4 Installation

Installation manual

9

EBLQ+EDLQ011~W1
Daikin Altherma low temperature monobloc
4P522031-1 – 2018.01

NOTICE

In case an optional domestic hot water tank is installed: A
pressure  relief  valve  (field  supply)  with  an  opening
pressure  of  maximum  10  bar  must  be  installed  on  the
domestic  cold  water  inlet  connection  in  accordance  with
the applicable legislation.

4.3.2

To connect the water piping to the backup
heater

NOTICE

Do  NOT  use  excessive  force  when  connecting  the  piping.
Deformation of the piping can cause malfunctioning of the
unit.  Make  sure  that  the  tightening  torque  does  NOT
exceed 30 N•m.

1

Connect  the  water  piping  (field  supply)  to  the  water  in-  and
outlet of the backup heater.

b

a

a

Water inlet

b

Water outlet

4.3.3

To protect the water circuit against
freezing

Frost can damage the system. To prevent the hydraulic components
from  freezing,  the  software  is  equipped  with  special  frost  protection
functions, that include the activation of pump, internal heaters, and/
or backup heater operation in case of low temperatures.

However,  in  case  of  a  power  failure,  these  functions  cannot
guarantee  protection.  It  is  therefore  recommended  to  add  glycol  to
the water circuit. The required concentration depends on the lowest
expected  outdoor  temperature,  and  on  whether  you  want  to  protect
the  system  from  bursting  or  from  freezing.  To  prevent  the  system
from  freezing,  more  glycol  is  required.  Add  glycol  according  to  the
table below.

INFORMATION

▪ Protection  against  bursting:  the  glycol  will  prevent  the

piping  from  bursting,  but  NOT  the  liquid  inside  the
piping from freezing.

▪ Protection  against  freezing:  the  glycol  will  prevent  the

liquid inside the piping from freezing.

Lowest expected
outdoor
temperature

Prevent from
bursting

Prevent from
freezing

–5°C

10%

15%

–10°C

15%

25%

–15°C

20%

35%

–20°C

25%

–25°C

30%

NOTICE

▪ The  required  concentration  might  differ  depending  on

the type of glycol. ALWAYS compare the requirements
from the table above with the specifications provided by
the  glycol  manufacturer.  If  necessary,  meet  the
requirements set by the glycol manufacturer.

▪ The  added  concentration  of  glycol  should  NEVER

exceed 35%.

▪ If the liquid in the system is frozen, the pump will NOT

be  able  to  start.  Mind  that  if  you  only  prevent  the
system from bursting, the liquid inside might still freeze.

▪ In  case  of  a  power  supply  failure  or  pump  failure,  and

NO glycol was added to the system, drain the system.

▪ When  water  is  at  standstill  inside  the  system,  the

system is very likely to freeze and get damaged.

The types of glycol that can be used depend on whether the system
contains a domestic hot water tank:

If…

Then…

The system contains a domestic
hot water tank

Only use propylene glycol

(a)

The system does NOT contain a
domestic hot water tank

You can use either propylene
glycol

(a)

 or ethylene glycol

(a)

Propylene glycol, including the necessary inhibitors,
classified as Category III according to EN1717.

WARNING

Ethylene glycol is toxic.

NOTICE

Glycol  absorbs  water  from  its  environment.  Therefore  do
NOT add glycol that has been exposed to air. Leaving the
cap  off  the  glycol  container  causes  the  concentration  of
water  to  increase.  The  glycol  concentration  is  then  lower
than  assumed.  As  a  result,  the  hydraulic  components
might freeze up after all. Take preventive actions to ensure
a minimal exposure of the glycol to air.

NOTICE

▪ If overpressure occurs, the system will release some of

the liquid through the pressure relief valve. If glycol was
added to the system, take adequate measures so as to
safely recover it.

▪ In  any  case,  make  sure  that  the  flexible  hose  of  the

pressure  relief  valve  is  ALWAYS  free  to  release
pressure.  Prevent  water  from  staying  and/or  freezing
up inside the hose.

Summary of Contents for Altherma EBLQ011CAV3

Page 1: ...low temperature monobloc English Installation manual Daikin Altherma low temperature monobloc EBLQ011CAV3 EBLQ014CAV3 EBLQ016CAV3 EBLQ011CAW1 EBLQ014CAW1 EBLQ016CAW1 EDLQ011CAV3 EDLQ014CAV3 EDLQ016CAV3 EDLQ011CAW1 EDLQ014CAW1 EDLQ016CAW1 ...

Page 2: ...A B C 500 250 100 A B C E 500 250 150 1000 500 500 D 500 500 D E 1000 500 B D 250 500 B D E 250 250 400 400 400 400 400 1000 150 150 150 150 150 150 150 1000 1000 1000 500 HD HU HD HU HB HU HD HU HB HU a b c d e eB eD A B C D E HB HU HD 1 ...

Page 3: ... niitä käytetään ohjeidemme mukaisesti za předpokladu že jsou využívány v souladu s našimi pokyny odpovídají následujícím normám nebo normativním dokumentům u skladu sa slijedećim standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s našim uputama 16 17 18 19 20 21 22 23 24 25 megfelelnek az alábbi szabvány ok nak vagy egyéb irányadó dokumentum ok nak ha azokat...

Page 4: ...opy the system settings from the first to the second user interface 14 5 1 4 To copy the language set from the first to the second user interface 15 5 1 5 Quick wizard Set the system layout after first power ON 15 5 2 Basic configuration 15 5 2 1 Quick wizard Language time and date 15 5 2 2 Quick wizard Standard 15 5 2 3 Quick wizard Options 16 5 2 4 Quick wizard Capacities energy metering 17 5 2 ...

Page 5: ...35 C in domestic hot water operation mode 3 2 Preparing water piping NOTICE In case of plastic pipes make sure they are fully oxygen diffusion tight according to DIN 4726 The diffusion of oxygen into the piping can lead to excessive corrosion 3 2 1 To check the water volume and flow rate The outdoor unit has an expansion vessel of 7 litre with a factory set pre pressure of 1 bar See the installer ...

Page 6: ...um flow rate can be checked by way of the pump test check that the user interface does NOT display error 7H NOTICE When circulation in each or certain space heating loops is controlled by remotely controlled valves it is important that the minimum flow rate is guaranteed even if all valves are closed In case the minimum flow rate cannot be reached a flow error 7H will be generated no heating or op...

Page 7: ...and washers field supply as follows 150 6 2 0 350 3 4 5 3 5 5 a mm 2 6 1 5 6 M12 a Make sure not to cover the drain holes INFORMATION The recommended height of the upper protruding part of the bolts is 20 mm 20 NOTICE Fix the outdoor unit to the foundation bolts using nuts with resin washers a If the coating on the fastening area is stripped off the nuts rust easily a 4 2 2 To install the outdoor ...

Page 8: ...in places where strong wind can tilt the unit take following measure 1 Prepare 2 cables as indicated in the following illustration field supply 2 Place the 2 cables over the outdoor unit 3 Insert a rubber sheet between the cables and the outdoor unit to prevent the cables from scratching the paint field supply 4 Attach the ends of the cables and tighten them 4 3 Connecting the water piping 4 3 1 T...

Page 9: ...ing Prevent from freezing 5 C 10 15 10 C 15 25 15 C 20 35 20 C 25 25 C 30 NOTICE The required concentration might differ depending on the type of glycol ALWAYS compare the requirements from the table above with the specifications provided by the glycol manufacturer If necessary meet the requirements set by the glycol manufacturer The added concentration of glycol should NEVER exceed 35 If the liqu...

Page 10: ...ter field supply indicates a pressure of 2 0 bar 5 Purge as much air as possible from the water circuit For instructions see 6 Commissioning on page 21 6 Refill the circuit until the pressure is 2 0 bar 7 Repeat steps 5 and 6 until no more air is purged and there are no more pressure drops 8 Close the drain and fill valve 9 Disconnect the water supply hose from the drain and fill valve 4 3 5 To in...

Page 11: ...remove reposition the switch box and gain access to other components during service CAUTION Do NOT push or place redundant cable length in the unit 4 4 2 To connect the main power supply 1 Connect the main power supply as follows X1M 1 2 3 L N a b V3 1 2 3 L1 L2 L3 N X1M a W1 a Power supply cable including earth b Cable tie 4 4 3 To connect the user interface INFORMATION If control box EKCB07CAV3 ...

Page 12: ... 4C From the top a b PCB b 1 4D From the top centre a PCB b b 1 a Notch this part for the wiring to pass through with nippers etc b Secure the wiring to the front part of the casing using the wiring retainer and clamp 4 4 4 To connect the shut off valve 1 Connect the valve control cable to the appropriate terminals as shown in the illustration below NOTICE Only connect NO normal open valves NO X5M...

Page 13: ...ver NOT all settings are accessible via both methods If so the corresponding table columns in this chapter are set to N A not applicable Method Column in tables Accessing settings via the breadcrumb in the menu structure Accessing settings via the code in the overview settings Code See also To access the installer settings on page 13 5 3 Menu structure Overview installer settings on page 20 5 1 1 ...

Page 14: ... other settings 6 Push to confirm the modification of the parameter 7 At installer settings menu press to confirm the settings Installer settings The system will restart Confirm Adjust Cancel OK Result The system will restart 5 1 3 To copy the system settings from the first to the second user interface If a second user interface is connected the installer must first proceed below instructions for ...

Page 15: ...ation select Confirm layout and press Confirm layout Please confirm the system layout The system will restart and will be ready for first startup OK Cancel Confirm Adjust 5 The user interface re initialises and you can proceed the installation by setting the other applicable settings and commissioning of the system When the installer settings are changed the system will request to confirm When con...

Page 16: ...ed backup heater Backup heater EKMBUHCA3V3 can only be configured to be a 3V3 backup heater Unified backup heater EKMBUHCA9W1 can be configured in 4 ways 3V3 1 230 V 1 step of 3 kW 6V3 1 230 V 1st step 3 kW 2nd step 3 3 kW 6W1 3N 400 V 1st step 3 kW 2nd step 3 3 kW 9W1 3N 400 V 1st step 3 kW 2nd step 3 6 kW To configure the backup heater both EKMBUHCA3V3 and EKMBUHCA9W1 combine settings E 03 and 5...

Page 17: ...r sensor connected to option box EK2CB07CAV3 INFORMATION You can only connect either the remote indoor sensor or the remote outdoor sensor Code Description A 2 2 F 6 D 04 PCC by digital inputs 0 No 1 Yes 5 2 4 Quick wizard Capacities energy metering Code Description A 2 3 1 6 02 Booster heater capacity kW Code Description A 2 3 2 6 03 Backup heater capacity step 1 kW A 2 3 3 6 04 Backup heater cap...

Page 18: ...maximum modulation 0 C 10 C default 3 C Requires modulation to be enabled This is the value by which the desired leaving water temperature is increased or lowered INFORMATION When leaving water temperature modulation is enabled the weather dependent curve needs to be set to a higher position than 8 06 plus the minimum leaving water temperature setpoint required to reach a stable condition on the c...

Page 19: ...rature at the hot water taps INFORMATION There is a risk of space heating cooling capacity shortage comfort problem in case of frequent domestic hot water operation frequent and long space heating cooling interruption will happen when selecting 6 0D 0 A 4 1 Domestic hot water Type Reheat only in case of a domestic hot water tank without an internal booster heater 5 2 7 Contact helpdesk number Code...

Page 20: ...ethod Number of LWT zones Pump operation mode Power saving possible User interface location Options DHW pump External sensor Control box Option box Leaving water Main Additional Delta T source Room thermostat Room temp range Room temp offset Ext room sensor offset Operation range Space heating OFF temp Space cooling On temp Disinfection Disinfection Operation day Start time Temperature target Dura...

Page 21: ...nit The shut off valves are properly installed and fully open The pressure relief valve purges water when opened The minimum water volume is guaranteed in all conditions See To check the water volume in 3 2 Preparing water piping on page 5 If glycol was added to the system confirm the correct glycol concentration and check if glycol setting E 0D 1 NOTICE Make sure glycol setting E 0D matches the l...

Page 22: ...e sure the room temperature control the leaving water temperature control and the domestic hot water control are turned OFF via the user interface 3 Go to A 7 4 Installer settings Commissioning Actuator test run 4 Select an actuator and press Example Pump 5 Select OK and press Result The actuator test run starts It automatically stops when finished To stop it manually press select OK and press Pos...

Page 23: ...ges 2 Press for more than 5 seconds 8 Technical data A subset of the latest technical data is available on the regional Daikin website publicly accessible The full set of latest technical data is available on the Daikin extranet authentication required 8 1 Piping diagram Outdoor unit M t R5T t R3T t R4T 1 1 2 3 4 5 6 7 8 9 12 28 13 29 16 20 18 17 26 27 21 24 25 32 33 24 23 31 36 14 26 32 16 15 V3 ...

Page 24: ...Factory setting of all switches OFF 4 Legend A1P Printed circuit board main A2P V3 only Printed circuit board service A2P W1 only Printed circuit board inverter A3P Printed circuit board noise filter A4P V3 only Printed circuit board communication BS1 BS4 A2P Push button switch C1 C4 A1P V3 only Capacitor C1 C3 A2P W1 only Capacitor DS1 A2P DIP switch E1H Bottom plate heater E1HC Crankcase heater ...

Page 25: ... hydro switch box Use normal kWh rate power supply for hydro switch box A1P Main PCB A2P Current loop PCB English Translation B1L Flow sensor E11H Flextube heater 15 6 W E12H Expansion vessel heater 50 W E13H PHE heater 50 W E14H Internal pipe heater 1 50 W E15H Internal pipe heater 2 33 W F1U A1P Fuse T5 A 250V K R A1P Magnetic relay M1P Main supply pump Q4DI Earth leakage circuit breaker R1T Out...

Page 26: ...ackup heater F1T F2T Thermal fuse backup heater F1U Fuse T 5 A 500 V backup heater option K1M Contactor backup heater step 1 English Translation K1R Relay backup heater step 1 K2M Contactor backup heater step 2 only for 9W K2R Relay backup heater step 2 only for 9W K5M Safety contactor backup heater only for 9W Q1DI Earth leakage circuit breaker Q1L Thermal protector backup heater R2T Outlet backu...

Page 27: ...oom thermostat Only for KRTW wired room thermostat 2 core 3m included signal R2T External sensor floor or ambient Only for KRTETS External indoor thermistor Electricity pulse meter input 2 Electricity pulse meter input 1 Space cooling heating On OFF output Ext heat source eg boiler Alarm Output Only for KRCS01 1 3 core communication 3 core Power supply Optional part Domestic hot water tank Only fo...