7 Configuration
Installation manual
28
ELBH/X12E
Daikin Altherma 3 R MT W
4P708482-1 – 2023.03
#
Code
Item
EKHWS*D* / EKHWSU*D*
150/180
200/250/300
N/A
[4-05]
Thermistor type 0: Automatic
1: Type 1
[5.8]
[6-0E]
Maximum tank
temperature
≤60°C
≤75°C
In case of a third-party tank, we recommend to use the following
settings:
#
Code
Item
Third-party tank
Coil≥1.05 m²
Coil≥1.8 m²
[9.2.1] [E‑07]
Tank type
7:
3rd party,
small coil
8:
3rd party,
big coil
N/A
[4-05]
Thermistor type 0: Automatic
1: Type 1
[5.8]
[6-0E]
Maximum tank
temperature
≤60°C
≤75°C
Emergency
When the heat pump fails to operate, the backup heater and/or
booster heater can serve as an emergency heater. It then takes over
the heat load either automatically or by manual interaction.
▪ When
Emergency
is set to
Automatic
and a heat pump failure
occurs, the backup heater automatically takes over the heat load,
and the booster heater in the optional tank takes over the
domestic hot water production.
▪ When
Emergency
is set to
Manual
and a heat pump failure
occurs, the domestic hot water heating and space heating stops.
To manually recover it via the user interface, go to the
Malfunctioning
main menu screen and confirm whether the
backup heater and/or booster heater can take over the heat load
or not.
▪ Alternatively, when
Emergency
is set to:
▪
auto SH reduced/DHW on
, space heating is reduced but
domestic hot water is still available.
▪
auto SH reduced/DHW off
, space heating is reduced and
domestic hot water is NOT available.
▪
auto SH normal/DHW off
, space heating operates as
normally but domestic hot water is NOT available.
Similarly as in
Manual
mode, the unit can take the full load with
the backup heater and/or booster heater if the user activates this
via the
Malfunctioning
main menu screen.
To keep energy consumption low, we recommend to set
Emergency
to
auto SH reduced/DHW off
if the house is unattended for longer
periods.
#
Code
Description
[9.5.1]
[4-06]
▪ 0:
Manual
▪ 1:
Automatic
▪ 2:
auto SH reduced/DHW on
▪ 3:
auto SH reduced/DHW off
▪ 4:
auto SH normal/DHW off
INFORMATION
The auto emergency setting can be set in the menu
structure of the user interface only.
INFORMATION
If [4‑03]=1 or 3, then
Emergency
=
Manual
is not applicable
for the booster heater.
INFORMATION
If a heat pump failure occurs and
Emergency
is not set to
Automatic
(setting 1), the following functions will remain
active even if the user does NOT confirm emergency
operation:
- Room frost protection
- Underfloor heating screed dryout
However, the disinfection function will be activated ONLY if
the user confirms emergency operation via the user
interface.
Number of zones
The system can supply leaving water to up to 2 water temperature
zones. During configuration, the number of water zones must be set.
INFORMATION
Mixing station.
If your system layout contains 2 LWT
zones, you need to install a mixing station in front of the
main LWT zone.
#
Code
Description
[4.4]
[7‑02]
▪ 0:
Single zone
Only one leaving water temperature
zone:
a
a
Main LWT zone
[4.4]
[7‑02]
▪ 1:
Dual zone
Two leaving water temperature zones.
The main leaving water temperature
zone consists of the higher load heat
emitters and a mixing station to
achieve the desired leaving water
temperature. In heating:
a
b
c
a
Additional LWT zone: Highest
temperature
b
Main LWT zone: Lowest temperature
c
Mixing station