10
|
Configuration
Installer reference guide
148
EPRA08~W1 + ET9W
Daikin Altherma 3 H MT F
4P634887-1 – 2021.03
#
Code
Description
[2.8.3]
[9-03]
Cooling minimum
:
▪
5°C~18°C
[2.8.4]
[9-02]
Cooling maximum
:
▪
18°C~22°C
Control
Define how the operation of the unit is controlled.
Control
In this control...
Leaving water
Unit operation is decided based on the leaving water
temperature regardless the actual room temperature
and/or heating or cooling demand of the room.
External room
thermostat
Unit operation is decided by the external thermostat or
equivalent (e.g. heat pump convector).
Room thermostat
Unit operation is decided based on the ambient
temperature of the dedicated Human Comfort Interface
(BRC1HHDA used as room thermostat).
#
Code
Description
[2.9]
[C‑07]
▪
0:
Leaving water
▪
1:
External room thermostat
▪
2:
Room thermostat
Thermostat type
Only applicable in external room thermostat control.
Following combinations are possible to control the unit (not applicable when
[C‑07]=0):
▪
[C‑07]=2 (
Room thermostat
)
a
b
c
a
User interface at indoor unit
b
Dedicated Human Comfort Interface (BRC1HHDA used as room thermostat) at main
zone
c
External room thermostat at additional zone
▪
[C‑07]=1 (
External room thermostat
)
a
b
c
a
User interface at indoor unit
b
External room thermostat at main zone
c
External room thermostat at additional zone
Summary of Contents for Altherma 3 H MT F
Page 274: ......
Page 275: ......
Page 276: ...4P634887 1 2021 03 Copyright 2021 Daikin Verantwortung f r Energie und Umwelt...