5 Configuration

Installation manual

13

EBLQ+EDLQ011~W1
Daikin Altherma low temperature monobloc
4P522031-1 – 2018.01

X2M

X8M

8 9

1~

M

M2P

X5M

X3M

3 4

5

Configuration

5.1

Overview: Configuration

This  chapter  describes  what  you  have  to  do  and  know  to  configure
the system after it is installed.

NOTICE

The  explanation  about  the  configuration  in  this  chapter
gives  you  ONLY  basic  explanations.  For  more  detailed
explanation  and  background  information,  see  the  installer
reference guide.

Why

If you do NOT configure the system correctly, it might NOT work as
expected. The configuration influences the following:

▪ The calculations of the software

▪ What you can see on and do with the user interface

How

You can configure the system via the user interface.

First time – Quick wizard.

 When you turn ON the user interface

for the first time (via the indoor unit), a quick wizard starts to help
you configure the system.

Afterwards.

  If  necessary,  you  can  make  changes  to  the

configuration afterwards.

INFORMATION

When the installer settings are changed, the user interface
will  request  to  confirm.  When  confirmed,  the  screen  will
shortly  turn  OFF  and  "busy"  will  be  displayed  for  several
seconds.

Accessing settings – Legend for tables

You  can  access  the  installer  settings  using  two  different  methods.
However,  NOT  all  settings  are  accessible  via  both  methods.  If  so,
the  corresponding  table  columns  in  this  chapter  are  set  to  N/A  (not
applicable).

Method

Column in tables

Accessing settings via the breadcrumb in the

menu structure

.

#

Accessing settings via the code in the

overview settings

.

Code

See also:

"To access the installer settings" on page 13

"5.3 Menu structure: Overview installer settings" on page 20

5.1.1

To connect the PC cable to the switch box

Prerequisite: 

The EKPCCAB kit is required.

1

Connect the cable with USB connection to your PC.

2

Connect the plug of the cable to X10A on A1P of the switch box
of  the  outdoor  unit,  or  to  X12A  on  A4P  of  the  switch  box  of
control box EKCB07CAV3.

X12A

A4P

X10A

A1P

A

B

A

Outdoor unit switch box

B

Control box switch box

3

Pay special attention to the position of the plug!

2

3

4

5

H J

ST

NOTICE

Another  cable  is  already  connected  to  X10A.  To  connect
the  PC  cable  to  X10A,  therefore  temporarily  disconnect
this other cable. Do NOT forget to reconnect it afterwards.

5.1.2

To access the most used commands

To access the installer settings

1

Set the user permission level to Installer.

2

Go to [A]: 

 > Installer settings.

To access the overview settings

1

Set the user permission level to Installer.

2

Go to [A.8]: 

 > Installer settings > Overview settings.

To set the user permission level to Installer

1

Set the user permission level to Adv. end user.

2

Go to [6.4]: 

 > Information > User permission level.

3

Press 

 for more than 4 seconds.

Result: 

 is displayed on the home pages.

Summary of Contents for Altherma EBLQ011CAV3

Page 1: ...low temperature monobloc English Installation manual Daikin Altherma low temperature monobloc EBLQ011CAV3 EBLQ014CAV3 EBLQ016CAV3 EBLQ011CAW1 EBLQ014CAW1 EBLQ016CAW1 EDLQ011CAV3 EDLQ014CAV3 EDLQ016CAV3 EDLQ011CAW1 EDLQ014CAW1 EDLQ016CAW1 ...

Page 2: ...A B C 500 250 100 A B C E 500 250 150 1000 500 500 D 500 500 D E 1000 500 B D 250 500 B D E 250 250 400 400 400 400 400 1000 150 150 150 150 150 150 150 1000 1000 1000 500 HD HU HD HU HB HU HD HU HB HU a b c d e eB eD A B C D E HB HU HD 1 ...

Page 3: ... niitä käytetään ohjeidemme mukaisesti za předpokladu že jsou využívány v souladu s našimi pokyny odpovídají následujícím normám nebo normativním dokumentům u skladu sa slijedećim standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s našim uputama 16 17 18 19 20 21 22 23 24 25 megfelelnek az alábbi szabvány ok nak vagy egyéb irányadó dokumentum ok nak ha azokat...

Page 4: ...opy the system settings from the first to the second user interface 14 5 1 4 To copy the language set from the first to the second user interface 15 5 1 5 Quick wizard Set the system layout after first power ON 15 5 2 Basic configuration 15 5 2 1 Quick wizard Language time and date 15 5 2 2 Quick wizard Standard 15 5 2 3 Quick wizard Options 16 5 2 4 Quick wizard Capacities energy metering 17 5 2 ...

