15
|
Technical data
Installer reference guide
199
C08AF + EHYKOMB33A
Daikin Altherma R Hybrid
4P471761-1E – 2020.10
A
room
(m
2
)
Maximum refrigerant charge in a room (m
max
) (kg)
H=500 mm,
600 mm,
700 mm
H=800 mm
H=900 mm
H=1000 mm
H=1100 mm
H=1200 mm
H=1300 mm
H=1400 mm
H=1500 mm
H=1600 mm
H=1700 mm
H=1800 mm
h=600 mm
h=700 mm
h=800 mm
h=900 mm
h=1000 mm
h=1100 mm
h=1200 mm
h=1300 mm
h=1400 mm
h=1500 mm
h=1600 mm
h=1700 mm
50
2.41
2.82
3.22
3.62
4.02
4.43
4.83
5.23
5.63
6.03
6.44
6.84
INFORMATION
▪
h=The height measured from the floor to the flare nut.
▪
H=The height measured from the floor to the bottom of the casing.
▪
For intermediate H values (i.e., when H is between 2 H values from the table),
consider the value that corresponds to the lower H value from the table. If
H=950 mm, consider the value that corresponds to "H=900 mm".
▪
In cases where H≤600 mm, h is always considered to be 600 mm, as specified in
IEC 60335-2-40:2013 A1 2016, clause GG2.
▪
For intermediate A
room
values (i.e., when A
room
is between 2 A
room
values from the
table), consider the lower A
room
value from the table. If A
room
=12.5 m
2
, consider the
value that corresponds to "A
room
=12 m
2
".
▪
Systems with a total refrigerant charge (m
c
) ≤1.842 kg are NOT subjected to any
requirements to the installation room.