4 Unit installation
Installation manual
12
ELBH/X12E
Daikin Altherma 3 R MT W
4P708482-1 – 2023.03
2×
1
2
4
If you have to do work behind the user interface panel or upload
new software into the user interface, open the user interface
panel.
1
2
3
2×
5
Optional: Remove the user interface panel.
NOTICE
If you remove the user interface panel, also disconnect the
cables from the back of the user interface panel to prevent
damage.
2
1
2
X14Y
X1A
3
4.2.2
To close the indoor unit
1
Reinstall the user interface panel.
2
Reinstall the switch box cover and close the switch box.
3
Reinstall the front panel.
NOTICE
When closing the indoor unit cover, make sure that the
tightening torque does NOT exceed 4.1 N•m.
4.3
Mounting the indoor unit
4.3.1
To install the indoor unit
1
Fix the wall bracket (accessory) to the wall (level) with 2×
Ø8 mm bolts.
2×
30.5
30.5
220
220
(mm)
(mm)
112.5112.5
a
a
Optional: If you want to fix the unit to the wall from inside
the unit, provide an additional screw plug.
2
Lift the unit.
11 kW: 52.5 kg
16 kW: 54.5 kg
3
Attach the unit to the wall bracket:
▪ Tilt the top of the unit against the wall at the position of the
wall bracket.
▪ Slide the bracket on the back of the unit over the wall
bracket. Make sure the unit is fixed properly.
4
Optional: If you want to fix the unit to the wall from inside the
unit:
Summary of Contents for Altherma 3 R MT W