8 Troubleshooting

Operation manual

19

EB23D
Daikin Altherma 3 R F
4P643606-1B – 2022.08

8.3

Symptom: You are feeling too cold
(hot) in your living room

Possible cause

Corrective action

The desired room temperature is
too low (high).

Increase (decrease) the desired
room temperature. See 

"5.6.2 To

change the desired room
temperature"

 [

4

 12].

If the problem recurs daily, do
one of the following:

▪ Increase  (decrease)  the  room

temperature  preset  value.  See
the user reference guide.

▪ Adjust  the  room  temperature

schedule.  See 

"5.8  Schedule

screen: Example"

 [

4

 14].

The desired room temperature
cannot be reached.

Increase the desired leaving
water temperature in accordance
with the heat emitter type. See

"5.6.3 To change the desired
leaving water temperature"

 [

4

 12].

The weather-dependent curve is
set incorrectly.

Adjust the weather-dependent
curve. See 

"5.9 Weather-

dependent curve"

 [

4

 15].

8.4

Symptom: The water at the tap is
too cold

Possible cause

Corrective action

You ran out of domestic hot
water because of unusually high
consumption.

If you immediately need domestic
hot water, activate the DHW tank

Powerful operation

. However,

this consumes extra energy. See

"5.7.4 Using DHW powerful
operation"

 [

4

 13].

If the problems recurs daily, do
one of the following:

▪ Increase 

the 

DHW 

tank

temperature  preset  value.  See
the user reference guide.

▪ Adjust 

the 

DHW 

tank

temperature 

schedule.

Example: 

Program 

to

additionally 

heat 

up 

the

DHW  tank  to  a  preset  value
(

Eco  setpoint

  =  lower  tank

temperature)  during  the  day.
See 

"5.8  Schedule  screen:

Example"

 [

4

 14].

The desired DHW tank
temperature is too low.

8.5

Symptom: Heat pump failure

When  the  heat  pump  fails  to  operate,  the  backup  heater  can  serve
as  an  emergency  heater.  It  then  takes  over  the  heat  load  either
automatically or by manual interaction.

▪ When 

Emergency

  is  set  to 

Automatic

  and  a  heat  pump  failure

occurs,  the  backup  heater  automatically  takes  over  the  domestic
hot water production and space heating.

▪ When 

Emergency

  is  set  to 

Manual

  and  a  heat  pump  failure

occurs, the domestic hot water heating and space heating stops.

To  manually  recover  it  via  the  user  interface,  go  to  the

Malfunctioning

  main  menu  screen  and  confirm  whether  the

backup heater can take over the heat load or not.

▪ Alternatively, when 

Emergency

 is set to:

auto  SH  reduced/DHW  on

,  space  heating  is  reduced  but

domestic hot water is still available.

auto  SH  reduced/DHW  off

,  space  heating  is  reduced  and

domestic hot water is NOT available.

auto  SH  normal/DHW  off

,  space  heating  operates  as

normally but domestic hot water is NOT available.

Similarly  as  in 

Manual

  mode,  the  unit  can  take  the  full  load  with

the  backup  heater  if  the  user  activates  this  via  the

Malfunctioning

 main menu screen.

When  the  heat  pump  fails, 

  or 

  will  appear  on  the  user

interface.

Possible cause

Corrective action

Heat pump is damaged.

See 

"8.1 To display the help text

in case of a malfunction"

 [

4

 18].

INFORMATION

When  the  backup  heater  takes  over  the  heat  load,
electricity consumption will be considerably higher.

8.6

Symptom: The system is making
gurgling noises after
commissioning

Possible cause

Corrective action

There is air in the system.

Purge air from the system.

(a)

Incorrect hydraulic balance.

To be performed by the installer:

1

Perform  hydraulic  balancing
to  assure  that  the  flow  is
correctly 

distributed

between the emitters.

2

If  hydraulic  balancing  is  not
sufficient,  change  the  pump
limitation  settings  ([9-0D]
and [9-0E] if applicable).

Various malfunctions.

Check if 

 or 

 is displayed

on the home screen of the user
interface. See 

"8.1 To display the

help text in case of a
malfunction"

 [

4

 18] for more

information about the
malfunction.

(a)

We recommend to purge air with the air purge function of the unit
(to be performed by the installer). If you purge air from the heat
emitters or collectors, mind the following:

WARNING

Air  purging  heat  emitters  or  collectors.

  Before  you

purge  air  from  heat  emitters  or  collectors,  check  if 

  or

 is displayed on the home screen of the user interface.

▪ If not, you can purge air immediately.

▪ If  yes,  make  sure  that  the  room  where  you  want  to

purge air is sufficiently ventilated. 

Reason:

 Refrigerant

might leak into the water circuit, and subsequently into
the room when you purge air from the heat emitters or
collectors.

Summary of Contents for Altherma 3 R F EBVZ16S18D 6V Series

Page 1: ...Operation manual Daikin Altherma 3 R F English Operation manual Daikin Altherma 3 R F EBVZ16S18D 6V EBVZ16S23D 6V EBVZ16S18D 9W EBVZ16S23D 9W A B C Z 1 2 3 9...

Page 2: ...Tables to be filled in by installer 20 11 1 Configuration wizard 20 11 2 Settings menu 20 1 About this document INFORMATION This unit is a heating only model Therefore all references to cooling in thi...

Page 3: ...a safe way and understand the hazards involved Children SHALL NOT play with the appliance Cleaning and user maintenance SHALL NOT be made by children without supervision WARNING To prevent electrical...

Page 4: ...e you purge air from heat emitters or collectors check if or is displayed on the home screen of the user interface If not you can purge air immediately If yes make sure that the room where you want to...

Page 5: ...al room thermostat control the protection is NOT guaranteed 1 Go to C 2 Operation Space heating cooling Operation Space heating cooling Tank Off On C 2 2 Set operation to On or Off To change the desir...

Page 6: ...Confirm changes and proceed More information For more information see also 5 4 Turning operation ON or OFF 411 5 6 Space heating cooling control 412 5 8 Schedule screen Example 414 5 9 Weather depend...

Page 7: ...darkens Pressing any button or rotating any dial awakens the display Dials and buttons You use the dials and buttons To navigate through the screens menus and settings of the LCD screen To set values...

Page 8: ...tpoint range Heating minimum Heating maximum Cooling minimum Cooling maximum 7 2 Time date Hours Minutes Year Month Day Daylight savings time Format 7 3 Holiday Activation From Till 7 4 Quiet Activati...

Page 9: ...lure and system operates in Emergency mode or heat pump is forced off d Current date and time e Smart energy e1 Smart energy is available via solar panels or smart grid e2 Smart energy is currently be...

Page 10: ...your main zone emitter type Set the leaving water temperature for the main zone 3 Additional zone Restriction Only displayed if there are two leaving water temperature zones Shows the applicable symbo...

Page 11: ...ion Even if you turn OFF space heating cooling operation C 2 Operation Space heating cooling room frost protection operation if enabled can still activate However for leaving water temperature control...

Page 12: ...n mode to Automatic 1 Go to 4 2 Space heating cooling Operation mode schedule 2 Select a month 3 For each month select an option Reversible Not restricted Heating only Restricted Cooling only Restrict...

Page 13: ...the domestic water entering the DHW tank example 15 C At 00 00 the DHW tank is programmed to heat up the water to a preset value example Comfort 60 C During the morning you consume hot water and the D...

Page 14: ...to the other weekdays 5 Program the schedule for Saturday and copy it to Sunday 6 Give the schedule a name To go to the schedule 1 Go to 1 1 Room Schedule 2 Set scheduling to Yes 3 Go to 1 2 Room Heat...

Page 15: ...nfirm the selected character The schedule name can contain up to 15 characters 5 Confirm the new name INFORMATION Not all schedules can be renamed 5 9 Weather dependent curve 5 9 1 What is a weather d...

Page 16: ...proceed 5 9 3 Slope offset curve Slope and offset Define the weather dependent curve by its slope and offset Change the slope to differently increase or decrease the temperature of the leaving water f...

Page 17: ...Cooling WD curve Additional zone Heating 3 5 Additional zone Heating WD curve Additional zone Cooling 3 6 Additional zone Cooling WD curve Zone Go to Tank Restriction Only available to installers 5 C...

Page 18: ...his unit is mildly flammable WARNING The refrigerant inside the unit is mildly flammable but normally does NOT leak If the refrigerant leaks in the room and comes in contact with fire from a burner a...

Page 19: ...ater heating and space heating stops To manually recover it via the user interface go to the Malfunctioning main menu screen and confirm whether the backup heater can take over the heat load or not Al...

Page 20: ...Configuration wizard Setting Fill in System Indoor unit type read only Backup heater type 9 3 1 read only Domestic hot water 9 2 1 Emergency 9 5 Number of zones 4 4 Backup heater Voltage 9 3 2 Config...

Page 21: ......

Page 22: ......

Page 23: ......

Page 24: ...4P643606 1B 2022 08 Copyright 2021 Daikin 4P643606 1 B 0000000 Verantwortung f r Energie und Umwelt...

Reviews: