3 Operation

Operation manual

6

08S18+23DA

Daikin Altherma – Low temperature split

4P495247-1B – 2017.12

t

60°C

00:00

07:00

50°C

15°C

40°C

14:00

21:00

1

2

3

4

5

Tt

T

t

DHW tank temperature

t

Time

3.4.3

Sch reheat mode

In  scheduled  +  reheat  mode,  the  domestic  hot  water  control  is  the
same  as  in  scheduled  mode.  However,  when  the  DHW  tank
temperature drops below a preset value (=reheat tank temperature –
hysteresis  value;  example:  35°C),  the  DHW  tank  heats  up  until  it
reaches  the  reheat  set  point  (example:  45°C).  This  ensures  that  a
minimum amount of hot water is available at all times.

Example: 

t

Tt

60°C

00:00

07:00

50°C

45°C

15°C

14:00

21:00

35°C

1

2

4

5

3

T

t

DHW tank temperature

t

Time

3.4.4

Using DHW powerful operation

About powerful operation

Powerful  operation  allows  the  domestic  hot  water  to  be  heated  by
the  backup  heater.  Use  this  mode  on  days  when  there  is  more  hot
water usage than usual.

To check if powerful operation is active

If 

 is displayed on the home screen, powerful operation is active.

Activate or deactivate Powerful operation as follows:

1

Go to [5.1]: Tank > Powerful operation

2

Turn powerful operation Off or On.

Usage example: You immediately need more hot water

You are in the following situation:

▪ You already consumed most of your domestic hot water.

▪ You  cannot  wait  for  the  next  scheduled  action  to  heat  up  the

domestic hot water tank.

Then  you  can  activate  powerful  operation.  The  domestic  hot  water
tank will start heating up the water to the Comfort temperature.

INFORMATION

When  powerful  operation  is  active,  the  risk  of  space
heating  and  capacity  shortage  comfort  problems  is
significant.  In  case  of  frequent  domestic  hot  water
operation,  frequent  and  long  space  heating  interruptions
will happen.

3.5

Advanced usage

The  amount  of  information  you  can  read  out  in  the  menu  structure
depends on your user permission level:

▪ User: Standard mode

▪ Advanced user: You can read out more information

3.5.1

To change the user permission level

You can change the user permission level as follows:

1

Go to [B]: User profile.

2

Enter the applicable code for the user permission.

▪ Move the cursor from left to right.

▪ Browse  through  the  list  of  digits  and  change  the

selected digit.

▪ Confirm the pincode and proceed.

User pin code

The User pin code is 

0000

.

Advanced user pin code

The Advanced user pin code is 

1234

. Additional menu items for the

user are now visible.

3.6

Schedule screen: Example

This  example  shows  how  to  set  a  room  temperature  schedule  in
heating mode for the main zone.

INFORMATION

The procedures to program other schedules are similar.

To program the schedule

Example: 

You want to program the following schedule:

Mon

Sat

Wed

Fri

Thu

Tue

Sun

User defined 1

Prerequisite: 

The  room  temperature  schedule  is  only  available  if

room  thermostat  control  is  active.  If  leaving  water  temperature
control is active, you can program the main zone schedule instead.

1

Go to the schedule.

2

Clear the contents of the schedule (optional).

3

Program the schedule for Monday.

4

Copy the schedule to the other weekdays.

5

Program the schedule for Saturday and copy it to Sunday.

6

Give the schedule a name.

To go to the schedule:

1

Go to [1.1]: Room > Schedule.

2

Set scheduling to Yes.

3

Go to [1.2]: Room > Heating schedule.

Summary of Contents for Altherma EHVZ-D6VG

Page 1: ...Operation manual Daikin Altherma Low temperature split English Operation manual Daikin Altherma Low temperature split EHVZ04S18DA6V G EHVZ08S18DA6V G EHVZ08S23DA6V G EHVZ08S18DA9W G EHVZ08S23DA9W G ...

Page 2: ... to inform you about the settings that he used to configure your system Check if he has filled in the installer settings tables If not request him to do so Keep the documentation for future reference Target audience End users Documentation set This document is part of a documentation set The complete set consists of General safety precautions Safety instructions that you must read before operating...

Page 3: ...the screen darkens Pressing any button or rotating any dial awakens the display The time of non interaction differs depending on the user permission level User or Advanced user 15 min Installer 1 h Dials and buttons You use the dials and buttons To navigate through the screens menus and settings of the LCD screen To set values a b c d e Item Description a Left dial The LCD shows an arc on the left...

Page 4: ...cription Additional zone h3 h1 h2 h1 Heat emitter type Underfloor heating Fancoil unit Radiator h2 Leaving water temperature setpoint h3 Room thermostat type External control Hidden Leaving water temperature control Domestic hot water i1 i2 i1 Domestic hot water i2 Measured tank temperature Malfunction j or A malfunction occurred See 6 1 To display the help text in case of a malfunction on page 11...

Page 5: ...g Possible actions on this screen Confirm changes and proceed 3 3 Space heating control 3 3 1 Setting the space operation mode About space operation modes This unit is a heating only model The system can heat up a space but NOT cool down a space 3 3 2 To change the desired room temperature During room temperature control you can use the room temperature setpoint screen to read out and adjust the d...

Page 6: ...When powerful operation is active the risk of space heating and capacity shortage comfort problems is significant In case of frequent domestic hot water operation frequent and long space heating interruptions will happen 3 5 Advanced usage The amount of information you can read out in the menu structure depends on your user permission level User Standard mode Advanced user You can read out more in...

Page 7: ...copy the schedule to the other weekdays 1 Select Monday Mon Sat Wed Fri Thu Tue Sun User defined 1 2 Select Copy Edit Copy Result C is displayed next to the copied day 3 Select Tuesday Mon Sat Wed Fri Thu Tue Sun User defined 1 C 4 Select Paste Copy Paste C Result Mon Sat Wed Fri Thu Tue Sun User defined 1 C 5 Repeat this action for all other weekdays Mon Sat Wed Fri Thu Tue Sun User defined 1 C T...

Page 8: ...ma Low temperature split 4P495247 1B 2017 12 1 Select the name of the current schedule Mon Sat Wed Fri Thu Tue Sun User defined 1 2 Select the Rename option Delete Rename 3 Browse through the character list and confirm the selected character 4 Confirm the new name ...

Page 9: ...rice C Operation Room Space heating cooling Tank B User profile 7 3 Holiday Activation From Till 7 4 Quiet Activation Schedule 7 5 Electricity price High Medium Low Schedule 7 2 Time date Hours Minutes Year Month Day Daylight savings time Format 1 4 Antifrost Activation Room setpoint 1 5 Setpoint range Heating minimum Heating maximum 1 Room Schedule Heating schedule Antifrost Setpoint range Room s...

Page 10: ...ods You can use the holiday mode Tips about DHW tank temperature Use a weekly schedule for your normal domestic hot water needs only in scheduled mode Program to heat up the DHW tank to a preset value Storage comfort higher DHW tank temperature during the night because then space heating demand is lower If heating up the DHW tank once at night is not sufficient program to additionally heat up the ...

Page 11: ...r temperature in accordance with the heat emitter type 6 3 Symptom The water at the tap is too cold Possible cause Corrective action You ran out of domestic hot water because of unusual high consumption If you immediately need domestic hot water activate the DHW tank Powerful operation However this consumes extra energy If you can wait overrule increase the active or next scheduled desired tempera...