting).

4.10. Temperature read-out mode

On the remote controller, the actual temperatures can be displayed.

1

Push and hold the 

 button for 5 seconds.

The heating/cooling leaving water temperature is displayed
(icons 

 and 

 and   are blinking).

2

Use the 

 and 

 buttons to display:

The entering water temperature (icons 

 and 

 are

blinking and the   icon is flashing slowly).

The indoor temperature (icons 

 and 

 are blinking).

The outdoor temperature (icons 

 and 

 are blinking).

The hot water supply tank temperature (icons 

 and 

 are

blinking).

3

Push the 

 button again to leave this mode. If no button is

pressed, the remote controller leaves the display mode after 10
seconds.

A

Storage temperature

B

Reheat maximum temperature

t

Time

T

Domestic hot water storage temperature

T

A

B

t

Summary of Contents for Altherma EKHVMRD50ABV1

Page 1: ...OPERATION MANUAL EKHVMRD50ABV1 EKHVMRD80ABV1 EKHVMYD50ABV1 EKHVMYD80ABV1 Daikin Altherma indoor unit ...

Page 2: ...wledge unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety Children shall be supervised to ensure that they do not play with the appliance 1 DEFINITIONS Installation manual Instruction manual specified for a certain product or application explaining how to install configure and maintain it Danger Indicates an imminently ha...

Page 3: ...g The more detailed information of how the unit must be operated is explained in the chapter 4 Operation of the unit on page 3 The quick start up offers the user the possibility to start up the system before reading the entire manual Space heating operation NOTE An EKHVMRD and EKHVMYD indoor unit can only be connected to an EMRQ outdoor unit The installation of the indoor unit s is described in th...

Page 4: ...eating only if domestic hot water tank option is installed Automatic storage daily water heat up once during night and or once during day Turn on field setting 1 00 and or 1 02 and then push the button See Automatic storage on page 8 The icon will display Hot water will be produced at next scheduled action When water heat up starts the icon will be blinking 1 second interval Manual storage one tim...

Page 5: ...r to Field settings in the installation manual the weather dependent set point button will not be operable 26 INSPECTION TEST OPERATION BUTTON This button is used for installation purposes and changing field settings Refer to 4 15 Field settings on page 19 27 PROGRAMMING BUTTON This multi purpose button is used to program the controller The function of the button depends on the actual status of th...

Page 6: ...aving water temperature which you want to be used to heat up your system for detailed information see Leaving water temperature control on page 6 Automatic setback function Setback function provides the possibility to lower the room temperature The setback function can for instance be activated during the night because the temperature demands during night and day are not the same The setback funct...

Page 7: ...al room thermostat 1 Press the button 1 time to select weather dependent set point operation or 2 times when the remote controller room thermostat function is used Icon appears on the display as well as the shift value The shift value is not shown in case it is 0 2 Use the and buttons to set the shift value Range for the shift value 5 C to 5 C Icon will be displayed as long as the weather dependen...

Page 8: ...edule timer function 3 Use the and buttons to select the leaving water temperature which you want to be used to cool down your system for detailed information see Leaving water temperature control on page 6 Leaving water temperature control In this mode cooling will be activated as required by the water temperature set point The set point can be set manually or through the schedule timer Selecting...

Page 9: ...Therefore it is recommended to use this function b 04 Automatic maximum domestic hot water storage temperature default 70 C NOTE Any domestic water heating operation is impossible when the domestic hot water tank is not installed A Storage operation if activated B Reheat operation if activated C Disinfection operation if activated Field settings D Disinfection operation temperature 5 00 e g 70 C E...

Page 10: ...estic water heating modes on page 8 Disinfection operation This mode will disinfect the domestic hot water tank by periodically heating the domestic water to a specific temperature During the operation of this mode the icon will be blinking rapidly with 0 5 second intervals The disinfection temperature set point is a field setting as are the retention time day and hour Refer to 4 15 Field settings...

Page 11: ...t possible If you are using the remote controller room temperature control When the reheat temperature is reached the further heat up of the domestic hot water tank will be decided by the remote controller room thermostat in order to prevent the room temperature to drop too much If you are using the external room thermostat When the reheat temperature is reached the further heat up of the domestic...

Page 12: ...stays enabled When pushing the button The schedule timer for space heating and domestic water heating along with the quiet mode will be stopped and will not start again The schedule timer icon will not be displayed anymore 1 Schedule timer 2 Setback function 3 When both setback function and schedule timer are enabled A Setback function t Time T Temperature set point Room temperature Leaving water ...

Page 13: ...n can be used Reheat the reheat function can be activated next to or separate from the automatic storage operation if the user wants to keep the domestic hot water tank at the minimum reheat temperature Next to the standard domestic water heating operation modes it is also possible to freely program the domestic water heating operation through the schedule timer refer to Programming domestic water...

Page 14: ...programmed for the same day and at the same time only the action with the highest action number will be executed Example You can always alter add or remove the programmed actions later NOTE If the auto restart function is disabled the schedule timer will not be activated when power returns to the unit after a power supply failure Press the button to enable the schedule timer again When power retur...

Page 15: ...ature 10 Use the and buttons to set the room temperature 11 Use the button to select to switch heating and the remote controller off to select automatic temperature calculation for leaving water temperature Use the and buttons to set the appropriate shift value refer to 4 3 Space heating operation on page 5 for more information about weather dependent set point 12 Repeat steps 7 to 11 to program t...

Page 16: ...ime 8 Use the and buttons to set the leaving water temperature 9 Use the and buttons to set the room temperature 10 Use the button to select to switch cooling and the remote controller off 11 Repeat steps 6 to 10 to program the other actions When all actions have been programmed make sure that the display shows the highest action number you would like to save 12 Press the button for 5 seconds to s...

Page 17: ...ppears 7 Use the button to select the action number you would like to program or to modify 8 Use the and buttons to set the correct action time 9 Use the button to select or deselect as action 10 Repeat steps 7 to 9 to program the other actions of the selected mode When all actions have been programmed make sure that the display shows the highest action number you would like to save 11 Press the b...

Page 18: ... program or to modify 7 Use the and buttons to set the correct action time 8 Use the button to select or deselect as action 9 Repeat steps 6 to 8 to program the other actions of the selected mode When all actions have been programmed make sure that the display shows the highest action number you would like to save 10 Press the button for 5 seconds to store the programmed actions If the button is p...

Page 19: ...copied You can return to step 2 by pressing the button Deleting one or more programmed actions Deleting one or more programmed actions is done at the same time as storing the programmed actions When all actions for one day have been programmed make sure that the display shows the highest action number you would like to save By pressing the button for 5 seconds you store all actions except those wi...

Page 20: ...on 3 will be displayed The current selected field setting code is indicated 2 with the set value displayed to the right 1 2 Press the button to select the appropriate field setting first code 3 Press the button to select the appropriate field setting second code 4 Press the button and button to change the set value of the select field setting 5 Save the new value by pressing the button 6 Repeat st...

Page 21: ...eather dependent set point 00 Low ambient temperature Lo_A 10 20 5 1 C 01 High ambient temperature Hi_A 15 10 20 1 C 02 Set point at low ambient temperature Lo_Ti 70 25 80 1 C 03 Set point at high ambient temperature Hi_Ti 45 25 80 1 C 4 Disinfection function 00 Status disinfection operation 1 ON 0 1 01 Disinfection operation day selection Fri Mon Sun 02 Disinfection operation start time 23 00 0 0...

Page 22: ...ture limits 00 Installation related setting a 80 37 80 1 C 01 Installation related setting a 25 25 37 1 C 02 Installation related setting a 20 18 22 1 C 03 Installation related setting a 5 5 18 1 C 04 Not applicable Do not change the default value 0 d Domestic water heating retention times 00 Installation related setting a 10 5 20 1 01 Installation related setting a 30 10 60 5 02 Installation rela...

Page 23: ...o not try to dismantle the system yourself the dismantling of the system treatment of the refrigerant of oil and other parts must be done by a qualified installer in accordance with the applicable legislation Units must be treated at a specialized treatment facility for re use recycling and recovery By ensuring this product is disposed off correctly you will help to prevent potential negative cons...

Page 24: ...NOTES ...

Page 25: ...NOTES ...

Page 26: ...NOTES ...

Page 27: ......

Page 28: ...4P404418 1 2015 04 Copyright 2015 Daikin ...

Reviews: