Daikin Altherma 3 H HT F ETVH16SU18E 6V Series Installation Manual Download Page 25

7 Configuration

Installation manual

25

ETV23E
Daikin Altherma 3 H HT F
4P644729-1E – 2023.10

NOTICE

NOT configuring the system in the following way can cause
damage  to  the  heat  emitters.  If  there  are  2  zones,  it  is
important that in heating:

▪ the  zone  with  the  lowest  water  temperature  is

configured as the main zone, and

▪ the  zone  with  the  highest  water  temperature  is

configured as the additional zone.

NOTICE

If  there  are  2  zones  and  the  emitter  types  are  wrongly
configured, water of high temperature can be sent towards
a  low  temperature  emitter  (underfloor  heating).  To  avoid
this:

▪ Install an aquastat/thermostatic valve to avoid too high

temperatures towards a low temperature emitter.

▪ Make sure you set the emitter types for the main zone

[2.7]  and  for  the  additional  zone  [3.7]  correctly  in
accordance with the connected emitter.

NOTICE

A  differential  pressure  bypass  valve  can  be  integrated  in
the  system.  Keep  in  mind  that  this  valve  might  not  be
shown on the illustrations.

Glycol Filled system

This setting gives the installer the possibility to indicate whether the
system is filled with glycol or water. This is important in case glycol is
used  to  protect  the  water  circuit  against  freezing.  If  NOT  set
correctly, the liquid in the piping can freeze.

#

Code

Description

N/A

[E-0D]

Glycol Filled system

: Is the system

filled with glycol?

▪ 0: 

No

▪ 1: 

Yes

7.2.4

Configuration wizard: Backup heater

The  backup  heater  is  adapted  to  be  connected  to  most  common
European  electricity  grids.  If  the  backup  heater  is  available,  the
voltage,  configuration  and  capacity  must  be  set  on  the  user
interface.

The  capacities  for  the  different  steps  of  the  backup  heater  must  be
set  for  the  energy  metering  and/or  power  consumption  control
feature  to  work  properly.  When  measuring  the  resistance  value  of
each heater, you can set the exact heater capacity and this will lead
to more accurate energy data.

Backup heater type

The  backup  heater  is  adapted  to  be  connected  to  most  common
European electricity grids. The type of backup heater can be viewed
but not changed.

#

Code

Description

[9.3.1]

[E‑03]

▪ 3: 

6V

Voltage

This can be set to:

230V, 1ph

230V, 3ph

#

Code

Description

[9.3.2]

[5‑0D]

▪ 0: 

230V, 1ph

▪ 1: 

230V, 3ph

Configuration

The  backup  heater  can  be  configured  in  different  ways.  It  can  be
chosen to have a 1-step only backup heater or a backup heater with
2 steps. If 2 steps, the capacity of the second step depends on this
setting.  It  can  also  be  chosen  to  have  a  higher  capacity  of  the
second step in emergency.

#

Code

Description

[9.3.3]

[4‑0A]

▪ 0: Relay 1

▪ 1: Relay 1 / Relay 1+2

▪ 2: Relay 1 / Relay 2

▪ 3: Relay 1 / Relay 2 

Emergency

 Relay

1+2

INFORMATION

Settings  [9.3.3]  and  [9.3.5]  are  linked.  Changing  one
setting influences the other. If you change one, check if the
other is still as expected.

INFORMATION

During normal operation, the capacity of the second step of
the  backup  heater  at  nominal  voltage  is  equal  to
[6‑03]+[6‑04].

INFORMATION

If  [4‑0A]=3  and  emergency  mode  is  active,  the  power
usage  of  the  backup  heater  is  maximal  and  equal  to
2×[6‑03]+[6‑04].

INFORMATION

Only for systems with integrated domestic hot water tank: If
the  storage  temperature  setpoint  is  higher  than  50°C,
Daikin  recommends  NOT  to  disable  the  backup  heater
second  step  because  it  will  have  a  big  impact  on  the
required time for the unit to heat up the domestic hot water
tank.

Capacity step 1

#

Code

Description

[9.3.4]

[6‑03]

▪ The  capacity  of  the  first  step  of  the

backup heater at nominal voltage.

Additional capacity step 2

#

Code

Description

[9.3.5]

[6‑04]

▪ The  capacity  difference  between  the

second  and  first  step  of  the  backup
heater  at  nominal  voltage.  Nominal
value  depends  on  backup  heater
configuration.

Summary of Contents for Altherma 3 H HT F ETVH16SU18E 6V Series

Page 1: ...Installation manual Daikin Altherma 3 H HT F English Installation manual Daikin Altherma 3 H HT F ETVH16SU18E 6V ETVH16SU23E 6V 1 2 3 9 A B C Z 1 2 3 9 https daikintechnicaldatahub eu...

Page 2: ...uration 22 7 1 Overview Configuration 22 7 1 1 To access the most used commands 23 7 2 Configuration wizard 23 7 2 1 Configuration wizard Language 24 7 2 2 Configuration wizard Time and date 24 7 2 3...

Page 3: ...and By Me platform is required For more information see https professional standbyme daikin eu Daikin e Care Mobile app for installers and service technicians that allows you to register configure and...

Page 4: ...be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid a hazard CAUTION Do NOT push or place redundant cable length into the unit WARNING The backup heater...

Page 5: ...ng Regulations you must verify that the following accessories are present Delivered with indoor unit Tundish 15 mm inlet 22 mm outlet Delivered with domestic hot water tank kit Pressure reducing valve...

Page 6: ...e top and slide the top panel upwards NOTICE If you remove the user interface panel also disconnect the cables from the back of the user interface panel to prevent damage 2 1 1 3 4 X14Y X1A 3 Remove t...

Page 7: ...torque does NOT exceed 4 1 N m 4 3 Mounting the indoor unit 4 3 1 To install the indoor unit 1 Lift the indoor unit from the pallet and place it on the floor Also see 3 1 2 To handle the indoor unit...

Page 8: ...m water pressure is 3 bar 0 3 MPa Provide adequate safeguards in the water circuit to ensure that the maximum pressure is NOT exceeded The minimum water pressure to operate is 1 bar 0 1 MPa Water temp...

Page 9: ...OUT to outdoor unit screw connection 1 NOTICE It is recommended to install shut off valves to domestic cold water in and domestic hot water out connections These shut off valves are field supplied How...

Page 10: ...e relief valve combination to the water mains inlet 7 Install the tundish part of the kit in a vertical position within a maximum of 600 mm away from the pressure reducing valve pressure relief valve...

Page 11: ...200 thereafter Maximum permitted equivalent length of 22 mm pipework is 9 m Each bend or elbow is equivalent to 0 8 m of pipework 5 2 3 To connect the recirculation piping Prerequisite Only required i...

Page 12: ...30 30 C 35 INFORMATION Protection against bursting the glycol will prevent the piping from bursting but NOT the liquid inside the piping from freezing Protection against freezing the glycol will preve...

Page 13: ...7 Alarm output See 6 3 6 To connect the alarm output 418 Space cooling heating operation control See 6 3 7 To connect the space cooling heating ON OFF output 418 Changeover to external heat source con...

Page 14: ...bizone kit 9 P Bizone kit for room thermostat wired or wireless In case of See Wireless room thermostat Installation manual of the wireless room thermostat Addendum book for optional equipment Wired r...

Page 15: ...ower supply and MUST be protected by the safety devices required by the applicable legislation CAUTION To guarantee the unit is completely earthed ALWAYS connect the backup heater power supply and the...

Page 16: ...OTICE Do NOT cut or remove the backup heater power supply cable 6 3 3 To connect the shut off valve INFORMATION Shut off valve usage example In case of one LWT zone and a combination of underfloor hea...

Page 17: ...User interface panel 3 Upper switch box cover 2 Connect the electricity meters cable to the appropriate terminals as shown in the illustration below A 6 5 4 3 S3S S2S B A B X5M 3 4 5 6 3 Fix the cable...

Page 18: ...between X2M 7 9 and Q1L thermal protector backup heater Do NOT change 3 Fix the cable with cable ties to the cable tie mountings 6 3 7 To connect the space cooling heating ON OFF output Wires 2 1 0 75...

Page 19: ...ppropriate terminals as shown in the illustration below A X1 X2 L N B A B A4P X2M X1 a X2 a Installation of EKRP1HBAA is required 3 Fix the cable with cable ties to the cable tie mountings 6 3 9 To co...

Page 20: ...ermostat stop error 8H 03 will occur 6 3 11 To connect a Smart Grid This topic describes 2 possible ways to connect the indoor unit to a Smart Grid In case of low voltage Smart Grid contacts In case o...

Page 21: ...K1A L N L N STEP 3 a b c d e f STEP 1 STEP 2 A1 A2 4 3 2 1 X10M K2A A1 A2 2 1 STEP 1 Smart Grid relay kit installation STEP 2 Low voltage connections STEP 3 High voltage connections 1 High voltage Sma...

Page 22: ...o and know to configure the system after it is installed NOTICE This chapter explains only the basic configuration For more detailed explanation and background information see the installer reference...

Page 23: ...ngs can be configured via the menu structure If for any reason it is required to change a setting using the overview settings then the overview settings can be accessed as follows 1 Set the user permi...

Page 24: ...the user interface go to the Malfunctioning main menu screen and confirm whether the backup heater can take over the heat load or not Alternatively when Emergency is set to auto SH reduced DHW on spac...

Page 25: ...n control feature to work properly When measuring the resistance value of each heater you can set the exact heater capacity and this will lead to more accurate energy data Backup heater type The backu...

Page 26: ...hermostat Unit operation is decided by the external thermostat or equivalent e g heat pump convector Room thermostat Unit operation is decided based on the ambient temperature of the dedicated Human C...

Page 27: ...ction function To set the heat pump ON hysteresis Code Description 5 9 6 00 Heat pump ON hysteresis 2 C 40 C Settings for Schedule only mode and Schedule reheat mode Comfort setpoint Only applicable w...

Page 28: ...ailable for Main zone Heating Main zone Cooling Additional zone Heating Additional zone Cooling Tank only available to installers INFORMATION To operate weather dependent correctly configure the setpo...

Page 29: ...define the setpoint mode To use the weather dependent curve you need to define the correct setpoint mode Go to setpoint mode Set the setpoint mode to Main zone Heating 2 4 Main zone Setpoint mode WD h...

Page 30: ...menus The most important settings are presented here 7 4 1 Main zone Ext thermostat type Only applicable in external room thermostat control NOTICE If an external room thermostat is used the external...

Page 31: ...rical heaters Limit setting kW Enable room buffering Allow heater Allow pump 9 Installer settings Configuration wizard Domestic hot water Backup heater Emergency Balancing Water pipe freeze prevention...

Page 32: ...nce guide The indoor unit is properly mounted The outdoor unit is properly mounted The following field wiring has been carried out according to this document and the applicable legislation Between the...

Page 33: ...start the measurement will be successful Before 30 min from start the measurement might be unsuccessful If the measurement is successful the logic to activate the backup heater will use a timeframe tu...

Page 34: ...r to keep it for future reference Inform the user that he can find the complete documentation at the URL mentioned earlier in this manual Explain the user how to properly operate the system and what t...

Page 35: ...ter coming out of the relief valve open the valve until the discharged water does NOT contain dirt anymore flush the system It is recommended to do this maintenance more frequently Pressure relief val...

Page 36: ...Temperature and pressure relief valve Check for correct operation of the temperature and pressure relief valve Manually operate the temperature and pressure relief valve to ensure free water flow thr...

Page 37: ...can thoroughly clean it Then you need to do as follows 10 6 1 To remove the water filter 437 10 6 2 To clean the water filter in case of trouble 438 10 6 3 To install the water filter 438 10 6 1 To r...

Page 38: ...er housing and clean with water 4 Install the cleaned rolled up filter and strainer in the water filter housing INFORMATION Correctly install the strainer in the magnetic filter dirt separator housing...

Page 39: ...B2L B f B f A Indoor unit B Field installed a1 Space heating cooling Water IN screw connection 1 a2 Space heating cooling Water OUT screw connection 1 b1 DHW Cold water IN screw connection 3 4 b2 DHW...

Page 40: ...eless ON OFF thermostat wireless Ext thermistor External thermistor Heat pump convector Heat pump convector Add LWT Additional leaving water temperature On OFF thermostat wired ON OFF thermostat wired...

Page 41: ...stic hot water pump Electrical meters Electrical meters For HV smartgrid For high voltage Smart Grid For LV smartgrid For low voltage Smart Grid For safety thermostat For safety thermostat For smartgr...

Page 42: ...l kWh rate power supply installation Unit power supply 400 V or 230 V earth Only for normal power supply installation OUTDOOR UNIT STANDARD PART POWER SUPPLY WLAN module communication 5 core A20P J2 X...

Page 43: ...VH16SU23EA6V 30 12 kW Primary flow rate to reach primary heating power input 15 l min Standing heat loss ETVH16SU18EA6V 1 35 kWh 24h ETVH16SU23EA6V 1 76 kWh 24h Model storage capacity mass of unit whe...

Page 44: ...re set pressure of pressure reducing valve 3 5 bar Maximum primary working pressure heating 2 5 bar Maximum flow temperature 65 oC Expansion vessel pre charge pressure 3 5 bar Expansion valve setting...

Page 45: ......

Page 46: ......

Page 47: ......

Page 48: ...4P644729 1E 2023 10 Copyright 2021 Daikin 4P644729 1 E 00000006 Verantwortung f r Energie und Umwelt...

Reviews: