background image

4 Installation

Installation manual

8

EBLQ+07CAV3

Daikin Altherma low temperature monobloc

4P403578-1F – 2018.06

4.3

Connecting the water piping

4.3.1

To connect the water piping

NOTICE

Do  NOT  use  excessive  force  when  connecting  the  piping.
Deformation of the piping can cause malfunctioning of the
unit.  Make  sure  that  the  tightening  torque  does  NOT
exceed 30 N•m.

To facilitate service and maintenance, 2 shut-off valves are provided.
Mount the valves on the space heating water inlet and space heating
water outlet. Mind their position: the integrated drain valves will only
drain the side of the circuit on which they are located. To be able to
only  drain  the  unit,  make  sure  the  drain  valves  are  positioned
between the shut‑off valves and the unit.

a

b

a

Water inlet

b

Water outlet

1

Screw the outdoor unit nuts on the shut-off valves.

2

Connect the field piping on the shut-off valves.

3

In case of connection with the optional domestic hot water tank,
see the installation manual of the domestic hot water tank.

NOTICE

Install a manometer in the system.

NOTICE

Install air purge valves at all local high points.

NOTICE

In case an optional domestic hot water tank is installed: A
pressure  relief  valve  (field  supply)  with  an  opening
pressure  of  maximum  10  bar  must  be  installed  on  the
domestic  cold  water  inlet  connection  in  accordance  with
the applicable legislation.

4.3.2

To protect the water circuit against
freezing

Frost can damage the system. To prevent the hydraulic components
from  freezing,  the  software  is  equipped  with  special  frost  protection
functions, that include the activation of pump, internal heaters, and/
or backup heater operation in case of low temperatures.

However,  in  case  of  a  power  failure,  these  functions  cannot
guarantee  protection.  It  is  therefore  recommended  to  add  glycol  to
the water circuit. The required concentration depends on the lowest
expected  outdoor  temperature,  and  on  whether  you  want  to  protect
the  system  from  bursting  or  from  freezing.  To  prevent  the  system
from  freezing,  more  glycol  is  required.  Add  glycol  according  to  the
table below.

INFORMATION

▪ Protection  against  bursting:  the  glycol  will  prevent  the

piping  from  bursting,  but  NOT  the  liquid  inside  the
piping from freezing.

▪ Protection  against  freezing:  the  glycol  will  prevent  the

liquid inside the piping from freezing.

Lowest expected
outdoor
temperature

Prevent from
bursting

Prevent from
freezing

–5°C

10%

15%

–10°C

15%

25%

–15°C

20%

35%

–20°C

25%

–25°C

30%

NOTICE

▪ The  required  concentration  might  differ  depending  on

the type of glycol. ALWAYS compare the requirements
from the table above with the specifications provided by
the  glycol  manufacturer.  If  necessary,  meet  the
requirements set by the glycol manufacturer.

▪ The  added  concentration  of  glycol  should  NEVER

exceed 35%.

▪ If the liquid in the system is frozen, the pump will NOT

be  able  to  start.  Mind  that  if  you  only  prevent  the
system from bursting, the liquid inside might still freeze.

▪ In  case  of  a  power  supply  failure  or  pump  failure,  and

NO glycol was added to the system, drain the system.

▪ When  water  is  at  standstill  inside  the  system,  the

system is very likely to freeze and get damaged.

The types of glycol that can be used depend on whether the system
contains a domestic hot water tank:

If…

Then…

The system contains a domestic
hot water tank

Only use propylene glycol

(a)

The system does NOT contain a
domestic hot water tank

You can use either propylene
glycol

(a)

 or ethylene glycol

(a)

Propylene glycol, including the necessary inhibitors,
classified as Category III according to EN1717.

WARNING

Ethylene glycol is toxic.

Summary of Contents for Altherma EBLQ05CAV3

Page 1: ...Installation manual Daikin Altherma low temperature monobloc English Installation manual Daikin Altherma low temperature monobloc EBLQ05CAV3 EBLQ07CAV3 EDLQ05CAV3 EDLQ07CAV3 ...

Page 2: ...du že jsou využívány v souladu s našimi pokyny odpovídají následujícím normám nebo normativním dokumentům u skladu sa slijedećim standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s našim uputama 16 17 18 19 20 21 22 23 24 25 megfelelnek az alábbi szabvány ok nak vagy egyéb irányadó dokumentum ok nak ha azokat előírás szerint használják spełniają wymogi następ...

Page 3: ...st during commissioning 18 6 2 1 To perform an air purge 18 6 2 2 To perform a test run 19 6 2 3 To perform an actuator test run 19 6 2 4 To perform an underfloor heating screed dryout 19 7 Hand over to the user 20 7 1 About locking and unlocking 20 To activate or deactivate a function lock 20 To activate or deactivate button lock 20 8 Technical data 21 8 1 Piping diagram Outdoor unit 21 8 2 Wirin...

Page 4: ...4726 The diffusion of oxygen into the piping can lead to excessive corrosion 3 2 1 To check the water volume and flow rate Minimum water volume If Then The system contains a backup heater The minimum water volume is 10 l a The system does NOT contain a backup heater The minimum water volume is 20 l a a The internal water volume of the outdoor unit NOT included NOTICE When circulation in each space...

Page 5: ...ingle user interface and dual user interface connection c Minimum cable section 0 75 mm d Cable section 0 75 mm till 1 25 mm maximum length 20 m e If valve kit EKMBHBP1 is part of the system then the required cable section is 0 75 mm If valve kit EKMBHBP1 is NOT part of the system then the minimum required cable section is 0 75 mm NOTICE More technical specifications of the different connections a...

Page 6: ...he unit Additionally make sure the unit is positioned at least 100 mm above the maximum expected level of snow mm 1 5 0 1 5 0 a 330 300 283 7 4 0 0 mm 100 a Maximum snowfall height It is possible to install the unit on brackets to the wall 250 400 300 250 400 mm a a Maximum snowfall height 4 2 2 To install the outdoor unit CAUTION Do NOT remove the protective cardboard before the unit is installed...

Page 7: ...viding drainage therefore make sure to cover the entire unit NOTICE If the unit is installed in a cold climate take adequate measures so that the evacuated condensate CANNOT freeze INFORMATION For information on the available options contact your dealer NOTICE Provide at least 300 mm of free space below the unit Additionally make sure the unit is positioned at least 100 mm above the expected level...

Page 8: ...owever in case of a power failure these functions cannot guarantee protection It is therefore recommended to add glycol to the water circuit The required concentration depends on the lowest expected outdoor temperature and on whether you want to protect the system from bursting or from freezing To prevent the system from freezing more glycol is required Add glycol according to the table below INFO...

Page 9: ...m For more information refer to the chapter To check the water volume and flow rate in the installer reference guide 4 3 3 To fill the water circuit 1 Connect the water supply hose to the drain and fill valve 2 Open the drain and fill valve 3 If an automatic air purge valve was installed make sure it is open 4 Fill the circuit with water until the manometer field supply indicates a pressure of 2 0...

Page 10: ...2 3 X4M 2 3 1 1 GND 2 L 3 N 4 4 3 To connect the user interface INFORMATION If control box EKCB07CAV3 is NOT part of the system connect the user interface directly to the outdoor unit If control box EKCB07CAV3 is part of the system you can also connect the user interface to the control box To do this connect the user interface to control box terminals X2M 20 21 and then connect the control box to ...

Page 11: ...ntrol box To do this connect outdoor unit terminals X3M 1 2 to control box terminals X8M 6 7 and then connect the shut off valve to control box terminals X8M 6 7 X2M X8M 6 7 X5M X3M M2S 1 2 4 4 5 To connect the domestic hot water pump 1 Connect outdoor unit terminals X3M 3 4 to the bottom side of terminals X8M 8 9 of control box EKCB07CAV3 2 Connect the cable of the domestic hot water pump to the ...

Page 12: ...or more than 1 hour or press again for more than 4 seconds the installer permission level switches back to End user To set the user permission level to Advanced end user 1 Go to the main menu or any of its submenus 2 Press for more than 4 seconds Result The user permission level switches to Adv end user Additional information is displayed and is added to the menu title The user permission level wi...

Page 13: ... See also illustrations below Domestic hot water pump installed for Instant hot water Disinfection c f a g h b c h b a d f e g a Outdoor unit b Tank c Domestic hot water pump d Heater element e Non return valve f Shower g Cold water h Control box Remote outdoor sensor Code Description A 2 2 B C 08 External sensor outdoor 0 No NOT installed 1 Outdoor sensor Remote outdoor sensor connected to the ou...

Page 14: ...lso table below Alarm output logic A 2 2 F 3 D 08 Optional external kWh meter 1 0 No NOT installed 1 Installed 0 1 pulse kWh 2 Installed 1 pulse kWh 3 Installed 10 pulse kWh 4 Installed 100 pulse kWh 5 Installed 1000 pulse kWh A 2 2 F 4 D 09 Optional external kWh meter 2 0 No NOT installed 1 Installed 0 1 pulse kWh 2 Installed 1 pulse kWh 3 Installed 10 pulse kWh 4 Installed 100 pulse kWh 5 Instal...

Page 15: ...perature difference between entering and leaving water In case a minimum temperature difference is required for the good operation of the heat emitters in cooling mode Leaving water temperature Modulation Code Description A 3 1 1 5 8 05 Leaving water temperature modulation 0 No Disabled 1 Yes Enabled The leaving water temperature is calculated according to the difference between desired and actual...

Page 16: ...water Type 0 Reheat only Only reheat operation is allowed 1 Reheat sched Same as 2 but between the scheduled heatup cycles reheat operation is allowed 2 Scheduled only The domestic hot water tank can ONLY be heated according to a schedule Code Description A 4 5 6 0E The maximum temperature that users can select for the domestic hot water You can use this setting to limit the temperature at the hot...

Page 17: ...eration mode Power saving possible User interface location Options DHW pump External sensor Control box Option box Leaving water Main Additional Delta T source Room thermostat Room temp range Room temp offset Ext room sensor offset Operation range Space heating OFF temp Space cooling On temp Disinfection Disinfection Operation day Start time Temperature target Duration Backup heater Operation mode...

Page 18: ...box of the control box is turned ON The correct pipe size is installed and the pipes are properly insulated There are no water leaks inside the outdoor unit The shut off valves are properly installed and fully open The pressure relief valve purges water when opened The minimum water volume is guaranteed in all conditions See To check the water volume in 3 2 Preparing water piping on page 4 If glyc...

Page 19: ...ving water temperature home page room temperature home page and domestic hot water home page are turned OFF 1 Set the user permission level to Installer See To set the user permission level to Installer on page 12 2 Make sure the room temperature control the leaving water temperature control and the domestic hot water control are turned OFF via the user interface 3 Go to A 7 4 Installer settings C...

Page 20: ... the maintenance of the unit Explain the user about energy saving tips as described in the operation manual 7 1 About locking and unlocking If required it is possible to lock the buttons of the main user interface making it impossible for the user to operate it For the user to be able to change setpoint temperatures the simplified user interface or an external room thermostat is then required You ...

Page 21: ...9 CuT 1 4 3 2 t 12 7 CuT 12 7 CuT R4T 9 5 CuT 6 4 CuT 6 4 CuT M 6 4 CuT 6 4 CuT Discharge pipe thermistor Accumulator Compressor High pressure switch Muffler Muffler 4 way valve Pressure sensor Refrigerant flow Cooling Heating Liquid stop valveV Plate heat exchanger Gas stop valve with service port Air purge Flow sensor Pump Flow switch Outlet Shut off valve with drain fill valve Expansion vessel ...

Page 22: ...onnector X1M X2M Terminal strip Y1E Electronic expansion valve coil Y1R Reversing solenoid valve coil Z1C Z4C Ferrite core Field wiring Terminal strip Connector Terminal Protective earth BLK Black BLU Blue BRN Brown GRN Green ORG Orange PPL Purple RED Red WHT White YLW Yellow Outdoor unit hydro module English Translation 1 Connection diagram 1 Connection diagram Compressor switch box Compressor sw...

Page 23: ...rmostat PC power circuit A3P Heat pump convector A4P Extension PCB control optional A5P User interface PCB A7P Receiver PCB wireless On OFF thermostat F2B Overcurrent fuse booster heater K3M Contactor booster heater M2P Domestic hot water pump M2S Shut off valve English Translation M3S 3 way valve for domestic hot water M4S Valve kit Q DI Earth leakage circuit breaker Q2L Q3L Thermal protector boo...

Page 24: ...tection voltage supplied by PCB Power limitation digital inputs 5 V DC detection voltage supplied by PCB Space C H On OFF output Space cooling heating On OFF output 2 Legend 2 Legend A4P Extension PCB control optional Q DI Earth leakage circuit breaker R6T External indoor ambient sensor option English Translation S1P Digital power limitation input 1 S2P Digital power limitation input 2 S3P Digital...

Page 25: ...1a 2 Only for heat pump convector Only for KRTR wireless room thermostat Only for KRTW wired room thermostat 2 core 3m included signal R2T External sensor floor or ambient Only for KRTETS External indoor thermistor Electricity pulse meter input 2 Electricity pulse meter input 1 Space cooling heating On OFF output Ext heat source eg boiler Alarm Output Only for KRCS01 1 signal signal signal signal ...

Page 26: ......

Page 27: ......

Page 28: ...4P403578 1F 2018 06 Copyright 2015 Daikin ...