10 Configuration
Installer reference guide
57
EJHA NHY32AA
Daikin Altherma H Hybrid
4P556861-1A – 2019.05
6
Push
to confirm the modification of the parameter.
7
At installer settings menu, press
to confirm the settings.
Installer settings
The system will restart.
Confirm
Adjust
Cancel
OK
Result:
The system will restart.
Quick wizard: Set the system layout after first
power ON
After first power ON of the system, you are guided on the user
interface to do initial settings:
▪ language,
▪ date,
▪ time,
▪ system layout.
By confirming the system layout, you can proceed with the
installation and commissioning of the system.
1
At power ON, the quick wizard starts as long as the system
layout was NOT confirmed yet, by setting the language.
Language
Select the desired language
Confirm
Adjust
2
Set the current date and time.
1
2013
Jan
Tue
Confirm
Adjust
Scroll
Date
What is the date today?
00
: 00
What is the current time?
Time
Confirm
Adjust
Scroll
3
Set the system layout settings:
Standard
,
Options
. For more
"10.1.2 Basic configuration" on page 57
.
A.2
1
Scroll
Select
System layout
Standard
Options
Confirm layout
4
After configuration, select
Confirm layout
and press
.
Confirm layout
Please confirm the system
layout. The system will
restart and will be ready for
first startup.
OK
Cancel
Confirm
Adjust
5
The user interface re-initialises and you can proceed the
installation by setting the other applicable settings and
commissioning of the system.
When the installer settings are changed, the system will request to
confirm. When confirmation is complete, the screen will shortly turn
OFF and "busy" will be displayed for several seconds.
10.1.2
Basic configuration
Quick wizard: Language / time and date
#
Code
Description
[A.1]
N/A
Language
[1]
N/A
Time and date
Quick wizard: Standard
Space heating settings
The system can heat up a space. Depending on the type of
application, the space heating settings must be made accordingly.
#
Code
Description
[A.2.1.7]
[C-07]
Unit temperature control:
▪ 0 (
LWT control
): Unit operation is
decided based on the leaving water
temperature regardless the actual
room temperature and/or heating
demand of the room.
▪ 1 (
Ext RT control
): Unit operation is
decided by the external thermostat or
equivalent (e.g. heat pump convector).
This is only applicable in case of
NHY32AA gas boiler.
▪ 2 (
RT control
): Unit operation is
decided
based
on
the
ambient
temperature of the user interface.