Page 5: ...35 C in domestic hot water operation mode 3 2 Preparing water piping NOTICE In case of plastic pipes make sure they are fully oxygen diffusion tight according to DIN 4726 The diffusion of oxygen into the piping can lead to excessive corrosion 3 2 1 To check the water volume and flow rate The outdoor unit has an expansion vessel of 7 litre with a factory set pre pressure of 1 bar See the installer ...

Page 6: ...um flow rate can be checked by way of the pump test check that the user interface does NOT display error 7H NOTICE When circulation in each or certain space heating loops is controlled by remotely controlled valves it is important that the minimum flow rate is guaranteed even if all valves are closed In case the minimum flow rate cannot be reached a flow error 7H will be generated no heating or op...

Page 7: ...and washers field supply as follows 150 6 2 0 350 3 4 5 3 5 5 a mm 2 6 1 5 6 M12 a Make sure not to cover the drain holes INFORMATION The recommended height of the upper protruding part of the bolts is 20 mm 20 NOTICE Fix the outdoor unit to the foundation bolts using nuts with resin washers a If the coating on the fastening area is stripped off the nuts rust easily a 4 2 2 To install the outdoor ...

Page 8: ...in places where strong wind can tilt the unit take following measure 1 Prepare 2 cables as indicated in the following illustration field supply 2 Place the 2 cables over the outdoor unit 3 Insert a rubber sheet between the cables and the outdoor unit to prevent the cables from scratching the paint field supply 4 Attach the ends of the cables and tighten them 4 3 Connecting the water piping 4 3 1 T...

Page 9: ...ing Prevent from freezing 5 C 10 15 10 C 15 25 15 C 20 35 20 C 25 25 C 30 NOTICE The required concentration might differ depending on the type of glycol ALWAYS compare the requirements from the table above with the specifications provided by the glycol manufacturer If necessary meet the requirements set by the glycol manufacturer The added concentration of glycol should NEVER exceed 35 If the liqu...

Page 10: ...ter field supply indicates a pressure of 2 0 bar 5 Purge as much air as possible from the water circuit For instructions see 6 Commissioning on page 21 6 Refill the circuit until the pressure is 2 0 bar 7 Repeat steps 5 and 6 until no more air is purged and there are no more pressure drops 8 Close the drain and fill valve 9 Disconnect the water supply hose from the drain and fill valve 4 3 5 To in...

Page 11: ...remove reposition the switch box and gain access to other components during service CAUTION Do NOT push or place redundant cable length in the unit 4 4 2 To connect the main power supply 1 Connect the main power supply as follows X1M 1 2 3 L N a b V3 1 2 3 L1 L2 L3 N X1M a W1 a Power supply cable including earth b Cable tie 4 4 3 To connect the user interface INFORMATION If control box EKCB07CAV3 ...

Page 12: ... 4C From the top a b PCB b 1 4D From the top centre a PCB b b 1 a Notch this part for the wiring to pass through with nippers etc b Secure the wiring to the front part of the casing using the wiring retainer and clamp 4 4 4 To connect the shut off valve 1 Connect the valve control cable to the appropriate terminals as shown in the illustration below NOTICE Only connect NO normal open valves NO X5M...

Page 13: ...ver NOT all settings are accessible via both methods If so the corresponding table columns in this chapter are set to N A not applicable Method Column in tables Accessing settings via the breadcrumb in the menu structure Accessing settings via the code in the overview settings Code See also To access the installer settings on page 13 5 3 Menu structure Overview installer settings on page 20 5 1 1 ...

Page 14: ... other settings 6 Push to confirm the modification of the parameter 7 At installer settings menu press to confirm the settings Installer settings The system will restart Confirm Adjust Cancel OK Result The system will restart 5 1 3 To copy the system settings from the first to the second user interface If a second user interface is connected the installer must first proceed below instructions for ...

Page 15: ...ation select Confirm layout and press Confirm layout Please confirm the system layout The system will restart and will be ready for first startup OK Cancel Confirm Adjust 5 The user interface re initialises and you can proceed the installation by setting the other applicable settings and commissioning of the system When the installer settings are changed the system will request to confirm When con...

Page 16: ...ed backup heater Backup heater EKMBUHCA3V3 can only be configured to be a 3V3 backup heater Unified backup heater EKMBUHCA9W1 can be configured in 4 ways 3V3 1 230 V 1 step of 3 kW 6V3 1 230 V 1st step 3 kW 2nd step 3 3 kW 6W1 3N 400 V 1st step 3 kW 2nd step 3 3 kW 9W1 3N 400 V 1st step 3 kW 2nd step 3 6 kW To configure the backup heater both EKMBUHCA3V3 and EKMBUHCA9W1 combine settings E 03 and 5...

Page 17: ...r sensor connected to option box EK2CB07CAV3 INFORMATION You can only connect either the remote indoor sensor or the remote outdoor sensor Code Description A 2 2 F 6 D 04 PCC by digital inputs 0 No 1 Yes 5 2 4 Quick wizard Capacities energy metering Code Description A 2 3 1 6 02 Booster heater capacity kW Code Description A 2 3 2 6 03 Backup heater capacity step 1 kW A 2 3 3 6 04 Backup heater cap...

Page 18: ...maximum modulation 0 C 10 C default 3 C Requires modulation to be enabled This is the value by which the desired leaving water temperature is increased or lowered INFORMATION When leaving water temperature modulation is enabled the weather dependent curve needs to be set to a higher position than 8 06 plus the minimum leaving water temperature setpoint required to reach a stable condition on the c...

Page 19: ...rature at the hot water taps INFORMATION There is a risk of space heating cooling capacity shortage comfort problem in case of frequent domestic hot water operation frequent and long space heating cooling interruption will happen when selecting 6 0D 0 A 4 1 Domestic hot water Type Reheat only in case of a domestic hot water tank without an internal booster heater 5 2 7 Contact helpdesk number Code...

Page 20: ...ethod Number of LWT zones Pump operation mode Power saving possible User interface location Options DHW pump External sensor Control box Option box Leaving water Main Additional Delta T source Room thermostat Room temp range Room temp offset Ext room sensor offset Operation range Space heating OFF temp Space cooling On temp Disinfection Disinfection Operation day Start time Temperature target Dura...

Page 21: ...nit The shut off valves are properly installed and fully open The pressure relief valve purges water when opened The minimum water volume is guaranteed in all conditions See To check the water volume in 3 2 Preparing water piping on page 5 If glycol was added to the system confirm the correct glycol concentration and check if glycol setting E 0D 1 NOTICE Make sure glycol setting E 0D matches the l...

Page 22: ...e sure the room temperature control the leaving water temperature control and the domestic hot water control are turned OFF via the user interface 3 Go to A 7 4 Installer settings Commissioning Actuator test run 4 Select an actuator and press Example Pump 5 Select OK and press Result The actuator test run starts It automatically stops when finished To stop it manually press select OK and press Pos...

Page 23: ...ges 2 Press for more than 5 seconds 8 Technical data A subset of the latest technical data is available on the regional Daikin website publicly accessible The full set of latest technical data is available on the Daikin extranet authentication required 8 1 Piping diagram Outdoor unit M t R5T t R3T t R4T 1 1 2 3 4 5 6 7 8 9 12 28 13 29 16 20 18 17 26 27 21 24 25 32 33 24 23 31 36 14 26 32 16 15 V3 ...

Page 24: ...Factory setting of all switches OFF 4 Legend A1P Printed circuit board main A2P V3 only Printed circuit board service A2P W1 only Printed circuit board inverter A3P Printed circuit board noise filter A4P V3 only Printed circuit board communication BS1 BS4 A2P Push button switch C1 C4 A1P V3 only Capacitor C1 C3 A2P W1 only Capacitor DS1 A2P DIP switch E1H Bottom plate heater E1HC Crankcase heater ...

Page 25: ... hydro switch box Use normal kWh rate power supply for hydro switch box A1P Main PCB A2P Current loop PCB English Translation B1L Flow sensor E11H Flextube heater 15 6 W E12H Expansion vessel heater 50 W E13H PHE heater 50 W E14H Internal pipe heater 1 50 W E15H Internal pipe heater 2 33 W F1U A1P Fuse T5 A 250V K R A1P Magnetic relay M1P Main supply pump Q4DI Earth leakage circuit breaker R1T Out...

Page 26: ...ackup heater F1T F2T Thermal fuse backup heater F1U Fuse T 5 A 500 V backup heater option K1M Contactor backup heater step 1 English Translation K1R Relay backup heater step 1 K2M Contactor backup heater step 2 only for 9W K2R Relay backup heater step 2 only for 9W K5M Safety contactor backup heater only for 9W Q1DI Earth leakage circuit breaker Q1L Thermal protector backup heater R2T Outlet backu...

Page 27: ...oom thermostat Only for KRTW wired room thermostat 2 core 3m included signal R2T External sensor floor or ambient Only for KRTETS External indoor thermistor Electricity pulse meter input 2 Electricity pulse meter input 1 Space cooling heating On OFF output Ext heat source eg boiler Alarm Output Only for KRCS01 1 3 core communication 3 core Power supply Optional part Domestic hot water tank Only fo...

Page 28: ...4P522031 1 2018 01 Copyright 2018 Daikin 4P522031 1 0000000B ...

Reviews: